Maruson MBS-610RM Quick Manual

Maintenance bypass switch module

Advertisement

Maintenance
Bypass Switch Module
Quick Guide

1. Introduction

The module is used as an external maintenance bypass switch to provide continuous
power without shutting down the connected loads during UPS scheduled maintenance
or battery replacement. It's perfect to use in conjunction with 6K/10K VA UPS.
Rack Mount the Unit
The module can be mounted to a 19" enclosure. Please follow below chart
for rack mount installation.

2. Product Overview

Diagram 1: Rear panel View
Input/Output terminal
(Refer to diagram 2 for the details)
UPS input breaker
Maintenance bypass switch
Control output signal slot

3. Installation and Operation

V. 1.1
Inspection
Unpack the package and check the package contents. The shipping package contains:
 Maintenance bypass switch module x 1
 Quick guide x 1
 Control signal cable x 1
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged during transportation. Do not turn on the unit and notify the
carrier and dealer immediately if there is any damage or lacking of some parts.
Please keep the original package in a safe place for future use.
Initial Setup
The Installation and wiring must be performed in accordance with the local electric
laws/regulations and execute the following instructions by professional personnel.
1) Make sure the mains wire and breakers in the building are enough for the rated
capacity of UPS to avoid the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its
rated current is less than the UPS's maximum input current. Otherwise, the receptacle may be
burned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off and shut down the connected UPS.
Diagram 2: Terminal overview
Output terminal
UPS output terminal
UPS input terminal
Utility input terminal
Grounding terminal

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MBS-610RM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Maruson MBS-610RM

  • Page 1 2. Product Overview Maintenance Bypass Switch Module Diagram 1: Rear panel View Diagram 2: Terminal overview   Input/Output terminal Output terminal  (Refer to diagram 2 for the details) UPS output terminal   UPS input breaker UPS input terminal ...
  • Page 2 4. Operation 4) Prepare wires based on the following table: Transfer to Maintenance Bypass UPS Model Wire Spec (AWG) To transfer to maintenance bypass from UPS, follow the below steps: 6K/6KL Step 1: Press “OFF” button of UPS unit to transfer to bypass mode. 10K/10KL Step 2: Open the maintenance switch cover.

Table of Contents