MANUAL
MANUAL
TIMER TI327401
TIMER TI327401
Wachendorff Prozesstechnik GmbH & Co. KG www.wp-direkt.de
e-mail: RSS@wachendorff.de
Version 2.0
DIMENSION and INSTALLATION
DIMENSION and INSTALLATION
Front panel
cut out
28.5 x 70.5 mm
2 to
8
mm
suggested thickness
Gasket
PIXSYS
1
CN1
6
Memory card (optional)
with battery (SFUR0KIT)
1
2
3
53 mm
77 mm
7
MODIFY SETPOINT
MODIFY SETPOINT
PRESS
EFFECT
1
Display SETPOINT 1 / 2
2
Modify selected SETPOINT
OR
2a
Select the chosen digit
Modify the flashing digit of the selected setpoint
3a
O
TECHNICAL DATA
TECHNICAL DATA
Operating
Operating temperature 0-40°C, humidity 35..95uR%
temperature
Sealing
Front panel IP65 (with optional gasket) ,
Box IP30, Terminal blocks IP20
Material
PC ABS UL94V0 self-extinguishing
Digital
3PNP/NPN configurable as analogue for potentiometers.
Inputs
(max 28 Vdc in PNP mode)
Outputs
2 relays 5A resistive charge
OUT 24V
30mA(24Vac),40mA(24 Vdc),60mA (110...230Vac)
.
Back-UP
Rechargeable battery, approx. 7days autonomy
Programming
Labsoftview 2.6 or later
Software
Power Supply
24...230Vac/Vdc +/-15% 50/60Hz / 2W
INTRODUCTION
Thanks for choosing a Wachendorff device.
Timer TI327401 can be set in 5 different modes: Timer-ON, Timer-OFF,
Pause-Work, Oscillator, PWM (time-proportioned output), all options
with independent setting of ON-OFF time.
3 digital inputs are available (NPN/PNP) for external commands like
Start, Stop, Reset; one input is also analogic in order to allow the
modification of working times by external potentiometer.
5 different time bases (hundredths, tenths, seconds, minutes, hours).
Counting can be incremental or decremental.
Read carefully the safety guidelines and programming instructions
contained in this manual before using/connecting the device.
Disconnect power supply before proceeding to hardware settings or
electrical wirings.
Only qualified personnel should be allowed to use the device and/or
service it and in accordance to technical data and environmental
conditions listed in this manual.
Do not dispose electric tools together with household waste materials in
observance of European Directive 2002/96/CE
WIRING DIAGRAM
WIRING DIAGRAM
Speicher
-
+
OUT
Proximity
sensor PNP
3 wires
Proximity
OUT
sensor PNP
2 wires
POTENTIOMETER 0 to 5/10 Kohm
Speicher
Accuracy 1.000 points
Potentiometer:
To modify Set1 or Set2 by external potentiometer follow the steps below:
1 use potentiometers 0 to 5/ 10kohm
-
2
-
connect cursor to pin I3; a wrong connection ma
potentiometer and lead to lock of th device.
e
3 accuracy on input is max 1000 points, therefore set the parameters "Upper
-
limit" and "Lower limit with a max difference of 1000 units.
"
(Ex.: LoS1 to 50,0 and uPS1 to 150,0 to modify time value related to Set1 between
50 and 150 seconds with steps of one tenth). Greater differences would make
unstable the less significant digit.
4 To calibrate the scale of potentiometer enter t e configuration mode and
-
h
select:
Hin.3 as Pot
Fin.3 as Set1 or Set2
P.tAr as Enable
Exit configuration mode and place potentiometer at minimum level and press
then place potentiometer at max level and press premere
automatically exit the calibration procedure.
N.B.: A switch-off of the device would interrupt the calibration.
MEMORY CARD (optional)
MEMORY CARD (optional)
Parameters and setpoint values can be copied from one device to
another using the Memory card
. A
ttention: pls. Perform first an update of the
memory card.
There are two methods:
>
With the device connected to the power supply
insert the memory card
when the controller is off
On activation display 1 shows and display 2 shows
(Only if the values stored on Mmeory Card are correct).
By pressing the
key display 2 shows
Confirm using the
key .
The device loads the new data and starts again
>
With the controller disconnected from the power supply:
The memory card is equipped with an internal battery with a life of about 1.000
uses.
Insert the memory card and press the programming button.
When writing the parameters, the LED turns red and on completing the procedure
it changes to green. It is possible to repeat the procedure.
UPDATING MEMORY CARD.
To
update
the memory card values, follow the procedure described in the first
method, setting display 2 to
so as not to load the parameters on controller.
Enter configuration and
change at least one parameter
Exit configuration. Changes are saved automatically.
LOADING DEFAULT VALUES
This procedure restores the factory settings of the instrument.
LOADING DEFAULT SETTINGS
LOADING DEFAULT SETTINGS
PRESS
EFFECT
Display 1shows
1
and 1st digit flashes,
for 3 seconds
Display 2 shows
PNP
Modify the flashing digit,
2
Or
NPN
press
to reach the next digit
The device loads default values
3
to confirm
(factory settings)
MODIFY PARAMETERS
PRESS
EFFECT
Display 1 shows
1
and 1st digit flashes,
for 3 seconds
display 2 shows
Modify flashing digit,
2
Or
press
to reach the following digit
Display shows first parameter
3
to confirm
of configuration table
4
Scroll the parameters
Or
Increade or decrease value on display
5
+
by pressing
and one of the arrow keys
Or
at same time
End of configuration,
6
the device exits programming mode.
LIST of PARAMETERS
LIST of PARAMETERS
P-01 Timer Function
Timer operating modes
Timer On
Activate output at elapsing of counting
Timer Off
Deactivate output at elapsing of counting
Pause/Work
T1 and T2 start in sequence
y
damage the
Oscillator
T1 and T2 start in sequence and cycling
PWM
Activate a percentage of output on a fixed time base
P-02 Power-off Memory
Memory after switch-off
Disable
Disabled
Only Timer
Memory stores only value of Timer
Timer / State
Memory stores value of Timer and
P-03 Hardware Input 1
Configuration Input 1
NPN
NPN
PNP
PNP
TTL
TTL
key,
P-04 Hardware Input 2
Configuration Input 2
key: the device
NPN
NPN
PNP
PNP
TTL
TTL
P-05 Hardware Input 3
PNP
TTL
Potent.
P-06 Active State Input 1
High Level
Low Level
Rising edge
.
P-07 Active State Input 2
High Level
Low Level
Rising edge
P-08 Active State Input 3
High Level
.
Low Level
Rising edge
P-09 Function Input 1
Disable
Start / Stop
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
P-10 Function Input 2
Disable
Reset
P-11 Function Input 3
Disable
.
Wait
Hold
Potent. To SET1
Potent. To SET2
P-12 Function Key UP
Disable
Start / Stop
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
Reset
OPERATION
Wait
Hold
P-13 Output Q1 Setup
Disable
Enter password
Out Timer 1 n.o.
Out Timer 1 n.c.
Out Timer 2 n.o.
Out Timer 2 n.c.
Switch-off and restart
Start
the device
Stop
P-14 Output Q2 Setup
OPERATION
Disable
Out Timer 1 n.o.
Out Timer 1 n.c.
Out Timer 2 n.o.
Out Timer 2 n.c.
Start
Enter password
Stop
P-15 Type of Timer
Incremental
Decremental
Enter new data
P-16 Format Set 1
which will be stored
releasing the keys
Second.Cent
Second.Decimal
Second
Minute.Second
Hour.Minute
Hour
P-17 Format Set 2
Second.Cent
Second.Decimal
Second
Default
Minute.Second
Hour.Minute
Hour
P-18 Display Set 1
P-19 Display Set 2
Disable
Default
Visualized
Modifiable
START/STOP status
P-20 Lower limit Set 1
P-21 Upper limit Set 1
P-22 Lower limit Set 2
Default
P-23 Upper limit Set 2
P-24 Potent. tarature
Disable
Default
Enable
Configuration input 3
PNP
Default
TTL
Potentiometer
Activate Input 1
High level
Low level
Rising edge
Default
Activate Input 2
High level
Low level
Rising edge
Default
Activate Input 3
High level
Low level
Rising edge
Default
Function of Input 1
Disabled
Start / Stop
Default
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
Function Input 2
Disabled
Reset
Default
Function Input 3
Disabled
Wait
(stop the counting)
Hold
Default
(Hold value on display but counting goes on)
Modify SET1 by potentiometer
Modify SET2 by potentiometer
Function of
key
Disabled
Default
Start / Stop
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
Reset
Wait (stop the counting)
Hold
(hold value on display but counting goes on)
Setting of output Q1
Disabled
Default
Output Timer 1 N.O.
Output
Timer 1 N.C.
Output
Timer 2 N.O.
Output
Timer 2 N.C.
Start
Stop
Setting of output Q2
Disabled
Default
Output Timer 1 N.O.
Output Timer 1 N.C.
Output Timer 2 N.O.
Output Timer 2 N.C.
Start
Stop
Counting mode
Incremental
Default
Decremental
Format of counting
Seconds, Hundredths
Seconds, Tenths
Default
Seconds
Minutes, Seconds
Hours, Minutes
Hours
Format of counting
Seconds, Hundredths
Default
Seconds, Tenths
Seconds
Minutes, Seconds
Hours, Minutes
Hours
Visualization of Set 1
Visualization of Set 2
Disabled
Default
Visualized
Visualized and modifiable
Low limit Set 1
0.0
Upper limit Set 1
99.9
Low limit Set 2
0.0
99.9
Upper limit Set 2
Calibration of potentiometer
Disabledd
Default
Enabled