Download Print this page
Advantech ADAM-45101 Startup Manual
Advantech ADAM-45101 Startup Manual

Advantech ADAM-45101 Startup Manual

Rodbust isolated rs-422/485 repeater. rodbust isolated rs-232 to rs-422/485 converter

Advertisement

Quick Links

ADAM-4510I
ADAM-4520I
Packing List
Before you begin installing your module, please
make sure that the following materials have been
shipped:
1 x ADAM-4510I or ADAM-4520I
1 x DIN-rail mounting bracket (attached)
1 x ADAM-4510I/4520I Startup Manual
1 x Panel mounting bracket
If any of these items are missing/damaged, contact
your distributor or sales representative immediately.
CE/FCC Certification
ADAM-4510I and ADAM-4520I developed by
Advantech Co., Ltd. has passed the CE and FCC test
for environmental specifications. The test conditions
for passing including the equipment being operated
within an industrial enclosure. Therefore, in order to
protect the ADAM module from being damaged by
ESD, we strongly recommend that the use of CE-
compliant industrial enclosure products.
Overview
Most industrial computer systems come with RS-
232 serial ports. Though widely accepted, RS-232
has limited transmission speed, range and network-
ing capabilities. RS-422 and RS-485 standards over-
come these limitations by using differential voltage
lines for data and control signals.
ADAM-4520I is isolated converter for systems orig-
inally equipped with RS-232. It transparently con-
verts RS-232 signals into isolated RS-422 or RS-
485 signals. You don't need to change your PC's
hardware or your software. The ADAM-4520I lets
you easily build an industrial grade, long distance
communication system with standard PC hardware.
The ADAM-4510I repeaters simply amplify, or
boost, existing RS-485 signals to enable them to
cover longer distances. They extend the communi-
cation distance by 4000 ft (1200 m) or extend the
number of connected nodes by 32.
1
Startup Manual
Robust Isolated RS-422/485 Repeater
Robust Isolated RS-232 to RS-422/485 Converter
Notes
For more information on this and other Advantech
products, please visit our websites at:
http://www.advantech.com
http://www.advantech.com/eAutomation
For technical support and service:
http://www.advantech.com.tw/eservice
This manual is for ADAM-4510I and ADAM-4520I.
Part No: 2003451010 (1st Ed)
Industrial Design
Intelligent RS-485 Control
The RS-485 standard supports half-duplex commu-
nication. This means that just two wires are needed
to both transmit and receive data. Handshaking sig-
nals (such as RTS, Request to Send) are normally
used to control the direction of the data flow. A spe-
cial I/O circuit in ADAM-4510I and ADAM-4520I
automatically senses the direction of the data flow
and switches the transmission direction. No hand-
shaking signals are necessary. So you can build an
RS-485 network with just two wires. This RS-485
control is completely transparent to the user. Soft-
ware written for half-duplex RS-232 can work with-
out modification.
Isolation
ADAM-4510I and ADAM-4520I's opto-isolators
provide 3000 VDC isolation to protect the host com-
puter from ground loops and destructive voltage
spikes on the RS-485 data lines.
Surge Protection
ADAM-4510I and 4520I offer internal surge protec-
tion on their data lines. Internal high speed transient
suppressors on each data line protect the modules
from dangerous voltages levels or spikes.
Tough Industrial Design
You can power ADAM-4510I and ADAM-4520
with any unregulated power source between +10
and +48 VDC. Their industrial-grade plastic shells
can be mounted on a DIN-rail, panel or in a piggy-
backed stack. You make signal connections through
plug-in screw terminal blocks, guaranteeing easy
installation, maintenance and modification.
May 2006

Advertisement

loading

Summary of Contents for Advantech ADAM-45101

  • Page 1 The RS-485 standard supports half-duplex commu- ADAM-4510I and ADAM-4520I developed by nication. This means that just two wires are needed Advantech Co., Ltd. has passed the CE and FCC test to both transmit and receive data. Handshaking sig- for environmental specifications. The test conditions...
  • Page 2: Specifications

    Features Switch Settings • Automatic internal RS-485 bus supervision Switch Description • No external flow control signals required for RS-485 • Minimum 3000 VDC isolation DIP switches in the ADAM converter and repeater modules set the data format (number of bits) and baud •...
  • Page 3 Baud Rate Settings (SW2) ADAM-4520I RS-422/485 Converter Module RTS Control ADAM-4510I Repeater Module 1200 bps 1200 bps 2400 bps 2400 bps 4800 bps 4800 bps 9600 bps (default) 9600 bps (default) 19.2 kbps 19.2 kbps 38.4 kbps 38.4 kbps 57.6 kbps 57.6 kbps 115.2 kbps /Auto...
  • Page 4 The power cables should be selected according to the Mode Settings (SW3) number of modules connected and the length of the power lines. When using a network with long cables, Normal (default) we advise the use of thicker wire to limit the line volt- age drop.
  • Page 5 Function Diagrams ADAM-4510I Repeater ADAM-4510I Repeater Module ADAM Dimensions ADAM-4520I Converter Startup Manual...

This manual is also suitable for:

Adam-45201