Specifications - Samsung AJ040MCJ2EH Installation Manual

Table of Contents

Advertisement

Outdoor-to-indoor power terminal

specifications

• Connect the cables to the terminal board using the
compressed ring terminal.
• Cover a solderless ring terminal and a connector part
of the power cable and then connect it.
Silver solder
Nominal
Nominal
dimensions
dimensions
Standard
for cable
for screw
dimension
(mm²)
(mm)
(mm)
4
6.6
1.5
4
8
4
6.6
2.5
4
8.5
4
4
9.5
• Connect the rated cables only.
• Connect using a driver which is able to apply the rated
torque to the screws.
• If the terminal is loose, fire may occur caused by arc. If
the terminal is connected too firmly, the terminal may
be damaged.
Tightening torque (kgf • cm)
M4
M5
• 1N · m = 10 kgf · cm
B
D
Standard
Allowance
Allowance
dimension
(mm)
(mm)
(mm)
+0.3
±0.2
3.4
-0.2
+0.3
±0.2
4.2
-0.2
+0.3
±0.2
5.6
-0.2
12.0 to 18.0
20.0 to 30.0
d1
E
F
Standard
Allowance
Min.
Min.
dimension
(mm)
(mm)
(mm)
(mm)
1.7
±0.2
4.1
6
2.3
±0.2
6
6
3.4
±0.2
6
5
CAUTION
• When connecting cables, you can connect the cables to
the electrical part or connect them through the holes
below depending on the spot.
• Connect the communication cable between the indoor
and outdoor units through a conduit to protect against
external forces, and feed the conduit through the wall
together with refrigerant piping.
• Remove all burrs at the edge of the knock-out hole
and secure the cable to the outdoor knock-out using
lining and bushing with an electrical insulation such as
rubber and so on.
• Must keep the cable in a protection tube.
• Keep distances of 50mm or more between power cable
and communication cable.
• When the cables are connected through the hole,
remove the Plate bottom.
L
d2
t
Standard
Max.
Allowance
Min.
dimension
(mm)
(mm)
(mm)
(mm)
+0.2
16
4.3
0.7
0
+0.2
17.5
4.3
0.8
0
+ 0.2
20
4.3
0.9
0