EMS FireCell FCX-500-444 Installation Manual page 2

Radio hub

Advertisement

7 Connection Wiring
Loop cables should only be
passed
via
the
access
points available.
Flame
retardant
cable
glands must be used.
DO NOT leave excess cable
in the Radio Hub.
9 Configuration
The Radio Hub's programming and loop address are configured
within the menu structure of the Radio Hub.
Refer to the programming manual (Doc Ref: MK98) for details of
compatible FireCell devices and full programming information.
Specification
Operating
Temperature
-10°C to 55°C
Storage
Temperature
5°C to 30°C
Humidity
Up to 95% non-condensing
Operating Voltage
17 to 28Vdc
Typical Operating
Current
24mA@24Vdc loop powered (1st loop)
+7mA per each connected loop
IP Rating
IP54
Operating Frequency 868MHz
Output Transmitter
Power
0 - 14 dBm (0 - 25 mW)
Dimensions
270mm (W) 205mm (H) 75mm (D)
Weight
0.95kg
©2018 EMS Ltd. All rights reserved
Radio Hub Loop 1 connection
LOOP 1
IN
OUT
-
+ -
+ -
OUT
IN
Repeat for
Loop 1
Loops 2, 3
Control Panel
and 4 if used.
Free to download from
www.emsgroup.co.uk
8 Applying Power
Apply power to the Control Panel. The normal LED states for the
Radio Hub are as below:
LOOP 2
Healthy LED - Green LED will be on.
IN OUT IN OUT
-
-
-
Fault LED - Yellow LED will be off.
Sys Fault LED - Yellow LED will be off.
10 Close Radio Hub
Ensure that the Radio Hub PCB is correctly inserted and that
the PCB retaining screws are refitted.
LOOP 1
IN OUT IN OUT
-
Refit the Radio Hub lid, ensuring the LEDs are not damaged by
the light pipe when refitting.
Regulatory Information
Manufacturer
Year of
manufacture
Certification
Certification body
CPR Certificate DOP
Approved to
European Union
directives
Page 2 of 2
RF1
HEALTHY
HEALTHY
FAULT
FAULT
SYS FAULT
SYS FAULT
LOOP 1
LOOP 2
IN OUT IN OUT
IN OUT IN OUT
-
-
-
LOOP 2
IN OUT IN OUT
-
-
-
POWER
FAULT
SYSTEM
FAULT
RADIO HUB
EMS Ltd. Technology House, Herne Bay, Kent,
CT6 8JZ, United Kingdom
See devices serial number label
10
0359
0359-CPR-0028
EN54-18:2005. Fire detection and fire alarm
systems. Part 18: Input/output devices.
EN54-25:2008.
Incorporating
September 2010 and March 2012. Fire detection
and fire alarm systems. Part 25: Components using
radio links.
EMS declares that the radio equipment type FireCell
Radio
Hub
is
in
2014/53/EU. The full text of the EU declaration of
conformity is available at the following internet
address:
www.emsgroup.co.uk
2012/19/EU (WEEE directive):
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return this
product to your local supplier upon purchase of
equivalent new equipment, or dispose of it at
designated collection points. For more information
see www.recyclethis.info
RF2
RF1
RF2
RESET
BACK
LOGON
LOOP 3
LOOP 4
IN OUT IN OUT
IN OUT IN OUT
-
-
-
-
-
RESET
corrigenda
compliance
with
Directive
TSD052 Iss 17 05/09/2018
AJM

Advertisement

loading

This manual is also suitable for:

Firecell fcx-500-004