INSIGHT SRC-C1 Manual page 2

Indoor co2 transmitter

Advertisement

Technical Speci cation
Power Supply
Operating Voltage
Power Consumption
Connection
Terminal Connectors
Sensing Method
CO2 measurement
Sampling Method
Response Time (T
Measurement Range
Repeatability
Accuracy
Pressure Dependence
Signal Outputs
Analog Outputs
Output Signal
Resolution
Maximum Load
Environment
Operation
Climatic Conditions
Temperature
Humidity
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
Standards
Product standards
Automatic electrical controls for
household and similar use
Special requirement on temperature
dependent controls
Electromagnetic compatibility for
industrial and domestic sector
Degree of Protection
Safety Class
Housing Materials
Cover
Mounting Plate
General
Dimensions (H x W x D)
Weight (including package)
Dimensions mm(inch)
21 (0.8)
Insight Control
Ph 1300 665 831
www.insightcontrol.net.au
)
1/e
conformity
EMC Directive
Low Voltage Directive
88 (3.5)
24 V AC 50/60 Hz ± 10%, 24VDC ± 10%
SELV to HD 384, Class II transformer, 48VA max
Max 2 VA
For wire 0.34...2.5 mm
Non-dispersive infrared (NDIR) waveguide
technology with ABC automatic
background calibration algorithm
Diffusion
20 sec diffusion time
0 - 5000 ppm
vol.
± 20 ppm ± 1 % of measured value
± 30 ppm ± 3 % of measured value
+ 1.6 % reading per kPa deviation from normal
pressure, 100 kPa
DC 0-10V or 0...20mA
10 Bit, 9.7 mV, 0.019.5 mA
20 mA, 500
To IEC 721-3-3
class 3 K5
0...50°C (32...122°F)
<95% R.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-30...70°C (-22...158°F)
<95% R.H. non-condensing
class 2M2
2004/108/EC
2006/95/EC
EN 60 730 –1
EN 60 730 – 2 - 9
Emissions: EN 60 730-1
Immunity: EN 60 730-1
IP30 to EN 60 529
III (IEC 60536)
Fire proof ABS plastic
Galvanized Steel
21 x 88 x 88 mm (0.8 x 3.5 x 3.5 in)
175 g (6.2 oz)
Subject to alteration
SRC- C1
2
(AWG 24...12)