UT-10 & UT-20 Installation Instructions
Operational Specifications:
Timing:
1 to 620 Seconds
Voltage:
12 - 24VDC/VAC
Voltage Selection:
12VDC: Factory Preset
12VAC: Cut White Jumper (W1)
Current:
12 Volts
Relay inactive: 9mA
Relay active: 65mA
24 Volts
Relay inactive: 28mA
Relay active: 102mA
Relay Contacts:
Ratings: 5 Amp @ 24VDC
5 Amp @ 120VAC
LED Indicator:Red LED illuminated when relay is active
UT-10 Mode Selection
UT-10
ON
1
4
S2
BASE
S1
TIME
AC
WHITE
W1
_
+
T GND
R NO C NC
UT-20 Mode Selection
ON
UT-20
1
BASE
8
PULSE
S2
S1
TIME
AC
WIDTH
WHITE
W1
_
+
T GND
R NO C NC
Terminal Legend:
+ :
Positive Input Power
- :
Ground
T :
Trip
GND :
Ground
Note:
Terminals 2 & 4 (Ground) are internally connected
AlarmSaf 65A Industrial Way Wilmington, MA 01887-3499 (978) 658-6717 FAX: (978) 658-8638 Web Site: www.alarmsaf.com
24VDC: Cut Red Jumper (W2)
24VAC: Cut Red and White Jumper (W1,W2)
The timer mode is selected with
the following switches:
ON
W2
1
24V
Mode
RED
8
The timer mode is selected with
the following switches:
W2
ON
1
Mode
S1-
S1-
24V
RED
6
7
One Shot
On
On
8
Delayed Release
On
Off
Delayed Operate
Off
On
Dual Delay
Off
Off
On
Off
On
Off
R :
Reset
NO :
Normally Open Contact
C :
Common Contact
NC :
Normally Closed Contact
Trip Terminal (T)
v
Timer may be configured for a positive or negative trip signal.
}
Positive Trip: S2-1 ON (Default Setting)
}
Negative Trip: S2-1 OFF
Retriggering
v
Retrigger Mode:
}
S1-8 OFF. Repeated applications of valid trip signal, applied during timeout, will extend timing.
v
Non-Retrigger Mode:
}
S1-8 ON. Repeat applications of a trip signal, applied during timeout, will not affect timing.
Reset Terminal (R)
v
Reset is used to cancel the operation of the timer.
v
Upon application of a valid reset signal, timing ceases and the output contacts return to their originaal
position.
v
The timer may be configured for reset to operate on a positive or negative reset signal.
v
To use the reset terminal, S2-4 (Reset Enable Switch) must be OFF.
}
Reset Disabled: S2-4 ON (Default Setting)
}
Positive Reset: S2-2 ON (Default Setting)
S1-6
S1-7
S1-8
}
Negative Reset: S2-2 OFF
On
On
On
v
Note: When not using the reset terminal S2-4 should be ON.
On
Off
-
Maintained Reset
v
Off
On
Off
The reset terminal may be used to override or block a trip signal.
v
When S2-3 is ON, a continuous signal applied to the reset terminal will cause the timer to remain in reset
Off
Off
Off
mode and ignore all trip signals.
Time Set Instructions
Pulse Width Adjustment
v
On the UT-20 only, the pulse width is adjustable for the Double Pulse and Delaed Pulse functions.
v
The pulse width (P) is adjustable from 1 to 220 seconds by turning the Pulse Width potentiometer.
Base Time Adjustment
v
S1-
S2-
S2-
S2-
Timing is adjusted using the time set switches (S1-1 through S1-5) in conjunction with the Base Time
8
5
6
7
Potentiometer.
v
On
Off
Off
On
The Base Time adjustment is adjustable from 1 to 20 seconds. This establishes a starting point for the time set
-
Off
Off
On
switches as follows:
}
Set the time set switchs for a value of 1 (S1-1 = ON, S1-2 through S1-5 = OFF).
Off
Off
Off
On
}
Off
Off
Off
On
Adjust the Base Time Potentiometer for a particluar time. This is the Base Time.
v
On
On
On
Off
S1-1 through S1-5 are time multipliers valued as follows: S1-1 has a value of 1, S1-2 = 2, S1-3 = 4, S1-4 = 8
and S1-5 = 16. These are selected by placing them in the ON position. The sum of the individual switch values
On
Off
On
Off
selected equals their total value.
}
Mode Configuration
Switch
OFF Value
ON Value
S1-1
0
1
Maximum Total Value if S1-1
S1-2
0
2
through S1-5 are ON = 31.
S1-3
0
4
S1-4
0
8
S1-5
0
16
52-093
091996