Download Print this page

Specifications - Camax SMARTRAIL-X835-MID User Manual

Din rail smart energy meter for single and three phase electrical systems

Advertisement

4.7.1
Pulse Rate
You can configure the number of pulses to relate to a defined
amount of Total Energy.
Please note there are limitations that need to be factored in
when setting the pulsed output. This is based upon the relay
output only being able to pulse 2 times per second.
For example, If the CT is set to 500/5A on a Single Phase
network this would generate (500Ax230V=115,000 / 1000)
115kWh which is 31W per second. A setting of 10IMP/kWh
(10 pulses per kWH) would generate 3 pulses per second.
This will exceed the 2 pulse per second limitation.
Pulse settings: 1 Pulse per: 10W (0.01) / 100W (0.1) /
1000W/1kWh (1) / 10kWh (10) / 100kWh (100) /1000kWh
(1000)
Use the
and
buttons to select the menu
option. The screen will
show the current setting.
Hold the
button to
enter the menu option, the
current selection will flash.
Use the
and
buttons to choose the desired pulse
rate. To save the new setting, hold the
button for 3
seconds until the selection stops flashing.
4.7.2
Pulse Duration
The energy monitored can be active or reactive and the pulse
width can be selected as 200, 100 or 60mS.
Use the
and
buttons to select the menu
option. The screen will
show the current setting.
Hold the
button to
enter the menu option, the
current selection will flash.
Use the
and
buttons to choose the desired pulse
rate. To save the new setting, hold the
button for 3
seconds until the selection stops flashing.
4.8
Communication
The RS485 port can be used for communication using
Modbus RTU Protocol. To configure the Modbus settings,
such as Address and Baud Rate, this is also done within the
Password-protected set up menu.
4.8.1
RS485 Address
Use the
and
buttons to select the menu
option. The screen will
show the current setting.
Hold the
button to
set the meter Address.
Range: 001(default) to 247.
Hold the
button to
confirm the selection.
Use the
and
buttons to choose the necessary
number, then press the
button to move along to the next
number. To save the new setting, hold the
button for 3
seconds until the selection stops flashing.
4.8.2
Baud Rate
Use the
and
buttons to select the menu
option. The screen will
show the current setting.
Hold the
button to
enter the menu option, the
current selection will flash.
Use the
and
buttons to select the
required option.
On completion of the entry procedure, hold the
button to
confirm the setting.
Camax UK Ltd | Unit 8 Jubilee Court, Copgrove, Harrogate, North Yorkshire. HG3 3TB, UK
01423 340 000 | www.camax.co.uk | Specifications are subject to change without notice
4.8.3
Parity
Use the
and
buttons to select the menu
option. The screen will
show the current setting.
Hold the
button to
enter the menu option, the
current selection will flash.
Use the
and
buttons to select the
required option.
Range: None (default), Odd
or Even.
On completion of the entry procedure, hold the
button
for 3 seconds until the selection stops flashing.
4.8.4
Stop bits
Use the
and
buttons to select the menu
option. The screen will
show the current setting.
Hold the
button to
enter the menu option, the
current selection will flash.
Use the
and
buttons to select the
required option.
Range: 1 (default) or 2.
On completion of the entry procedure, hold the
button
for 3 seconds until the selection stops flashing.
4.9
CLR
The meter provides a function to reset the maximum demand
value of current and power.
Use the
and
buttons to select the menu
option. The screen will
show the current setting.
Hold the
button to
enter the menu option, the
current selection will flash.
Hold the
button to confirm the setting and press
return to the main set up menu.
5

Specifications

5.1
Measured Parameters
The unit can monitor and display the following parameters
of a Single Phase Two Wire (1P2W), Three Phase Three Wire
(3P3W) or Three Phase Four Wire (3P4W) system.
5.1.1
Voltage and Current
• Phase to Neutral Voltages 100-289V AC
(not for 3P3W supplies).
• Phase to Phase Voltages 173-500V AC
(3 Phase supplies only).
• Percentage Total Voltage Harmonic Distortion (V %THD) for
each Phase to Neutral (not for 3P3W supplies).
• Percentage Total Voltage Harmonic Distortion (V% THD)
between Phases (3 Phase supplies only).
• Current %THD for each Phase.
5.1.2
Power factor and Frequency and
1
Max. Demand
• Frequency in Hz
9 10 11 12 13 14 15 16 17 18 19 20
• Instantaneous power:
• Power 0-3600 MW
• Reactive power 0-3600 MVAr
• Volt-amps 0-3600 MVA
• Maximum Demand Power since last reset
• Power factor
• Maximum Neutral Demand Current, since the last reset (for
Three Phase supplies only)
5.1.3
Energy Measurements
1
• Imported/Exported active energy
0 to 9999999.9 kWh
• Imported/Exported reactive energy
0 to 9999999.9 kVArh
• Total active energy
0 to 9999999.9 kWh
• Total reactive energy
0 to 9999999.9 kVArh
L1
5.2
Measured Inputs
N
Voltage inputs through 4-way fixed connector with 2.5mm²
stranded wire capacity. Single Phase Two Wire (1P2W), Three
Phase Three Wire (3P3W) or Three Phase Four Wire (3P4W)
unbalanced. Line frequency measured from L1 Voltage
or L3 Voltage. Three current inputs (six physical terminals) with
2.5mm² stranded wire capacity for connection of external CTs.
Nominal rated input current 5A or 1A AC RMS.
5.3
Accuracy
• Voltage
• Current
• Frequency
• Power factor
• Active power (W)
• Reactive power (VAr)
• Apparent power (VA)
• Active energy (Wh)
• Reactive energy (VARh)
• Total harmonic distortion
• Response time to step input
5.4
Auxiliary Supply
Two-way fixed connector with 2.5mm² stranded wire
capacity. 85-275V AC 50/60Hz ±10% or 120-380V DC ±20%.
Consumption <2W 10VA.
5.5
Interfaces for External Monitoring
Three interfaces are provided:
• RS485 communication channel that can be programmed
for Modbus RTU protocol
• Relay output indicating real-time measured energy.
(configurable)
• Pulse output 3200IMP/kWh (not configurable)
The Modbus configuration (baud rate etc.) and the pulse
relay output assignments (kW/kVArh) are configured through
the set-up screens.
5.5.1
Pulse Output
Opto-coupler with potential free SPST-NO Contact
(Contact rating 5-27V DC / Max current input: Imin 2mA and
Imax 27mA DC). The pulse output can be set to generate
pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width 200/100/60 mS.
5.5.2
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication
parameters can be configured from the set-up menu:
Baud rate: 2400, 4800, 9600, 19200, 38400
Parity: none (default) / odd / even
Stop bits: 1 or 2
RS485 Network Address: 3 digit number - 001-247
Modbus
Word order Hi/Lo byte order is set automatically to
normal or reverse. It cannot be configured from the
set-up menu.
5.6
Reference Conditions of Influence
to
Quantities
Influence Quantities are variables that affect measurement
errors to a minor degree. Accuracy is verified under nominal
value (within the specified tolerance) of these conditions.
• Ambient temperature
• Input waveform
• Input waveform
1
• Auxiliary supply voltage
• Auxiliary supply frequency
• Auxiliary supply waveform (if AC)
L1
• Magnetic field of external origin
N
5.7
Environment
• Operating temperature
• Storage temperature
• Relative humidity
• Altitude
2 B A
• Warm up time
• Vibration
• Shock
*Maximum operating and storage temperatures are in the
context of typical daily and seasonal variation.
5.8
Mechanics
• DIN rail dimensions
• Mounting
• Sealing
2
3
4
5
6
7
8
• Material
L
N
L
N
5.9
Declaration of Conformity
L1
We, Camax UK Ltd, declare under our sole responsibility as
L2
the distributor that the poly phase multifunction electrical
L3
energy meter "SMARTRAIL X835-MID" correspond to the
production model described in the EC-type examination
certificate and to the requirements of the Directive 2004/22/
EC EC type examination certificate number 0120/SGS0150.
Identifcation number of the NB 0120.
We, Smart Process & Control LTD, declare under our sole
responsibility as the manufacturer that the poly phase
multifunction electrical energy meter "SMARTRAIL X835-MID"
correspond to the production model described in the EC-type
examination certificate and to the requirements of the Directive
2004/22/EC EC type examination certificate number 0120/
SGS0150. Identifcation number of the NB 0120.
6
Dimensions
0·5% of range maximum
0·5% of nominal
0·2% of mid-frequency
1% of unity (0.01)
±1% of range maximum
±1% of range maximum
±1% of range maximum
Class 1 IEC 62053-21
±1% of range maximum
1% up to 31st harmonic
1s, typical, to >99% of
final reading, at 50 Hz.
7
Installation
7.1
Single phase two wires
L1
N
7.2
Three phase three wires
1
2 B A
9 10 11 12 13 14 15 16 17 18 19 20
23°C ±1°C
50 or 60Hz ±2%
Sinusoidal (distortion
2
3
4
5
6
7
8
factor < 0·005)
L
N
L
N
Nominal ±1%
Nominal ±1%
Sinusoidal (distortion
factor < 0·05)
L1
L2
Terrestrial flux
L3
7.3
Three phase four wires
-25°C to +55°C*
-40°C to +70°C*
0 to 95%,
non-condensing
Up to 3000m
1
2 B A
1 minute
10Hz to 50Hz, IEC
60068-2-6, 2g
9 10 11 12 13 14 15 16 17 18 19 20
30g in 3 planes
72 x 94.5 mm (WxH)
per DIN 43880
DIN rail (DIN 43880)
IP51 indoor
1
2
3
4
5
6
7
8
Self-extinguishing UL
L
N
L
N
94 V-0
L1
L2
L3
N
1
2 B A
9 10 11 12 13 14 15 16 17 18 19 20
1
2
3
4
5
6
7
8
L
N
L
N
1
2 B A
9 10 11 12 13 14 15 16 17 18 19 20
1
2
3
4
5
6
7
8
L
N
L
N
1
2 B A
9 10 11 12 13 14 15 16 17 18 19 20
1
2
3
4
5
6
7
8
L
N
L
N

Advertisement

loading