EATURES OF THE EX-5165 ............................4 3.0 I NSTALLATION OF THE 3.1 Mounting the EX-5165 Enclosure ..............................4 3.2 Wiring the EX-5165 to a Control Unit ............................. 5 EX-5165 ............................... 7 4.0 O PERATION OF THE 4.1 Start up ......................................7 4.1.1 Typical Start Up ......................................
1.2 Check Order Check, the contents of the shipment against the purchase order. Verify that the EX-5165 is received as ordered. [Each EX-5165 is labeled with its target gas.] If there are accessories on the order, ascertain that they are present. Check the contents of calibration kits.
Referred to as tap. Since the magnetic field penetrates the window, the enclosure cover is not removed to perform calibration. Three alarm points are preprogrammed into the EX-5165 sensor/transmitters. At each alarm point, an LED on the front panel is activated.
, 4-20 mA S/T for the detection of Carbon Dioxide. The S/T is meant to be used in conjunction with an appropriate power supply and controller. The ENMET EX-5165 sensor/transmitter has been designed and approved to be used in a Class I, Div. 1, Groups B, C, D, classified areas. The approval was issued by CSA International.
(1.5 ) wires to the enclosure from the power supply and controller. If the EX-5165 is installed in a hazardous location as defined by the National Electrical Code, then ALL wiring must be in accordance with the National code and any local governing codes.
Figure 3: Terminal Positions EX-5165 Sensor/Transmitter When wiring is complete, reassemble the EX-5165. Use caution when installing the overlay so as not to damage the magnetic switches. Put the cover back on the S/T Do Not apply power to the S/T without the cover in place.
ENMET 4.0 Operation of the EX-5165 It is best to have the EX-5165 transmitters powered up, operational and stable for several minutes before applying calibration or test gas to them. When the EX-5165 transmitter is first powered up, it goes through a series of momentary screens, which identify the instrument model number, serial number and software revision.
4.2 Normal Display Mode When the EX-5165 is installed as described in section 3, and in clean air, the POWER green LED is on, the display is lit and the information on the display is measurement of the target gas detected by the EX-5165. The red alarm and fault LEDs are not lit.
Hold the magnet over M switch for 2 – 5 seconds to enter the Maintenance Menu The Power/Fault LED will flash Green – Red to indicate the EX-5165 is in Maintenance Mode To exit the maintenance Menu and return to the Normal...
Span reference point for calibration. Depending on the instrument calibration, the Span gas may be the same gas that the instrument is calibrated to display, or it may be another gas, which ENMET has found to have a similar response.
Watch for the signal level to stabilize. Once the signal level has stabilized, the EX-5165 will automatically lock in the calibration data and: If the Span is successful, Cal OK appears on the display momentarily, then advances to Alarm 1. Remove calibration switch until Exit appears, then tap the S switch.
To return to Normal Gas Display: ELECT Tap M switch until EXIT is displayed Then tap S switch ELECT Figure 5: EX-5165 Maintenance Menu Flow Chart Manual Revision Date – June 14, 2017 P a g e | 12 Manual Part No. – 80003-094...
Sensors should be replaced when they can no longer be calibrated. Replacement sensor part numbers are listed in Section 6.0 of this manual. If you do not know the proper part number for your sensor, be sure to have the EX-5165 serial number available when contacting your Distributor or ENMET Technical Support.
ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour. All instruments sent to ENMET are subject to a minimum evaluation fee, even if returned unrepaired.