Download Print this page

Landscape Forms Arne Installation Manual

Column mount led light

Advertisement

Quick Links

Arne
Column mount LED Light
Installation Guide
Included components
1/4‐20 x 5/8" button 
4.5m
6m
8m
10m
Pole with base plate
Tools Required
• Safety glasses
• Wrenches: 1‐1/4" for 4.5m and 6m poles or 1‐5/8" for 8m (5in/7in) and 10m (5in/8in) pole
• Wiring tools and connectors
• Proper personnel, crane or lift for hoisting unit onto anchors
• Level
• Dimming control, if required
• Hex key 5/32" for nut covers
• Twist lock photo eye, if required
• 4mm and 6mm hex keys
• 13mm wrenches
• 17mm socket wrench
Landscape Forms is not responsible for site preparation and footings.  Refer to the 
installation guide for the Arne light anchor kit for installing the anchor bolts.
CAUTION! This unit is heavy. To avoid injury or damage to the finish, we recommend using 
a crane or lift for hoisting the unit onto the anchors.
WARNING! Pole mounted luminaires must be attached either before or immediately after 
pole installation. Failure to do so may cause vibration damage to the pole and will void the 
pole warranty.
ASSEMBLE WITH CARE! To protect this finish during assembly, place unwrapped powdercoated parts on 
packaging foam or other non‐marring surface.  Do not place or slide powdercoated parts on concrete or 
other hard or textured surface – this will damage the finish causing rust to occur.  Use touch‐up paint on 
any gouges in the finish caused by assembly tools.
Twist lock receptacle,
Column mount
luminaire
bracket
Shorting cap for
Twist lock, optional
4X ‐ Nut cover with 
head cap screw
Standard
Pole  cap
INSTALLATION PROCEDURE FOR LIGHT POLE:
1.
Lift the light pole into position over the installed anchors (refer to Arne anchor kit 
installation guide) as shown in Fig. 1.  Ensure that the base plate is resting on all four 
washers.
2.
Install washer and hex nut as shown in Fig. 2.
optional
3.
Plumb and level the pole and tighten all anchors.
4.
Install luminaire. Refer to page 2 for mounting luminaire to pole.
5.
Make electrical connections. Refer to wiring diagram.
6.
Install the top cap on the pole (shipped with the pole). If the unit has a twist lock 
receptacle, assemble the receptacle and the top cap as shown in Fig. 3 and connect 
wiring before installing the top cap. 
7.
Install the nut covers as shown in Fig. 4.
For twist lock
SIDEWALK
Fig. 1 – Pole orientation
Fig. 3 – Install twist lock 
receptacle to top cap
www.landscapeforms.com
HAND HOLE
ORIENTED ON 
SIDE OPPOSITE
OF LUMINAIRE
SETBACK
Fig. 2 – Install pole
Fig. 4 – Install nut covers
Date: November 6, 2017
Ph: 800.521.2546
Page 1 of 4

Advertisement

loading

Summary of Contents for Landscape Forms Arne

  • Page 1 Arne Column mount LED Light Date: November 6, 2017 Installation Guide www.landscapeforms.com Ph: 800.521.2546 Included components INSTALLATION PROCEDURE FOR LIGHT POLE: Lift the light pole into position over the installed anchors (refer to Arne anchor kit  installation guide) as shown in Fig. 1.  Ensure that the base plate is resting on all four  washers. Twist lock receptacle, Install washer and hex nut as shown in Fig. 2. Column mount optional luminaire bracket Plumb and level the pole and tighten all anchors. Install luminaire. Refer to page 2 for mounting luminaire to pole. Make electrical connections. Refer to wiring diagram. Install the top cap on the pole (shipped with the pole). If the unit has a twist lock  Shorting cap for Twist lock, optional receptacle, assemble the receptacle and the top cap as shown in Fig. 3 and connect  wiring before installing the top cap.  4X ‐ Nut cover with  Install the nut covers as shown in Fig. 4. 1/4‐20 x 5/8” button  head cap screw Standard For twist lock 4.5m...
  • Page 2 Arne Column mount LED Light Date: November 6, 2017 Installation Guide www.landscapeforms.com Ph: 800.521.2546 OPEN GROMMET ANGULAR LOCKING EVERY 10° MAX TIGHTENING TORQUE 27 Nm MAXIMUM TIGHTENING Column mount step 3 Column mount step 4 TORQUE 27 Nm Column mount step 1 Column mount step 2 LINE‐IN POWER CORD, NOT  INCLUDED. CABLE GLAND  CABLE: MAX TIGHTENING  ACCEPTS SIZE 5‐12mm DIA TORQUE 8Nm SCREW: MAX TIGHTENING  TORQUE 6Nm DO NOT DISASSEMBLE THE LOWER PART Column mount step 5 Page 2 of 4...
  • Page 3 Arne Column mount LED Light Date: November 6, 2017 Installation Guide www.landscapeforms.com Ph: 800.521.2546 PROCEDURE FOR WIRING ARNE LED LUMINAIRES: The Arne luminaire ships fully assembled from the factory.  The wiring schematics are to be used to connect the unit to line voltage.  It is the responsibility of the installer to make sure that all connections are made in accordance with the NEC  and local building codes. Line‐in cord should be connected to the weather proof cord grip as shown.  Line‐in power cord not included. 1‐10v WIRING PLAN Page 3 of 4...
  • Page 4 Arne Column mount LED Light Date: November 6, 2017 Installation Guide www.landscapeforms.com Ph: 800.521.2546 DALI WIRING PLAN Page 4 of 4...