Directional Earth Fault Elements Deff And Defr - Toshiba GRL100-701B Instruction Manual

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

where,
V = fault voltage
I = fault current
θ = angle difference between V and IZs
Zs = impedance setting
Vs = undervoltage setting
When the value and angle of Zs are set to those similar to the impedance of the protected line, the
phase selection element will detect all single-phase earth faults that have occurred on the protected
line even with a strong source and the voltage drop is small.
As a result of current compensation, the operating zone expands only in the direction leading the
current by the line impedance angle. Therefore, the effect of current compensation is very small
under load conditions where the current and voltage have almost the same phase angle.

2.16.5 Directional Earth Fault Elements DEFF and DEFR

There are two types of directional earth fault element, the forward looking element (DEFF) and
reverse looking element (DEFR). Their characteristics are shown in Figure 2.16.5.1.
Both the DEFF and DEFR use a residual voltage as their polarizing voltage and determine the fault
direction based on the phase relationship between the residual current and polarizing voltage.
The operation decision is made using the following equation.
DEFF
⋅ cos(φ − θ) ≥ I sf
3I
0
≥ V sf
3V
0
DEFR
cos(φ − θ − 180°) ≥ I sr
3I
0
≥ V sr
3V
0
where,
3I
= residual current
0
I sr
θ + 180°
θ
I sf
Figure 2.16.5.1 Directional Earth Fault Element
 143 
DEFR
DEFF
−3V 0
φ
3I 0
6 F 2 S 0 8 5 0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Grl100-702bGrl100-711bGrl100-712b

Table of Contents