Download Print this page

Armstrong VORTEX Installation And Operating Manual

Air separators

Advertisement

Quick Links

VO RTE X AI R S E PAR ATO R S
I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N S
Sizes: 4" to 6" – Cast Iron
8" to 12" – Fabricated C. Steel
1.0 vessel description
Armstrong va / va s Vortex Air Separators eliminate air quickly
and efficiently from heating/cooling systems. Water enters and
exits through unique tangential connections which promote a
low velocity swirling effect in the centre of the unit. Centrifu-
gal force moves the water to the outer edges of the unit and
a vortex is formed. Entrained air migrates to the eye of the
vortex (lower pressure point) and is evacuated at the top of the
separator. The water exits the unit near the bottom of the unit,
bubble free, protecting the system against the noise, corrosion
and damage associated with entrained air.
va s models are equipped with a stainless steel strainer.
2.0 construction details
Materials of construction
Shell: 4" to 6" models: Cast Iron
8" to 12" models: Fabricated steel
Strainer: Stainless steel mesh (N"× O")
Gasket: Non-asbestos
Technical data
Max. working temperature: 375°f ( 19 0°c)
Max. working pressure: 4" to 6" models: 160 psi (1103 kPa)
8" to 12" models: 165 psi (1140 kPa)
Connection type: 150# Flanged ansi (rfso)
|
MO DEL S VA / VA S
outlet
3 .0 steps & procedure
• Visually inspect the air separator for damage, which may
occur during transit.
• A manual drain can be added to help facilitate purging sedi-
ment from the air separator.
• va s models have a strainer that must be removed and
cleaned after 2 4 hours of operation.
distance required to remove strainer
size
distance inch (mm)
vas 4
16 (406)
vas 5
19 (483)
vas 6
22 (558)
vas 8
26 (660)
vas 10
29 (737)
vas 12
36 (914)
|
File No: 37.874
Date: september 22, 2016
Supersedes: 37.874
Date: december 18, 2007
npt air outlet
inlet
blind flg.
1" npt
(sq. hd. pipe plug)

Advertisement

loading

Summary of Contents for Armstrong VORTEX

  • Page 1 Centrifu- gal force moves the water to the outer edges of the unit and a vortex is formed. Entrained air migrates to the eye of the vortex (lower pressure point) and is evacuated at the top of the separator.
  • Page 2 t o r o n t o 23 bertrand avenue toronto, ontario canada m1l 2p3 +1 416 755 2291 b u f f a l o 93 east avenue north tonawanda, new york u.s.a. 14120 -6594 +1 716 693 8813 b i r m i n g h a m heywood wharf, mucklow hill halesowen, west midlands...