Download Print this page

Watson McDaniel WD600S Installation And Maintenance Manual

Thermodynamic steam trap

Advertisement

Quick Links

S T E A M T R A P S
WD600S
Thermodynamic Steam Trap
Model
Sizes
Connections
Body Material
Options
PMO
Max. Operating Pressure
TMO
Max. Operating Temperature
PMA
Max. Allowable Pressure
TMA
Max. Allowable Temperature
T Y P I C A L A P P L I C AT I O N S
DRIP, TRACER:
The WD600S thermodynamic steam trap
is commonly used as a drip trap on steam mains and steam
supply lines. Supplied with integral strainer and optional
blowdown valve to protect the trap from contamination. These
traps can be used on tracing applications; however, thermostatic
traps are normally recommended for this service. Ideal for
outdoor applications that are subject to freezing and for
superheated steam conditions.
H O W I T W O R K S
The thermodynamic trap has cyclic on-off operation with a disc
that is pushed open by incoming condensate and closes tightly
when steam tries to escape.
F E AT U R E S
Integral strainer with optional blowdown valve to protect
trap from contamination
High pressure applications up to 600 PSIG
Hardened stainless steel seat and disc for extended service
life even at high pressure
Single trap will operate over the entire pressure range of
3.5-600 PSIG (Not recommended for use below 10 PSI)
Suitable for superheated steam
Freezeproof when trap is piped in a vertical orientation
for complete drainage of condensate
Three-hole balanced discharge extends life of the seat area
Trap will function in any orientation (horizontal preferred)
428 Jones Boulevard
8
WD600S, WD600LS
1/2", 3/4", 1"
NPT
Stainless Steel 420F
Blowdown Valve, Insulation Cap
600 PSIG
750ºF
915 PSIG up to 250ºF
610ºF @ 750 PSIG
Limerick Airport Business Center
WD600S
Strainer
S A M P L E S P E C I F I C AT I O N
The steam trap shall be all stainless steel thermodynamic
type with hardened integral seat and disc with integral strainer
and blowdown valve.
I N S TA L L AT I O N
Trap can be installed in any position; however, horizontal is
preferred. Installation should include isolation valves. Do not
weld or damage can occur to the seat area.
M A I N T E N A N C E
If trap fails, close isolation valves and remove cap. Clean disc
and seating surfaces and replace cap and disc with groove side
toward seat. NOTE: Do not over tighten cap. For full maintenance
details see Installation and Maintenance Manual.
O P T I O N S
An insulation cap is available to reduce cycle rates and steam
loss in rain, snow, or cold environments. Blowdown valve, used
for flushing dirt and scale from strainer.
SB = Strainer and Blowdown Valve
L = Low Capacity
W D 6 0 0 L S
WD600LS is a low capacity version of the standard WD600S model.
3/4" WD600LS has the same capacity as the 1/2" WD600S.
Pottstown PA
19464
Tel: 610-495-5131
www.watsonmcdaniel.com
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
WD600SB
Strainer & Blowdown Valve
Fax: 610-495-5134

Advertisement

loading

Summary of Contents for Watson McDaniel WD600S

  • Page 1 W D 6 0 0 L S for complete drainage of condensate • WD600LS is a low capacity version of the standard WD600S model. Three-hole balanced discharge extends life of the seat area • Trap will function in any orientation (horizontal preferred) 3/4”...
  • Page 2 D I M E N S I O N S & W E I G H T S – M AT E R I A L S inches/pounds Size/Model Connection Weight (lbs) Body Stainless Steel, AISI 420F Series WD600S (Strainer) Disc Stainless Steel, AISI 420 1/2" WD600S 3.156 2.531 Cover Stainless Steel, AISI 416 Insulation Cap Stainless Steel, AISI 304 1/2"...

This manual is also suitable for:

Wd600ls