Download Print this page

Bell and Gossett EASB-JR Instruction Manual

Enhanced air separator

Advertisement

Quick Links

Warning label V56871
installed in this location.
If missing, it must be
replaced.
INSTALLER:
DESCRIPTION
The Bell &
Gossett Model EASB-JR Enhanced Air Separator
automatically removes entrained air bubbles in hydronic systems.
As fluid enters the EASB-JR, the velocity is slowed down creat-
ing a low pressure area. The air bubbles are then released from
fluid and collect on the coalescing medium. As the bubbles
coalesce, they will rise to the top of the air separator where they
can be released to atmosphere through the built-in automatic
air vent. The air separator has a bottom
accommodate a B&G diaphragm expansion tank. The compact
design and brass body construction make the EASB-JR ideal
for residential and commercial hydronic heating systems.
TECHNICAL
SPECIFICATIONS
Available Sizes:
/
" NPT
3
4
1"
NPT
1
/
" NPT
1
4
1
/
" NPT
1
2
2"
NPT
Materials:
Body
. . . . . . . . . . . . . . . . . . . . . . . .Brass
Coalescing Medium . . . . .Stainless Steel
PLEASE
LEAVE THIS MANUAL FOR THE OWNER'S USE.
/
" NPT connection to
1
2
/
" Sweat
3
4
1"
Sweat
1
/
" Sweat
1
4
INSTRUCTION MANUAL
Enhanced
Air Separator
Model EASB-JR
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual
attention to safety related instructions. When used, the safety
alert symbol means ATTENTION! BECOME ALERT! YOUR
SAFETY IS INVOLVED! FAILURE TO FOLLOW THE INSTRUC-
TIONS MAY RESULT IN A SAFETY HAZARD.
Working Pressure & Temperature Limits
(Solder
Type Limits Per ASTM Std. B16.18-1979)
FLOW-CONTROL
TYPE OF
STYLE
SOLDER
NPT
95-5
SWEAT
Tin-Antimony
A07180C
Chart A
MAXIMUM LIMITATIONS
PRESSURE PSI
TEMPERATURE °F
150
150
to draw
250
250

Advertisement

loading

Summary of Contents for Bell and Gossett EASB-JR

  • Page 1: Technical Specifications

    This safety alert symbol will be used in this manual to draw As fluid enters the EASB-JR, the velocity is slowed down creat- attention to safety related instructions. When used, the safety ing a low pressure area. The air bubbles are then released from alert symbol means ATTENTION! BECOME ALERT! YOUR fluid and collect on the coalescing medium.
  • Page 2: Installation Instructions

    (see Figure 1). Turn the cap on top of the vent counterclockwise one full turn to allow the EASB-JR to automatically remove the air from the 2. Use a torch with a sharp pointed flame. system. This is the normal operating position.