OMN WIRE
Red
Black
Orange
Blue
Pink
Brown
White/Yellow
White/Brown
Alarm Grounds
*If connections already exist on these terminals, contact OmniMetrix Technical Support before continuing installation).
If you have any questions, please call OmniMetrix Tech Support at 770-209-0012 or
email at techsupport@omnimetrix.net.
Cummins PCC2100 Wiring Table
FUNCTION
Power In
Ground
Generator Running
Common Warning
Not in Auto
Common Shutdown
Remote Start/Stop
Remote Start/Stop
Daisy chain Terminals 9, 11, 13, and 15 and connect to Terminal 20 Ground.*
Cummins PCC2100 Wiring Table
4295 Hamilton Mill Road, Suite 100 ▪ Buford, GA 30518 ▪ 770-209-0012
www.omnimetrix.net ▪ 770-209-0012
TERMINATION
TB1 - 17
TB1 - 20
TB1 - 14
TB1 - 8
TB1 - 12
TB1 - 10
TB1 - 1
TB1 – 22
IM-002 Rev G