HellermannTyton TDDGT Instruction Manual

HellermannTyton TDDGT Instruction Manual

7-day digital geyser timer

Advertisement

TDDGT
Instruction Manual
-
7-Day Digital Geyser Timer (Internal Relay)
Rated Voltage: 220-240V AC
16 Programmable Settings
15-Day Backup Battery
IEC 60730 Rated

Operating Instructions

Apply 220V to Live (L) terminal and Neutral (N) terminal
on timer.
Wait for 20 seconds, then push recessed Reset button.
Timer will reset.
SETTING DAY & TIME
Push and hold Clock button.
Push D+ repeatedly to adjust Day.
Push H+ repeatedly to adjust Hour.
Push M+ to adjust Minute.
Release Clock button. Time and Date set.

PROGRAMMING TIMER

Push P button once (Program 1 On appears.)
Push D+ repeatedly until desired day is reached (various
combinations of days are available).
Push H+ repeatedly until desired hour is reached.
Push M+ repeatedly until desired minute is reached.
Push P button once again (Program 1 Off appears).
Push D+ repeatedly until desired day is reached (various
combinations of days are available).
Push H+ repeatedly until desired hour is reached.
Push M+ repeatedly until desired minute is reached.

WIRING DIAGRAM

Line In
Geyser
Circuit
Breaker

Please note:

All electrical installations should be done by a qualified electrician.
The maximum current rating is 20 Amps.
Resistive loads (geysers, under-floor heating and lights)
Inductive loads (pool pump, air-conditioners).
Live In
TDDGT
Timer
Live
Load Out
Max 20A (3500 Watts)
Resistive Load (Geyser)
Max 10A (Inductive Load)
DIN Rail Mounted
Push Clock button once. Program 1 is now set.
For timer to operate automatically press Manual button
until On Auto appears on screen.
To operate timer manually press Manual button until On
or Off appears on screen.
RECOMMENDED MUNICIPAL TIME SETTINGS
Timer 1: 04:00 ON – 06:00 OFF
Timer 2: 11:00 ON – 14:00 OFF
Timer 3: 16:00 ON – 18:00 OFF
Timer 4: 21:00 ON – 23:00 OFF
OR
RECOMMENDED POWER UTILITIES TIMES
21:00 ON – 06:00 OFF

WIRING

Connect 220V to Live (L) terminal and Neutral (N) terminal
on timer.
The Load must be connected to the Load terminal.
The Load terminal will be LIVE only when timer is on.
The Neutral of the Load must be connected to the
appropriate Neutral bar and NOT the timer.
Neutral