Current Evolve Installation Instructions Manual page 3

Led area light
Table of Contents

Advertisement

Available languages

Available languages

2c. Square Pole Architectural Arm
This luminaire has been configured the same as 4 and
no adapter plate is needed to mount to a square pole.
Hole pattern on square pole shall be in accordance with
Figure 6.
• Place fixture against pole. Adjust nut plate
(See Figure 3.) to desired hole spacing and tighten set
screw on plate.
• For legacy diagonal bolt pattern (Figure 5.) set nut
plate to 4.58" (116 mm). For all other mounting
patterns reference Figure 2.
• Install 3/8 bolt, lock washer and washer in top hole as
shown and tighten into nut plate. (See Figure 4).
• Install 3/8 bolt, lock washer and washer below arm as
shown and tighten into nut plate.
• Torque top and bottom bolts to 25-32 ft-lbs
(34-43 N-m).
• Inspect installation to ensure fixture is secure.
DRILLING TEMPLATE SQUARE POLE MOUNTING
5.2500 in.
(133 mm)
(MIN.)
1.250 in. DIA.
(32 mm DIA.)
(HOLE)
FIGURE 6
Under no conditions should architectural arm mounting
bolts be torqued to greater than 32 foot pounds (43 N-m).
2d. Knuckle Slipfitter for 2-3/8 in. (60mm) to 3.0 in.
(76mm) OD Vertical Tenon
This luminaire has been configured to provide 0 to 45°
vertical aiming in 5° increments and mount on 2-3/8-inch
O.D. (73mm) through 3-inch O.D. (76mm) vertical pipe.
• Place slipfitter on the tenon.
• Clamp the fixture to the pipe with three set screws
(See Figure 6) Tighten set screws to 18-22 foot pounds
(24-30 N-m).
• To aim the luminaire, loosen the knuckle bolt, adjust
the aim 0 to 45°, and tighten to 45-50 ft-lbs (61-68 N-m).
• Inspect installation to ensure fixture is secure.
2e. Wall Mounted Units:
The wall mounting plate has four .438 inch clearance
holes spaced 4.375 (H) x 2.875 (V) inches for mounting.
Do not mount the unit such that the hinge side of door
is higher than the latch side of door
.438 in. DIA.
(11 mm DIA.)
(2 PLACES)
2.1960 in.
(56 mm)
4.3920 in.
(112 mm)
.656 in. (17 mm)
1.312 in. (33 mm)
WARNING
• Open wiring compartment cover loacted on the
mounting bracket. Make electrical connections and
close wiring compartment cover. Seal wall mounting
flange to the mounting surface with silicone, caulk,
or equivalent.
• To aim the luminaire loosen the knuckle bolt, adjust
the aim 0° to 45° (see Figure 7), and tighten to
45-50 ft-lbs (61-68 N-m).
Set Screws
3
WIRING
Risk of Damage or Injury: Door should be closed with
screw until fixture in final location.
• NOTE: Make all electrical connections in accordance
with the National Electrical Code and any applicable
local code requirements.
• Strain relief for incoming power must be provided in
the pole top by the customer.
Terminal Block (Optional)
• Supply Wire Type and Size, for Customer Connection
to (if option present) Terminal Block: 16 AWG (1.5mm
to 6 AWG (10mm
) Solid or Stranded.
2
Terminal Block Connections:
Terminal Board Position
L1
G
N/L2
• NOTE: Verify that supply voltage is correct by
comparing it to nameplate inside door or on carton.
• See table below for screw torques (Table 1).
Terminal Block Torque Table UL Units:
Wire Range Copper
10-16 SOL,STR
8-6 SOL,STR
STR6, SOL, STR
45° MAX
FIGURE 7
CAUTION
Supply Type
High Line
Ground
Low Line/Neutral
Aluminum
Torque (in lbs)
30
45
)
2