Mount
Refer to the System Smoke Detectors Application Guide (P/N
SPAG9101) and the Limitations of Fire Alarm Systems (P/N
800-15144) for detailed information on detector spacing,
placement zoning and special applications. Copies of this
document are available on https://mywebtech.honeywell.com/.
NOTE: Before mounting the detector permanently, conduct
Go/No Go tests (see control's instructions) to verify adequate
signal strength and adjust the device location and orientation as
necessary.
The detector can be mounted on the ceiling or on the wall (if
local ordinances permit). Select a location and mount using the
included mounting hardware.
Test
The detector should be tested immediately after installation
and at least once a year.
Recommended: To prevent unwanted alarms, notify the
Central Station that the smoke detector system is undergoing
maintenance before testing begins.
Test Mode can be activated remotely from the Controller (see
the Controller's manual), or on-site by pressing the test switch.
Tests and testing methods:
Test Switch –
-
• press and release to check circuitry functionality;
• press and hold for 3 seconds to test the sounder (the
device will emit a temporal tone).
Direct Heat Test (hair dryer)
-
Smoke Entry Test (canned smoke*)
-
Signal Strength (signal strength information is sent with
-
every communication to the panel.)
Programmed Services [Loops].
-
*Use UL/ANSI
Approved
canned smoke.
Mount
Press for 3 seconds
≥ 12" (30.48 cm)
Follow
instructions
on the can
Test