RFL Electronics Inc. 353 Powerville Road ● Boonton Twp., NJ 07005-9151 USA Tel: 973.334.3100 ● Fax: 973.334.3863 Email: sales@rflelect.com ● www.rflelect.com Publication Number MC3200MK10 Printed in U.S.A. August 17, 2012 • Notice RFL Electronics Inc. RFL 3200 MK-10 August 17, 2012 973.334.3100...
Page 2
This manual has been compiled and checked for accuracy. The information in this manual does not constitute a warranty of performance. RFL Electronics Inc. reserves the right to revise this manual and make changes to its contents from time to time. We assume no liability for losses incurred as a result of out-of-date or incorrect information contained in this manual.
Page 3
The following Instruction manual is for the use of maintenance and operating personnel responsible for communications in the electric utility or other facility utilizing the 3200 MK-10. All local safety rules in force at the facility where the 3200 MK-10 is installed must be strictly enforced. Only properly trained personnel may install or work on the 3200 MK-10.
Page 4
Have practical training on communications equipment. • Be comfortable working with a PC/notebook computer in a Windows operating system. • Take ESD precautions when working on or around the 3200 MK-10. • Have read and understood this manual. Trademark information: “Windows”, “Windows XP”, “Vista”...
4.5 Power and Ethernet Connections ....................4-4 Section 5. System User Interface ......................5-1 5.1 Overview............................5-1 5.2 Accessing the 3200 MK-10 through the USB Port................. 5-1 5.3 Configuring for USB User Access ....................5-2 5.4 Getting Started ..........................5-8 5.5 Starting Configuration of the 3200 MK-10 (CLI)................5-9 5.6 Web Interface ..........................5-12...
Page 6
List of Effective Pages When revisions are made to the RFL 3200 MK-10 Instruction Manual, the entire section where revisions were made is replaced. For this addition of the Instruction Manual dated August 17, 2012 the sections are dated as follows.
Page 7
Ordering Information, Decoding the Part Number Serial and part number information is located on the rear right side of the 3200 MK-10 as shown below. Sales order number Purchase order number SO 163277 PO 163287 PN MK-1022GG2 SN 09340033 Part number, see below...
Page 8
This page intentionally left blank RFL Electronics Inc. RFL 3200 MK-10 viii August 17, 2012 973.334.3100...
Section 1. Introduction - Overview of Product 1.1 Introduction RFL is proud to introduce the 3200 MK-10 Managed Ethernet Switch. Designed to operate in harsh substation environments the managed switch provides eight 10/100 Base TX RJ-45 electrical ports and two 10/100/1000 Base TX RJ-45 electrical ports with parallel SFP cages.
• 4 - 10/100 Base-TX or 100 Base-FX optical Ethernet ports. Power Supply. The Power supply converts input power from a station battery or other power source into an isolated low voltage supply used by the 3200 MK-10 circuitry. (See Section 3.3) External Power Connections.
Page 11
Alarm relays will respond to alarm conditions. The functionality can be set by the user as required and connected to their plant monitoring system. The alarm condition is displayed on the CPU LED as a red indication. (See Section 4.5.1) RFL 3200 MK-10 RFL Electronics Inc. March 1, 2012 973.334.3100...
Page 12
Introduction – Overview of Product This page intentionally left blank RFL 3200 MK-10 RFL Electronics Inc. March 1, 2012 973.334.3100...
Section 2. Safety Instructions 2.1 Important Safety Warnings Important: The RFL 3200 MK-10 Managed Ethernet Switch contains no user serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. If problems are experienced with this product please contact RFL using the contact information below for assistance.
The unit is intended to be permanently connected to supply mains by properly rated wiring in accordance with applicable local and national codes (e.g. CEC, NEC etc). Warning! The chassis of the unit shall be reliably bonded to protective ground. RFL3200 MK-10 RFL Electronics Inc. July 1, 2011 973.334.3100...
Safety Instructions Warning! The RFL 3200 MK-10 may use third party SFP Class 1 Laser Modules. These modules may be purchased through RFL or third parties. The class 1 certification originates with the SFP manufacturer, not RFL. Read the following safety information and any additional safety information included with the modules.
Page 16
Safety Instructions This page intentionally left blank RFL3200 MK-10 RFL Electronics Inc. July 1, 2011 973.334.3100...
EMI immunity and environmental requirements as mission critical protective relaying devices. The reliability of the RFL 3200 MK-10 exceeds that of a commercial Ethernet Switch by having no fans for cooling. The unit utilizes high temperature solid state components and incorporates the necessary transient and surge suppression circuitry required for electrically harsh environments.
System Description 3.2 LED Indicators Straight forward, simple LED indicators are located on the front of the RFL 3200 MK-10. The indicators give the user a constant picture of the unit’s health. Indicators on the front of the unit show: •...
Page 19
SFP -100/1000 Base Unit (typical) The integral LED indicators will continue to show status for the fiber heads however. The LED indicators are shown below. Right green LED Left green LED indicator indicator RFL3200 MK-10 RFL Electronics Inc. March 1, 2012 973.334.3100...
10 Mb/s data transfer 3.3 Power Supply The power supply for the RFL 3200 MK-10 is built onto the main circuit board and must be specified by the customer at order entry. See ordering information, decoding the part number page vii The RFL 3200 MK-10 power supply provides an isolated power source for the MK-10 circuitry, with surge suppression and voltage conversion.
3.4 User Access USB Port The user can connect to the RFL 3200 MK-10 via a USB (Universal Serial Bus) port on the front of the unit. A laptop or PC is used to communicate with and configure the unit through a CLI interface.
Page 22
System Description This page intentionally left blank RFL3200 MK-10 RFL Electronics Inc. March 1, 2012 973.334.3100...
3200-MK-10 4.3 Mounting the Equipment The RFL 3200 MK-10 is primarily designed for installation in a 1U rack, however it can also function in an office or lab environment un-mounted. Mounting ears (brackets) are provided for installation in a standard 19 inch rack. Optionally, DIN rail and wall mounting can be accommodated.
Page 24
Carefully install onto the DIN rail and snap into place. DIN Mounting Clip located on bottom of 3200 MK-10 Figure 4-2. DIN Rail Mounting RFL Electronics Inc. RFL 3200 MK-10 August 17, 2012 973.334.3100...
Installation 4.3.3 Wall Mounting Brackets are provided to mount the RFL 3200 MK-10 to a wall as shown below. Attach the brackets with the screws provided Figure 4-3. Wall Mounting Because of the many different wall materials available, RFL does not provide wall mounting hardware.
4.5 Power and Ethernet Connections The following section will give instructions on making data, alarm relay and power connections to the RFL 3200 MK-10. Before beginning the installation note the following: • Before proceeding with the connection of power and alarm relay (if required) connections to the RFL3200 MK-10 ensure that the power and alarm relay wires to be installed are disconnected at their source.
Page 27
Installation Connections are made to the compression block (TB-2) on the right rear of the 3200 MK-10 as shown below. Compression block on right rear of the 3200 MK-10 N.C. N.O. Figure 4-4. Alarm Relay Connections 1. Before proceeding with the connection of alarm relay connections to the RFL3200 MK-10 ensure that the wires to be installed are disconnected at their source.
Page 28
Power and ground connections are made to the compression block (TB-1) on the rear left of the RFL3200 MK-10 as shown below: Compression block on rear of the 3200 MK-10 Figure 4-6. Power Connections 1. Before proceeding with the connection of power to the RFL3200 MK-10 ensure that the power wires to be installed are disconnected at their source.
Page 29
2. Is the polarity of the input power correct? 3. Have the power wires been inspected as described in step 5. 4. Is the unit ventilated correctly? The RFL3200 MK-10 may now have power applied. RFL Electronics Inc. RFL 3200 MK-10 August 17, 2012 973.334.3100...
Page 30
If your RFL3200 MK-10 has Optical Fiber Heads installed, always reinstall the protective covers when the unit is not in use. Go to the next section for details on communicating with the unit and configuring your network. RFL Electronics Inc. RFL 3200 MK-10 August 17, 2012 973.334.3100...
5.2 Accessing the 3200 MK-10 through the USB Port To access the USB port on the 3200 MK-10 with a laptop computer, a USB cable is required with a type “B” connector at the Ethernet Switch end; this is not supplied by RFL.
MUST be completed to correctly configure the USB Driver. After the USB cable is connected to the 3200 MK-10 and also to the user’s computer, dialog boxes will appear. It is recommended that the user follow the steps below to configure the USB ®...
Page 33
Select "Browse my computer Select the USB Driver for driver software" and click "Next" RFL 3200 MK-10 USB CLI Access Select "Install this driver software anyway RFL Electronics Inc. RFL 3200 MK-10 March 1, 2012...
Page 34
Note: Both the "USB Serial Port" and the "RFL Serial Click "Close" Converter" should display. If they do not, return to the "Devices and Printers" dialog as shown below and double click on "RFL 3200 MK-10 USB Interface" Double click RFL 3200 MK-10 USB Interface RFL Electronics Inc.
Page 35
Software is located Select "Browse my computer Select the USB Driver and click for driver software" "Next" RFL 3200 MK-10 USB CLI Access (COM3) RFL 3200 MK-10 USB CLI Access Select "Install this driver software anyway" The USB communications are now configured.
Page 36
Note: The USB Interface may also click "Next" be downloaded from the RFL website Browse and select "USB Check OK, then Driver" from the CD or the check "Next file downloaded from the RFL website RFL Electronics Inc. RFL 3200 MK-10 March 1, 2012 973.334.3100...
Page 37
"Next" Click "Continue Anyway" Click "Finish" The USB communications are now configured. The following sections will describe how to communicate with the switch by either the CLI or Web interface. RFL Electronics Inc. RFL 3200 MK-10 March 1, 2012 973.334.3100...
5.4.1 Configuring your PC/Laptop for Static IP In a situation where both the 3200 MK-10 and the users PC are connected to the same network configuring for “Static IP” is not required as the computer will get IP address information from the DHCP server.
Check OK 5.5 Starting Configuration of the 3200 MK-10 (CLI) A default login and password are supplied. Before putting the unit into a network, we strongly recommend that the password be changed for security. (See Section 3. System Commands in...
Page 40
See important RFL 3200(config-sntp)# set sntp client time-zone -05:00 information on the following page RFL 3200(config-sntp)# exit RFL 3200(config)# exit RFL 3200# write startup-config RFL Electronics Inc. RFL 3200 MK-10 5-10 March 1, 2012 973.334.3100...
Page 41
RFL 3200# show sntp unicast-mode status RFL 3200# show sntp status For detailed information on CLI settings please refer to the RFL 3200 MK-10/16 Command Line Interface Manual MCD32KMK1016CLI. This manual is included on a customer CD shipped with the unit.
The 3200 MK-10 can be configured through a web browser such as Internet Explorer or Firefox. The 3200 MK-10 starts with a default IP address, which is also the management IP address. This IP address is essentially provided for remote management of the switch. For managing the switch through Web browsers, enter the default IP address to start accessing the switch.
Page 43
Form at the top of the screen Check box Option button Form at the bottom of the screen Note: The “Help” feature in the web pages is currently not supported. RFL Electronics Inc. RFL 3200 MK-10 5-13 March 1, 2012 973.334.3100...
Page 44
System User Interface This page intentionally left blank RFL Electronics Inc. RFL 3200 MK-10 5-14 March 1, 2012 973.334.3100...
Pollution degree 2. Rated/Working voltage 300V Stationary Vibration: IEC 60870-2-2, Class Cm (3M6) 2g Shock: IEC 60870-2-2, Class Cm 30g Free Fall: IEC 60870-2-2, Class Cm Seismic Withstand: IEC 60255-21-3, 1/.0.5g RFL Electronics Inc. RFL 3200 MK-10 August 17, 2012 973.334.3100...
When disposing of the equipment, it should be done in strict accordance with all local and national regulations for the disposal of electrical and electronic equipment. The printed circuit boards should be separated for recycling. Email: sales@rflelect.com for information on other innovative RFL products. RFL Electronics Inc. RFL 3200 MK-10 August 17, 2012 973.334.3100...