Any similarity to names and addresses of actual busi- nesses or persons is entirely coincidental. Trademarks The Wiegand Interface Unit Four-State (WIU-4) name and logo are trade- and patents marks of UTC Fire & Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products.
Introduction Introduction The Wiegand Interface Unit-Four State (WIU-4) board features a Wiegand to F/2F data converter, which can accommodate both conventional and proprietary Wiegand reader protocols, and includes an 8 Amp relay for door strike control (entrance/exit) activity. It provides the communications interface that enables support of up to 16 Wiegand-output readers.
Wiegand Interface Unit Four State (WIU-4) Installation Manual Safety Radio interference WARNING: This is an FCC Class A product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take adequate measures.
Four built-in LEDs to help with installation and troubleshooting. • Supports Wiegand formats up to 64 bits. • Supports most 8 bit keypad reader output formats. Note: Do not use the WIU-4 with a 2SRP supervised reader processor board/microcontroller configuration.
Wiegand Interface Unit Four State (WIU-4) Installation Manual System requirements For UL compliant installation notes, refer to “UL Listed Installations” on page 18 Host software ® • Secure Perfect Edition 3.0 or later ™ • Picture Perfect 1.7 or later Microcontrollers •...
* UTC Fire & Security recommends using shielded cable for all installations. ** WIU-4 to micro: The maximum cabling distance of 1,000 ft (304.8 meters) is influenced by wire gauge, reader power requirements, and the 12 VDC level from the microcontroller.
1. Mount the WIU-4. Refer to “Mounting the WIU-4” on page 7. Note: The WIU-4 must be mounted indoors, in a protective enclosure or standard 2-gang electrical box (Installer supplied) as shown Figure 2. Configure the WIU-4.
Mounting the WIU-4 Mounting the WIU-4 Figure 1. Mounting instructions 1. To mount the WIU-4 board in the 2 gang electrical box, remove the electrical box cover and clean it with the alcohol wipes provided in the mounting hardware kit.
Wiegand Interface Unit Four State (WIU-4) Installation Manual Configuring the WIU-4 The WIU-4 has the following connectors and jumpers: • J3: Door and REX switch connector • J4: Four state door supervision jumper (Enabled) • J5: Reserved. (A jumper must be installed on pins 1 and 2) •...
If the door or REX switch is set up as supervised (1K resistor in series with switch between high and return pins, 1K in parallel with switch), the WIU-4 treats both the door and REX switch as supervised and reports four states: cut line, short circuit, closed circuit, and open circuit.
If a tamper switch is desired, connect a single-pole, single- throw (SPST), normally-closed push button switch (installer supplied) to connector J6, pins 8 and 9 on the WIU-4. When used with a Micro/5-PX, Micro/5-PXN, M5PXNplus, Micro/ PX-2000, Micro/PXN-2000, M2000PXNplus, or M3000PXNplus, the WIU-4 sends a supervised reader alarm message.
Installation Manual J7: Tamper switch connector The 2-pin connector, J7, can be used to connect a tamper switch to protect the enclosure in which the WIU-4 is mounted. To activate this feature, connect a single-pole, single-throw (SPST), normally-open push button switch (installer supplied) to connector J7 on the WIU-4 and install the switch in the desired position.
Configuring the WIU-4 J9: Reserved The 2-pin connector, J9, is reserved. J10: Door strike relay connectors The 5-pin connector, J10, is the door strike relay connection. Table 5. J10 Door strike relay connector Description Relay power (Source) Relay power (Return)
Wiegand Interface Unit Four State (WIU-4) Installation Manual Connecting the WIU-4 Connect the WIU-4 between the microcontroller and access control reader as indicated in Figure 3 WARNING: It is important to ensure all connections are made prior to applying power.
4. If the reader does not function, be sure to install a jumper across pins 1 and 2 of J5. Indicators The WIU-4 has four green LEDs that operate as indicated in the following table. Table 7. Green LED indicator status...
Input voltage range: 9 to 16 VDC, 55 mA or higher to ensure the measured 60 mA is within 110% of the current rating. • For UL Listed installations, the WIU-4 must be mounted within the protected area of a protective enclosure.
Page 23
Regulatory approvals MANUFACTURERS DECLARATION OF CONFORMITY Product identification: Model/type : WIU-4 BOM revision level Category (description) : Interface Board Brand Manufacturer: UTC Fire & Security, Americas Corp., Inc 3211 Progress Dr. Lincolnton, NC 28092 EU Representative: UTC Fire & Security B.V.
Page 24
Wiegand Interface Unit Four State (WIU-4) Installation Manual Model listing (list of all product variants or models for which this declaration is valid) Model BOM revision level WIU-4 Wiegand Interface Unit, 430160001 Signature of representative/manufacturer: Rafael Martinez Compliance Leader, Access...