Pentair TRACETEK Operating Instructions page 2

Test device for tt-ffs probe

Advertisement

Connect TT-FFS Probe Tester test
plug to cable end termination.
Are LEDs double
flashing at 2 second
intervals?
Press and hold RED test button.
Yes
Are LEDs single
flashing each second?
Battery voltage is low,
replace batteries.
Batteries are completely dead, or TT-FFS Probe
Tester is damaged. Replace batteries and repeat
this test step. If single flash test still fails, the
TT-FFS Probe Tester must be replaced.
Maintenance and Troubleshooting
Battery Powered Device
The TT-FFS Probe Tester is a powered by two "AA" Alkaline Long Life
batteries.
Under normal conditions, when the test plug is connected to the cable end
termination, the TT-FFS Probe Tester will not be flashing.
If the batteries reach a low voltage condition, the TT-FFS Probe Tester will
DOUBLE Flash at 2 second interval continuously, and maintain the DOUBLE
Flash signal for about 1 month before the battery voltage drops to an
unusable level. It does not matter if the test plug is connected to the cable
end termination, or to a TT-FFS Probe, the DOUBLE Flash signal will still
be produced as long as the battery voltage is low.
Note: If the batteries are completely dead, the TT-ffS Probe Tester
will stop its DOUBLE flash. The TT-ffS Probe Tester will not be able to
signal the low battery condition, or properly evaluate the condition of a
TT-ffS Probe.
Battery Lifetime
Two "AA" Alkaline Long Life batteries can be expected to provide service
for nominally one year. However, under extreme high and low temperature
conditions, battery service life may be reduced relative to nominal condi-
tions.
Battery lifetime also depends on how much flashing is required as part of
the TT-FFS Probe evaluation testing.
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7215
thermal.info@pentair.com
Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change
specifications without prior notice.
© 2009-2016 Pentair.
THERMAL BUILDING SOLUTIONS
No
Yes
Batteries are OK. Release RED test
button, connect TT-FFS Probe Tester to
No
TT-FFS Probe directly, or with alligator4
clip adapter.
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511
Fax: +32.16.213.603
thermal.info@pentair.com
EN-TraceTekTTFFSprobetester-IM-H58496      04/16
flashing each second?
TT-FFS Probe is in alarm
condition. Attempt reset
procedure per H58307
TT-FFS Probe care and
cleaning instruction. DO
NOT RETURN TT-FFS
PROBE TO SERVICE.
TT-FFS Probe has
internal wire damage or
connector damage. DO
NOT RETURN TT-FFS
PROBE TO SERVICE. IT
MUST BE REPLACED.
Battery Replacement
• The battery replacement for the TT-FFS Probe Tester should be
performed in a work shop or other nonhazardous location.
• Place a soft towel on the work surface.
• Position the TT-FFS Probe Tester face down, with the LEDs resting
on the soft towel.
• Loosen the four screws securing the back cover of the TT-FFS Probe
Tester, being careful not to put excessive force on the unit, which
might result in damage to the LEDs.
• Remove the back cover taking care to not lose any of the four
screws. Now the black battery cover is visible in the interior of the
TT-FFS Probe Tester.
• Loosen the small screw on the battery cover, then remove the
battery cover.
• Remove the old batteries, replace with fresh batteries and verify
batteries are installed correctly.
• Reposition the battery cover and tighten the small battery cover
screw.
• Replace the back cover of the TT-FFS Probe Tester, and tighten the
four screws evenly.
Dispose of the old batteries properly. Do not throw away
the old batteries in a garbage receptacle; take them to your locally
approved collection center for recycling.
AsIA pACIfIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2937
cn.thermal.info@pentair.com
Are LEDs single
No
Press and hold RED test button.
Yes
Are LEDs single
No
flashing each second?
Yes
Release RED test
button, TT-FFS Probe
is good. Return to
service or spares
inventory.