Figure 4.11 Liebert DCD door hinge location
10. Check that the door moves freely.
If there are any irregularities or roughness in the movement of the door:
Check for obstructions or loosen screws of the hinges and adjust alignment.
Tighten any loose screws.
11. Apply pipe wrap or plumber's dope to the coil connection.
12. Thread one of the short, flexible pipes onto the coil connection by hand to ensure that the
threads properly mate (see Figure 4.12 on the facing page).
13. Tighten to 350 in-lb (39.5Nm).
NOTICE
Risk of improper tightening. Can cause equipment damage.
Turn only the nut on the flexible pipe when tightening this connection. Moving the coil connection may
damage the coil.
14. Pull the flexible piping slightly to elongate it enough to connect the union nuts.
NOTICE
Risk of overextending the flexible pipe. Can cause equipment damage.