Fenwal 27020-0 Installation Instructions

27000 series. horizontal detected-a-fire units

Advertisement

Quick Links

Series 27000
Horizontal DETECT-A-FIRE
Installation Instructions
12.02.D
Contact
Model
Operation on
Number
Temperature Rise
27020-0
Opens
27020-1
27021-0
Closes
27021-1
*Although incandescent lamps are considered resistive, their inrush
current is 10 -15 times their steady current. Do not exceed ratings.
LOCATION
DETECT-A-FIRE detectors are precision temperature sensors.
They must be mounted in an area (normally a ceiling) so that:
1. The detector spacing complies with both system
requirements and requirements of the agency having
local jurisdiction.
2. The thermal air path to the shell is not obstructed.
Spacing per UL, FM, and UL of Canada is shown in Table 1.
Distances given are for between units on smooth ceilings.
Distances from partitions or walls are half that shown.
To assure that all spacing requirements are met, consult
the authority having local jurisdiction.
MOUNTING
DETECT-A-FIRE units are not position sensitive. Horizontal
and vertical detectors refer to the most common mounting
configurations for that unit. However, each type can be
mounted either horizontally or vertically depending on the
application and installation requirements.
Table 1: Model Number 27020*, 27021
Spacings (in feet)
°F
°F
Setting
Tolerance
UL
140
+7/-8
50
160
+7/-8
25
190
+7/-8
50
210
+7/-8
25
225
+7/-8
25
+ 10
275
25
+ 10
325
50
* 27020 is a normally closed device and does not meet the
requirements of NFPA-72 for use as an initiating device.
Anderson-Bolds -- 216-360-9800
®
Units
Electrical Rating
(Resistive Only)
5.0 Amps 125 VAC
5.0 Amps 126 VAC
0.5 Amps 125 VDC
2.0 Amps 24 VDC
1.0 Amps 48 VDC
Color
RTI
Coding
ULc
FM
50
20
Quick
Black
25
20
Quick
Black
50
25
Fast
White
50
25
Fast
White
50
25
Fast
White
50
25
Fast
Blue
50
25
Fast
Red
INSTALLATION
Figure1: Surface Mount Units
Series 27020-1 and 27021-1
These detectors are provided with a surface mount adaptor
which may be mounted on a ceiling or to an outlet box.
However, if the adaptor is direct ceiling mounted, CIRCUIT
VOLTAGE MUST BE LIMITED TO 30 VOLTS.
The Canadian Electrical Code, Part 1, requires that these
devices be installed, mounted to an approved outlet box
and connected to Class 1 wiring. Surface mount units shall
be used only in this manner for Canadian approval.
For direct ceiling mount, proceed as follows:
1. The knockouts are located on the side of the surface
mount adaptor. Remove appropriate knockouts and
install rubber grommets.
2. Mount adaptor to solid ceiling surface through slotted holde in
adaptor mounting brackets. Supplied insulator gasket should
be placed between ceiling and adaptor. Adaptor may be
rotated to position detector.
3. Run system wiring through rubber grommets and connect
to terminals on detector per Figure 3 observing applicable
electrical codes.
4. Mount detector to adaptor with two #8-32 screws supplied.
For optional outlet box mount, proceed as follows:
1. Bend the mounting brackets on the supplied adaptor to fit
standard 4-including outlet box.
2. Mount adaptor to solid ceiling surface through slotted holes in
adaptor mounting brackets. Supplied insulator gasket should
be placed between ceiling adaptor. Adaptor may be rotated to
position detector.
®

Advertisement

loading

Summary of Contents for Fenwal 27020-0

  • Page 1 Contact Model Operation on Electrical Rating Number Figure1: Surface Mount Units Temperature Rise (Resistive Only) Series 27020-1 and 27021-1 27020-0 5.0 Amps 125 VAC Opens 27020-1 5.0 Amps 126 VAC 27021-0 0.5 Amps 125 VDC Closes 2.0 Amps 24 VDC 27021-1 1.0 Amps 48 VDC...
  • Page 2 TEL: (508) 881-2000 FAX: (508) 881-6729 information be desired or should particular problems arise which are not covered sufficiently for www.fenwalcontrols.com the purchaser’s purposes, the matter should be referred to KIDDE-FENWAL, Inc., Ashland, Massachusetts. Fenwal is a registered trademark of Kidde-Fenwal, Inc.