Maintenance; Replacement Parts - Delta Controls GR2 Installation, Operation & Maintenance Instructions Manual

Gr series
Table of Contents

Advertisement

Compound range eg –12.5 to +12.5 mbar
(Models GR3, GR6 - range BC)
For normal operation, negative pressure may be
applied to the LP port, whereby the HP port is left
open to atmosphere and the set point is between 0
and +12.5 mbar.
For reverse operation, negative pressure may be
applied to the HP port, whereby the LP port is left
open to atmosphere and the set point is between 0
and –12.5 mbar.
For positive pressures, the opposite applies.
It is recommended that the minimum setting is to be
not less than 5% of FS either side approaching zero.

MAINTENANCE

Inspections should be carried out at quarterly to
yearly
intervals
depending
conditions.
Where a terminal enclosure is fitted, isolate the unit
from process and power and remove the lid. Check
all terminals for tightness. Check that cable tails are
not
fouled
or
chafed.
condensation. Rectify as necessary.
It is recommended that instruments used to provide
an alarm are operated periodically to ensure they
are functioning correctly.
If further maintenance is required, seek advice from
DELTA CONTROLS before attempting repair or
replacement of parts.
Should the diaphragm fail the process will vent to
atmosphere via a control orifice without pressurising
the switch enclosure. Periodically ensure the vent
area does not become blocked and vent plug has
not degraded. Ensure that the vent area is not
obstructed.
THE
EQUIPMENT
USERREPLACEABLE PARTS AND IS NOT
INTENDED TO BE REPAIRED BY THE
USER. REPAIR OF THE EQUIPMENT IS
TO
BE
MANUFACTURER, OR THEIR APPROVED
AGENTS, IN ACCORDANCE WITH THE
APPLICABLE CODE OF PRACTICE.
ELECTRICAL
PRODUCTS ARE NOT SUITABLE FOR
ELECTRICAL
ISOLATE CIRCUIT TO CARRY OUT ANY
ELECTRICAL WORK.

REPLACEMENT PARTS:

Use only factory authorised parts and the fitting
instructions that are supplied.
upon
operating
Check
for
internal
CONTAINS
CARRIED
OUT
BY
ISOLATION—THESE
ISOLATION.
ALWAYS
www.delta-controls.com
NO
THE
IOM-GR-A : AUGUST 2016

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GR2 and is the answer not in the manual?

This manual is also suitable for:

Gr6Gr4Gr7Gr3

Table of Contents