1 Pre Installation
Installation must conform to applicable local installation
!
codes and should only be installed by a fully trained
competent person.
Ensure the Radio Hub is located as per the site survey.
Refer to step 3 to ensure optimised wireless performance.
If using remote aerials with this product, refer to the Remote
Aerial Installation manual for more information.
3 Mounting Location Guidelines
For optimum wireless
p e r f o r m a n c e , t h e
following
must
observed:
Ensure the Radio Hub is not
installed within 2m of other
wireless
or
electrical
equipment (not including the
Control Panel).
Ensure the Radio Hub is not
installed within 0.6m of any
metal work.
5 Remove Cable Entry Points
Drill the cable entry
points as necessary.
= Do Not Use
= Available cable
entry points
©2018 EMS Ltd. All rights reserved
RADIO HUB
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE
2m
be
0.6m
Radio
POWER
Hub
FAULT
FIRE
Control
Panel
Fire Alarm Control
Part No

Product Description

4 Loop Radio Hub
FCX-500-004
4 Loop Radio Hub c/w Remote Aerial Facility
FCX-500-444
2 Components
1
2
3
1
4x Corner Covers
4
1x Radio Hub PCB
4 Optional PCB Removal
Remove the three circled retaining screws, before unclipping
the PCB.
HEALTHY
FAULT
SYS FAULT
LOOP 1
IN OUT IN OUT
-
-
6 Fix to the Wall
All
five
circled
fixing
positions
are available for
use.
The key hole can
also be used for
locating
and
fixing
where
required.
Page 1 of 2
2
4x Lid Screws
3
1x Radio Hub Lid
5
1x Radio Hub Back Box
RF1
RF2
RESET
BACK
LOGON
LOOP 2
LOOP 3
LOOP 4
IN OUT IN OUT
IN OUT IN OUT
IN OUT IN OUT
-
-
-
-
-
-
TSD052 Iss 17 05/09/2018
4
5
AJM

Advertisement

loading

Summary of Contents for EMS FireCell FCX-500-444

  • Page 1: Product Description

    The key hole can also be used for locating fixing where required. = Do Not Use = Available cable entry points ©2018 EMS Ltd. All rights reserved Page 1 of 2 TSD052 Iss 17 05/09/2018...
  • Page 2 Part 25: Components using Output Transmitter radio links. Power 0 - 14 dBm (0 - 25 mW) European Union EMS declares that the radio equipment type FireCell Dimensions 270mm (W) 205mm (H) 75mm (D) directives Radio compliance...

This manual is also suitable for:

Firecell fcx-500-004