1.2
External dimensions/weight
Main units
Unit: mm(inches)
(13)
(0.52")
74(2.91")
W
FX
input/output extension blocks (Connector type)
2NC
Unit: mm(inches)
(13)
W
(0.52")
74(2.91")
FX
input/output extension blocks (Terminal block type)
2NC
Unit: mm(inches)
15
W
(0.6")
74(2.91")
W:mm
Type
Model name
(inches)
FX
-16MT/D(SS)
34.0 (1.34)
0.2 (0.44)
3UC
FX
-32MT/D(SS)
34.0 (1.34)
0.2 (0.44)
3UC
Main units
FX
-64MT/D(SS)
59.7 (2.36)
0.3 (0.66)
3UC
FX
-96MT/D(SS)
85.4 (3.37)
0.35 (0.77)
3UC
FX
-16EX(-DS)
14.6 (0.57)
0.15 (0.33)
2NC
Input/output
extension
FX
-32EX(-DS)
26.2 (1.03)
0.2 (0.44)
2NC
blocks
FX
-16EYT(-DSS)
14.6 (0.57)
0.15 (0.33)
2NC
(Connector
type)
FX
-32EYT(-DSS)
26.2 (1.03)
0.2 (0.44)
2NC
Input/output
FX
-16EX-T(-DS)
20.2 (0.57)
0.15 (0.33)
2NC
extension
blocks
FX
-16EYR-T(-DS)
24.2 (0.95)
0.2 (0.44)
2NC
(Terminal
block type)
2.
General specifications and Installation
→For more details, refer to the FX
INSTALLATION
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally
before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the
product.
INSTALLATION
PRECAUTIONS
• Use the product within the generic environment specifications
described in section 2.1 of this manual.
Never use the product in areas with excessive dust, oily smoke,
conductive dusts, corrosive gas (salt air, Cl
flammable gas, vibration or impacts, or expose it to high
temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire,
malfunctions, deterioration or damage may occur.
• Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
• Install the product securely using a DIN rail or mounting
screws.
• Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to
the PC board, thereby causing nonconformities.
• When drilling screw holes or wiring, make sure that cutting and
wiring debris do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or
malfunctions.
• Be sure to remove the dust proof sheet from the PLC's
ventilation port when installation work is completed.
Failure to do so may cause fire, equipment failures or
malfunctions.
• Connect the extension cables, peripheral device cables, input/
output cables and battery connecting cable securely to their
designated connectors.
Unsecured connection may cause malfunctions.
• Turn off the power before attaching or detaching the following
MASS
devices.
Failure to do so may cause device failures or malfunctions.
(Weight):
- Peripheral devices, extension blocks, connector conversion
kg (lbs)
adapter, extension power supply units, special adapters, and
FX Series terminal blocks
- Battery and memory cassettes
Notes
• When a dust proof sheet is supplied with an extension unit/
block, keep the sheet applied to the ventilation slits during
installation and wiring work.
• To prevent temperature rise, do not install the PLC on a floor, a
ceiling or a vertical surface.
Install it horizontally on a wall as shown in section 2.2.
• Keep a space of 50mm (1.97") or more between the unit main
body and another device or structure (section 2.2 part A). Install
the unit as far away as possible from high-voltage lines, high-
voltage devices and power equipment.
2.1
Generic specifications [Main unit]
Item
Series User's Manual -
3UC
0 to 55°C (32 to 131°F) when operating and -25 to
Ambient
Hardware Edition
temperature
75°C (-13 to 167°F) when stored
Ambient
5 to 95%RH (no condensation) when operating
humidity
Vibration
resistance
When
installed
on DIN
rail
Shock
(147m/s
resistance
half-sine pulse in each direction X, Y, and Z)
, H
S, SO
or NO
),
2
2
2
2
By noise simulator at noise voltage of 1,000Vp-p,
Noise
noise width of 1µs, rise time of 1ns and period of 30 to
resistance
100Hz
Dielectric
500V AC for one
withstand
minute
voltage
Insulation
5MΩ or more by
resistance
500V DC megger
Class D grounding (grounding resistance: 100Ω or
less) <Common grounding with a heavy electrical
Grounding
system is not allowed.>
Working
Free from corrosive or flammable gas and excessive
atmosphere
conductive dusts
Working
<2000m
altitude
*1 For common grounding, refer to section 3.2.
*2 The PLC cannot be used at a pressure higher than the
atmospheric pressure to avoid damage.
2.2
Installation location
Install the PLC in an environment conforming to the generic
specifications (section 2.1), installation precautions and notes.
→For more details, refer to FX
Installation location in enclosure
Space in enclosure
Extension devices can be connected on the left and right sides of the
PLC main unit.
Specification
If you intend to add extension devices in the future, keep extra space
on the left and right sides open.
Half
Accel-
Fre-
ampli-
eration
quency
Sweep Count
tude
2
(Hz)
(m/s
)
for X, Y, Z: 10
(mm)
times
10 to 57
-
0.035
(80 min. in
each direction)
57 to
4.9
-
150
2
Acceleration, Action time: 11ms, 3 times by
Comply with JEM-1021
• Between batch of all terminals
and ground terminal
*1
*2
2.3
The main unit can be installed on a DIN46277 rail [35mm (1.38")
wide].
(It cannot be installed directly with screws.)
Series User's Manual -
3UC
2.3.1
Hardware Edition.
1) Turn the power supply OFF.
2) Push the DIN rail mounting hooks
Configuration without extension cable
A
A
A
≥50mm
A
A
(1.97")
Configuration with extension cable
A
A
A
FX
-65EC
A
0N
FX
-30EC
0N
A
Other
A
equipment
FX
-CNV-BC
2N
A
≥ 50mm
Other
A
(1.97")
equipment
Procedures for installing to and detaching from
DIN rail
Installing methods
1
of all connected units/blocks as
shown in the figure on the right
.
A
A

Advertisement

loading

This manual is also suitable for:

Melsec fx3u-4ad-pt-adpMelsec fx3u-4ad-tc-adpMelsec fx3u-232adp-mbMelsec fx3u-flrom-64Melsec fx3u-4da-adpMelsec fx3u-4ad-adp ... Show all