Download Print this page
Zeta Alarm Limited MKII-AHR Installation Manual

Zeta Alarm Limited MKII-AHR Installation Manual

Fyreye ii sandwich sounder

Advertisement

Quick Links

FYREYE II SANDWICH SOUNDER INSTALLATION MANUAL
Description
The Fyreye II Sandwich sounder base is a platform
sounder that works with the Zeta Fyreye II
protocol. The sounder can be triggered from
it`s detectors remote LED output, allowing the
sounders to be triggered individually. It can
also be triggered using the Protocol`s common
sounder group command, meaning that it can be
triggered even if it`s detector has been removed.
Connections & Address Setting
This sounder has been designed to be sandwiched
between a common base and an addressable
Fyreye II Detector. All loop cables are terminated
at the detector base, with the sounder base
clipping onto the common base. The sounder
should then be secured with it`s grub screw to
prevent unauthorised removal. The sounder does
not need to be addressed. If it is to be started
individually, it is controlled by the detector`s
remote LED output.
The sounder does not need to be addressed. If it
is to be started individually, it is controlled by the
detector`s remote LED output.
Compatible Devices & Bases
Part Number
Model
80-210
MKII-AOP
80-212
MKII-AHR
80-214
MKII-AHF
80-216
MKII-AOH
80-220
MKII-CB
Document No: GLT-203-7-1
Issue No: 1.8
FYREYE II SANDWICH SOUNDER - INSTALLATION MANUAL
Description
Fyreye MKII Addressable Optical Smoke Detector
Fyreye MKII Addressable Rate of Rise Heat Detector (A1R)
Fyreye MKII Addressable Fixed Heat Detector (A2S)
Fyreye MKII Addressable Opto-heat Detector
Fyreye MKII Common Base (Shallow)
LOOP +
LOOP -
Page 1
L2 = Loop +ve
L1IN = Loop -ve
Author: NRP Jones
Date: 15/02/2017

Advertisement

loading

Summary of Contents for Zeta Alarm Limited MKII-AHR

  • Page 1 Compatible Devices & Bases Part Number Model Description 80-210 MKII-AOP Fyreye MKII Addressable Optical Smoke Detector 80-212 MKII-AHR Fyreye MKII Addressable Rate of Rise Heat Detector (A1R) 80-214 MKII-AHF Fyreye MKII Addressable Fixed Heat Detector (A2S) 80-216 MKII-AOH Fyreye MKII Addressable Opto-heat Detector...
  • Page 2 FYREYE II SANDWICH SOUNDER - INSTALLATION MANUAL Protocol Usage The Sandwich Sounder is a listen only device, so does not send any information back to the control panel. Because of this, the sandwich sounder does not have a device type code allocation.
  • Page 3: Technical Data

    FYREYE II SANDWICH SOUNDER - INSTALLATION MANUAL Technical Data Model MKII-SSB Part Number 80-224 Operating Voltage 17 – 28V DC Quiescent Current 650µA Alarm Current 5.5mA Sound Output Aprox 85 dB (Depending on tone – See Table) Min 75dB Minimum Operating Temperature 0°C Operating Temperature -10°C to +55°C Max Humidity...
  • Page 4 FYREYE II SANDWICH SOUNDER - INSTALLATION MANUAL Other Information Like all electronic equipment, at the end of it`s working life this unit should not be disposed of in a refuse bin. It should be taken to a local reprocessing site as per the guidelines of the WEEE directive, for correct disposal. 330r/02 0832 Zeta Alarms Limited,...

This manual is also suitable for:

Mkii-cbMkii-aohMkii-ahfMkii-aop