Rosslare SA-64-2W Installation Manual
Rosslare SA-64-2W Installation Manual

Rosslare SA-64-2W Installation Manual

2-wire photoelectric smoke detector

Advertisement

Quick Links

SA-64-2W
2-Wire Photoelectric Smoke Detector
Installation Manual

1. Introduction

The SA-64-2W is a 2-wire conventional smoke detector for fire control
panel of type Notifier SFP2404.
The smoke sensor unit can easily be plugged into or detached from the
wired base unit (AS-64B-2W) for cleaning and maintenance purposes.
The sensor chamber is engineered to sense smoke by a wide range of
combustion sources. The chamber is well protected and proofed from
insects and dust contamination. A LED indicator on the sensor unit
shows the operating status and Alarm mode.
The SA-64-2W smoke detector has a low profile and a professional and
trendy appearance.

2. Technical Specifications

2.1

Electrical Characteristics

System Voltage (Nominal)
24 VDC
Min. Operating Voltage
8.5 VDC
Max. Operating Voltage
30 VDC
Avg. Standby Current
30 µA
Sensitivity
EN: xx dB/m
UL: 0.5~4% /ft (2.5% /ft normal)
Alarm
Type: current, latch
Rate: 35 mA
Remote Annunciation
Type: N.O.
Rate (during alarm): 12/24 V, 35/70 mA max
2.2

Environmental Characteristics

Environment
Indoor
Operating Temperature Range 0°C to 37.8°C (32°F to 100°F)
Storage Temperature Range
-20°C to 70°C (-4°F to 158°F)
Operating Humidity Range
0 to 95% RH (non-condensing)
2.3

Physical Characteristics

Weight
120 g (4.23 oz)
Dimensions (L x W x H)
121.9 x 121.9 x 34 mm (4.8 x 4.8 x 1.34 in.)
Compliance with Standards
EN54-7: 2001 +A1+A2, UL268
EC certificate number: 0843-CPD-XXXX

3. Installation

3.1

Choosing a Mounting Location

A smoke detector should be installed according to NFPA (National Fire
Protection Association) Standard 72. For complete coverage in
residential units, smoke detectors should be installed in all rooms, halls,
storage areas, and basements. At the least, one detector should be
placed on each floor and in each sleeping area.
Install smoke detectors as close to the center of the ceiling as possible
or at least 10 cm (4 inches) away from any wall or corner.
Do NOT locate smoke detectors at the top of peaked or gabled
ceilings; the dead air space in these locations may prevent the unit
from detecting smoke. Avoid areas with turbulent air flow such as near
doors, fans or windows. Rapid air movement around the detector may
prevent smoke from entering the unit and affected the accuracy.
Figure 1: SA-64-2W
2.4

Modes of Operation

Operation Mode
Red LED flash indication every 10 seconds
Alarm Mode
The detector sends an alarm signal to the Fire
Control Panel. The LED remains on.
Trouble Mode
Trouble is detected by Fire Control Panel (if the EOL
resistor is removed)
2.5

Signaling and Events

Tamper Event
When the sensor is disconnected from the base or
the base unit from the ceiling.
Signaling Type
Red LED on detector
Report Types
Alarm, Tamper, Remote Annunciation
Alarm Report:
3.2

Smoke Detector Limitations

Smoke detectors will not sense a fire if the smoke does not reach
the sensor.
Some smoke detectors cannot easily be seen from every location.
Connect a remote announcement light that can be seen more
easily from other parts of the house.
Smoke from a slow fire rises slowly and may not reach the smoke
detector until the fire gets bigger.
To keep your smoke detectors working properly, be sure to
maintain the unit according manufacturer's recommendations and
UL and NFPA standards
1
Alarm Report – The detector announces an
alarm via the alarm annunciation terminal. The
event ends only by cutting power from the
panel momentarily.
Tamper Report – If detector is removed or line
was cut. Use EOL (depending on panel request)
according to Figure 4 in Section 3.5.
Remote Annunciation Report – GND on output
during event. The event ends only by cutting
power from the panel momentarily.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SA-64-2W and is the answer not in the manual?

Questions and answers

Summary of Contents for Rosslare SA-64-2W

  • Page 1: Technical Specifications

    The chamber is well protected and proofed from insects and dust contamination. A LED indicator on the sensor unit shows the operating status and Alarm mode. The SA-64-2W smoke detector has a low profile and a professional and trendy appearance. 2. Technical Specifications...
  • Page 2 Disassembly Wiring The unit arrives assembled, so you must disassemble the unit into its Easy-to-wire screw terminals provide flexible connections as shown in three pieces before you can mount it. Figure 4. To disassemble: The detector works in N.O. (Normally Open) mode. 1.
  • Page 3: Limited Warranty

    Limited Warranty The full ROSSLARE Limited Warranty Statement is available in the Quick Links section on the ROSSLARE website at www.rosslaresecurity.com. Rosslare considers any use of this product as agreement to the Warranty Terms even if you do not review them.

Table of Contents