Typical Wiring Diagram
Note: Polarity must be observed on detector as indicated on schematic wiring diagram.
Earth terminal is provided to maintain earth screen continuity. It does not connect to this detector head.
Base Installation
Connect the zone wires to the appropriate terminal. Tighten with a correct sized screwdriver: a wrong screwdriver may damage the screw
heads.
Make sure that the base contacts are clean and unobstructed.
Note, the base model No. for MKII-A Series is MKII-CB or MKII-CB/D.
Detector Head Installation
If there is still minor construction work in progress, the head may be fitted, provided that the dust cover is still in place.
To fit the detector, mate the detector onto the base and rotate the detector in clockwise until the detector loads into the base.
Continue to twist clockwise to secure it.
Model List
Part No
Model No.
80-210
MKII-AOP
80-212
MKII-AHR
80-214
MKII-AHF
80-216
MKII-AOH
80-218
MKII-AHF/CS90
Specifications
Electrical Characteristics
Loop voltage
Maximum current consumption, at 24 VDC
Switch-on surge, max 65 ms
Quiescent
Alarm (with no remote output.)
Remote Output Capacity
Startup Time
Maximum cable resistance
Environmental
Operating temperature
Operating humidity
Design environment
IP Rate
32-0068-r03
Description
Analogue optical detector
Analogue A1R heat detector
Analogue A2S heat detector
Analogue optical and A1 heat detector
Analogue CS heat detector
Parameter
17 V – 28 V DC
800uA
500uA
5mA
Vloop@5mA
-10 °C to + 80 °C
0-95% RH
(no condensation or icing)
Indoor use only
Zeta Alarms Limited, 72/78 Morfa Road, Swansea, SA1 2EN
MKII-Axx Installation Guide
CPR No.
0832-CPR-F0075
0832-CPR-F0079
0832-CPR-F0081
0832-CPR-F0077
0832-CPR-F1921
15S
50Ω
42
1 / 3
LPCB No
330n/02
330q/04
330q/03
330p/02
330q/05
17/10/2017

Advertisement

loading

Summary of Contents for Zeta Alarm Systems 80-210

  • Page 1 To fit the detector, mate the detector onto the base and rotate the detector in clockwise until the detector loads into the base. Continue to twist clockwise to secure it. Model List Part No Model No. Description LPCB No CPR No. 80-210 MKII-AOP Analogue optical detector 0832-CPR-F0075 330n/02 80-212 MKII-AHR Analogue A1R heat detector...
  • Page 2 MKII-Axx Installation Guide Detector Address Setting Each detector fitted to the loop needs to have a unique address set. There can only be one device set to each ADDR 87654321 ADDR 87654321 ADDR 87654321 ADDR 87654321 address. 00000000 00100000 01000000 01100000 00000001 00100001...
  • Page 3 MKII-Axx Installation Guide Maintenance Information Fyreye Mk II detectors are generally installed as part of a fire alarm system. Servicing of the system should be carried out in accordance with the requirements of the local code of practice for fire alarm installations, eg.