Wireless Thermostat (WTS10)
Testing
WARNING! Read BEFORE Testing
Do not short across terminals on the gas valve or
at the heating or cooling system control board to
test the thermostat installation. This could damage
the thermostat and void the warranty.
Do not select COOL mode if the outside temperature
is below 50° F (10° C). This could damage the
controlled cooling system and cause personal
injury.
Ensure the power supply is correct and the display is
reading current room temperature.
Test for Conventional System
1. Press and hold down the (LEFT) button, then
momentarily press Reset pinhole. The screen will go blank.
When you see INSTALLATION MODE release (LEFT) button.
All the outputs are turned off.
2. "HVAC: ELEC Heat/Cool" indicates SW1 is set for Electric
Conventional System. "HVAC: GAS Heat/Cool" indicates
SW1 is set for Gas Conventional System. If the display is
incorrect , please review the SW1 switch positions.
3. "FAN" is highlighted. Press the
FAN output (ON/OFF). After testing the FAN output , it is
best to keep the FAN output ON to test other outputs.
4. Press the
(DOWN) button to highlight COOL: "Stage1".
+
Press the
button to toggle the COOL stage 1 output
(ON/OFF).
5. Press the
(DOWN) button to highlight "Stage 2". Press
+
button to toggle the COOL stage 2 output (ON/OFF).
6. Press the
(DOWN) button to go to the HEAT test. All
cool outputs are turned off; the fan output will be turned
off for a GAS System, and the fan output will keep current
status for an Electric System.
7. HEAT: "Stage1" is highlighted, press the
toggle the HEAT stage 1 output (ON/OFF).
8. Press the
(DOWN) button to highlight "Stage2". Press
+
the
button to toggle the HEAT stage 2 output (ON/OFF).
+
button to toggle the
+
button to
9. Press the
(DOWN) button to highlight "Stage3". Press
+
the
button to toggle the HEAT stage 3 output (ON/OFF).
10. Press the Reset pinhole to stop the INSTALLATION
MODE.
Test for Heat Pump Systems
1. Hold the (LEFT) button, then momentarily press
Reset pinhole. The screen will go blank. When you see
INSTALLATION MODE release the (LEFT) button. All the
outputs are turned off.
2. "HVAC: Heat Pump <O>" indicates SW1 is set for cool
changeover valve O. "HVAC: Heat Pump <B>" indicates
SW1 is set for heat changeover valve B. If the display is
incorrect , please review the SW1 switch positions.
3. The setting for "STAGE" is highlighted. Press the
button to scroll through the selections: "1H1C or 2H/1C"
and "2H2C or 3H2C." When the desired STAGE selection
is highlighted, press the
selection and advance to the FAN selection.
+
4. Press the
button to toggle the FAN output (ON/OFF).
Keep the FAN output ON while testing the other outputs.
5. Press the
(DOWN) button to highlight the setting for
"COOL: Stage1". Press the
stage 1 output (ON/OFF). For a 2-Stage cooling system,
press the
(DOWN) button to highlight "Stage2". Press the
+
button to toggle the COOL stage 2 output (ON/OFF).
6. Press the
(DOWN) button to go to the HEAT test . All
cool outputs will be turned off, and the fan output will
keep it's current status. HEAT: "Stage1" is highlighted.
+
Press the
button to toggle the HEAT stage 1 output
(ON/OFF). For a 2 or 3-Stage heat system, press the
(DOWN) button to highlight "Stage2". Press the
to toggle the HEAT stage 2 output (ON/OFF). For a 3-Stage
heat system, press the
+
"AUX". Press the
button to toggle the Auxiliary Heating
output (ON/OFF). Press the
the "EMER" setting. Press the
EMERGENCY output (ON/OFF).
7. Press the Reset pinhole to stop the INSTALLATION
MODE.
+
(DOWN) button to enter your
+
button to toggle the COOL
+
button
(DOWN) button to highlight
(DOWN) button to highlight
+
button to toggle the