AM-CRI
Card
Reader
Interface

Installation Instructions

USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340
www.linearcorp.com
2. OPEN CASE
SQUEEZE
SIDES
TOGETHER
SEPARATE
CASE
INTRODUCTION
The AM-CRI card reader interface is designed for use with Linear's
AE1000Plus, AE2000Plus, and AM3Plus access control systems. The
interface will support one or two 26-bit Weigand input devices.
If the readers used have a "hold" or "buffer" connection, two readers may
be used to the AM-CRI. If the readers do not have a "hold" or "buffer"
connection, one reader may be used with the AM-CRI.
Usually mounted near the readers, the AM-CRI interface connects to the
controller through a six-wire cable. Each reader connects to the AM-CRI
through a six-wire (one LED in reader) or seven wire (two LEDs in reader)
cable.
Two rotary switches in the AM-CRI select the PBUS device address for each
reader connected. Each remote PBUS device connected to the controller
must be set to a different device address. The address switches in the
AM-CRI must be set to different addresses if two readers are used.
Power is supplied to the interface and reader(s) from the controller. A power
selection jumper is provided for each reader. Five or eight volt power or
external power for locally powered readers can be selected.
3. LOCATE COMPONENTS
READER "A"
DEVICE ADDRESS
READER "A"
TERMINALS
READER "A"
POWER JUMPER
READER "B"
POWER JUMPER
READER "B"
TERMINALS
1. TYPICAL INSTALLATION
ONE OR TWO READERS
CAN BE USED
CABLE LENGTH FORMULA FOR EACH AM-CRI USED IN SYSTEM
CABLE RUN
120 FEET MAXIMUM
400 FEET MAXIMUM
4. MOUNT READERS
SELECTOR
POWER & DATA
TERMINALS
(CONNECTS TO
CONTROLLER)
READER "B"
DEVICE ADDRESS
SELECTOR
AM-CRI
INTERFACE
(INSIDE WALL)
CABLE TO
CONTROLLER
(SEE FORMULA)
HOMERUN
WIRE EACH
AM-CRI TO THE
CONTROLLER
EACH AM-CRI EQUALS 25 LOAD UNITS
CABLE TYPE
FORMULA
BELDEN 9931 (24 AWG)
FEET x LOAD UNITS < 3,000 MAXIMUM
WEICO 9405 (20 AWG)
FEET x LOAD UNITS < 10,000 MAXIMUM
MOUNT READER(S)
PER MANUFACTURER'S
SPECIFICATIONS

Advertisement

loading

Summary of Contents for Linear AM-CRI

  • Page 1: Installation Instructions

    If the readers used have a “hold” or “buffer” connection, two readers may AM-CRI be used to the AM-CRI. If the readers do not have a “hold” or “buffer” connection, one reader may be used with the AM-CRI. Usually mounted near the readers, the AM-CRI interface connects to the CABLE TO controller through a six-wire cable.