PRODUCT SPECIFICATIONS
POWER REQUIREMENTS:
POLARIZED COIL INPUT(S):
ENERGIZED INDICATOR:
CONTACT RATINGS:
CONTACT CONSTRUCTION:
AMBIENT TEMPERATURE:
WIRING:
"/T" VERSIONS:
"/C" VERSIONS:
APPROVALS:
CAUTION: DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE
!
NOTE: 230VAC NOT INTENDED FOR CONTINUOUS USE
WIRING
(TYPICAL FOR ONE
MR-101
MODULE POSITION)
SPDT CONTACT
7A @ 28VDC, 10A (NO: 1/6HP, NC: 1/8HP)
@ 120VAC, 7A @ 230VAC
NC C
NO
RELAY
ENERGIZED
LED
ON
INPUT
0
18/24 115 230
CONTROL
VOLTAGES
24(18-35)VDC @ 18mA
(-)
(+)
24(18-35)VAC @ 18mA
A.C.
A.C.
120VAC @ 18mA
N
230VAC @ 18mA
L2
FOR ADDITIONAL APPLICATION INFORMATION AND/OR ASSISTANCE,
PLEASE CONTACT OUR TECHNICAL SUPPORT HOTLINE. (888) 332-2241
© Air Products and Controls Inc. 2005
MR-100 Series: 24(18-35)VDC / 24(18-35)VAC / 120VAC / 230VAC @ 18mA per module position
MR-200 Series: 24(18-35)VDC / 24(18-35)VAC / 120VAC / 230VAC @ 40mA per module position
DC control inputs only
One red LED per module position
Resistive load: 7A @ 28VDC, 10A (NO: 1/6HP, NC: 1/8HP) @ 120VAC, 7A @ 230VAC
MR-100 Series: Dry form "C" SPDT per module position
MR-200 Series: Dry form "C" DPDT per module position
32ºF to 120ºF (0ºC to 49ºC) @ 85% RH
Solid or stranded: #12 to #22 AWG terminals
3.5" wide, low profile snap track provided with mounting screws
Backbox: 18ga CRS, plated with ½" conduit knockouts top and bottom
Cover Material:
MR-101, MR-201: plastic ABS 94V-0 ("/C" Grey, "/C/R" Red)
MR-104, MR-204: CRS 18ga ("/C" Grey, "/C/R" Red)
"T" versions: UL Recognized Component
"C" versions:
UL Listed
MEA File #73-92-E Vol.14
"C/R" versions: UL Listed
CSFM File #7300-1004:101, MEA File #73-92-E Vol. 22
7A @ 28VDC, 10A (NO: 1/6HP, NC: 1/8HP)
RELAY
ENERGIZED
LED
INPUT
CONTROL
VOLTAGES
24(18-35)VDC @ 40mA
24(18-35)VAC @ 40mA
H
120VAC @ 40mA
230VAC @ 40mA
L1
1749 East Highwood
Pontiac, MI 48340
MR-100 SERIES
MR-200 SERIES
MULTI-VOLTAGE RELAY INSTALLATION GUIDE
Non-Condensing / Non-Freezing
(@32ºC)
(UL864, UOXX2)
, CUL Listed
(UL864, UOXX)
(UL864, UOXX7)
(MR-101, MR-104),
, CUL Listed
(UL864, UOXX)
(UL864, UOXX7)
MR-201
DPDT CONTACTS
@ 120VAC, 7A @ 230VAC
NC C NO
NC C NO
ON
0
18/24 115
230
(-)
(+)
A.C.
A.C.
N
H
L2
L1
Ph. (248) 332-3900
File #S3403, CSFM File #7300-1004:106
File #S3403, CSFM File #7300-1004:101,
Vol. 16
(MR-201, MR-204)
File #S3403,
APPLICATION EXAMPLE
LOAD POWER
SOURCE
WHEN RELAY COIL ENERGIZES,
"NC" CONTACTS ARE SWITCHED
TO OPEN POSITION, REMOVING
POWER TO TURN OFF LOAD
MEA ACCEPTED
CSFM LISTED
RECOGNIZED COMPONENT
Fax (248) 332-8807
www.ap-c.com
-/N
-/N
LOAD
+/AC
+/AC
NC C
NO
ON
0
18/24 115 230
-/N +/AC
RELAY POWER
SUPPLY
INST AP-021 B050203
Need help?
Do you have a question about the MR-101 and is the answer not in the manual?
Questions and answers