Secutron MR-2602A Installation Instruction

Class a zone input module

Advertisement

Limited Warranty

Secutron warrants that for a period of five years from the date of purchase, the product
shall be free of defects in material and workmanship under normal use and that in ful-
fillment of any breach of such warranty, Secutron shall, at its option, repair or replace
the defective equipment upon return of the equipment to its repair depot. This warranty
applies only to defects in materials and workmanship and not to damage incurred in
shipping or handling, or damage due to causes beyond the control of Secutron such
as, lightning, excessive voltage, mechanical shock, water damage or damage arising
out of abuse, alteration or improper application of the product.
The foregoing warranty shall apply only to the original buyer, and shall be in lieu of any
and all other warranties, whether expressed or implied and of all other obligations or
liabilities on the part of Secutron. This warranty contains the entire warranty. Secutron
neither assumes responsibility for, nor authorizes any other person purporting to act on
its behalf to modify or to change this warranty, nor to assume for it any other warranty
or liability concerning this
product.
In no event shall Secutron be liable for any direct, indirect or consequential damages,
loss of anticipated profits, loss of time or any other losses incurred by the buyer in con-
nection with the purchase, installation or operation or failure of this product.

Important!

Secutron recommends that the entire system be completely tested on a regular
basis. However, despite frequent testing, and due to but not limited to criminal
tampering or electrical disruption, it is possible for this product to fail to perform
as expected.
Secutron Inc.
Tel: (905) 695-3545
25 Interchange Way
Fax: (905) 660-4113
Vaughan, Ontario, Canada
www.secutron.com
L4K 5W3
60 Industrial Parkway
Cheektowaga, NY, 14227
Tel: 1-888-SECUTRON
Fax: 888-660-4113

INSTALLATION INSTRUCTIONS

MR-2602A/2605A
Class A Zone Input Module
The MR-2602A Zone Input module converts the two zones on the MR-2602 fire alarm
control panel from Class 'B' Style 'B' to Class 'A' Style 'D'. The MR-2605A Zone Input
module converts the five zones on the MR-2605 fire alarm control panel from Class 'B'
Style 'B' to Class 'A' Style 'D'.

SPECIFICATIONS

Voltage: 24 V
(nom)
DC
Standby current: MR-2602A ... 2 mA, MR-2605A ... 5 mA
Alarm current: 60 mA (max)
Loop Resistance: 100 W (max)
Devices per zone: 20 @ 100mA each
NOTE: This component must be included in the control panel battery calcula-
tion. Refer to the Standby Battery Calculation Sheet (PN# 29005850)
included with the control panel.
MR-2602A
MR-2605A
LT-2019 Rev. A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MR-2602A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Secutron MR-2602A

  • Page 1: Specifications

    INSTALLATION INSTRUCTIONS Limited Warranty Secutron warrants that for a period of five years from the date of purchase, the product MR-2602A/2605A shall be free of defects in material and workmanship under normal use and that in ful- fillment of any breach of such warranty, Secutron shall, at its option, repair or replace Class A Zone Input Module the defective equipment upon return of the equipment to its repair depot.
  • Page 2 INSTALLATION he MR-2602A/2605A module mounts in the corresponding MR-2602/2605 fire alarm back box. Refer to Figure 1. 1. Place the supplied spacers (2) on the pem studs. 2. Insert the module header pins into the corresponding Class ‘B’ zone terminals on the main board.

This manual is also suitable for:

Mr-2605a

Table of Contents