The LC-Series can also be used with any manufactures sensor transmitter that can produce a voltage or current output within a specified range; however, it is advisable that you contact ENMET for proper setup and programming instructions.
LC-Series Controller: 1-4 Channel ENMET 2.0 Features The LC-Series Controller houses all of the components required to implement a sophisticated and reliable monitoring system (alarm relays etc.). See Figure 1 for location of features: 2.1 Front panel features See Figure 1 for location of features.
LC-Series Controller: 1-4 Channel ENMET 3.0 Installation The LC-Series Controller is fully tested prior to delivery. However, it is recommended that the LC-Series Controller system be checked after installation is complete. CAUTION: The MCU Control Units and associated modules contain no user serviceable parts. Refer all servicing to qualified...
LC-Series Controller: 1-4 Channel ENMET LC-4 Control Unit Figure 2: Mounting LC Series Manual Revision Date – June 13, 2017 P a g e Manual Part No. – 80003-050...
4.0 Wiring the LC Series The electrical installation should conform to appropriate electrical codes, such as the National Electrical Code in the United States. : The compliance of the installation to appropriate codes is not ENMET’s responsibility. ARNING 4.1 System Wiring All connections should be made according to the appropriate sensor or loop diagram for the configuration required.
LC-Series Controller: 1-4 Channel ENMET 4.1.1 Power Supply Module The Power Supply is situated on the LHS of the main PCB within the enclosure and provides the power for the whole system. The power supply is a standard item and does not require any modifications regardless of the type and quantity of detector heads being used.
Located on the bottom edge of the main PCB is a number of screw connectors. This is used to provide connections for inputs, outputs and external buttons: 4.1.3 Connections LC1 Channel 1 Pins 1, 2 and 3 AC power input...
LC-Series Controller: 1-4 Channel ENMET 4.1.5 Connections LC4 Chanel 1 Connections Display PCB Connector Sensor Options: Pin 13: Signal In (1 – 5 Vdc) Pin 14: Signal In (4-20mA) Pin 15: Voltage Out to S/T Pin 16: Ground to S/T...
LC-Series Controller: 1-4 Channel ENMET 4.2 Sensor Transmitter Installation Mounting location for the gas detectors need to be considered individually, initial points for consideration are: Ensure all gas detectors are mounted to allow routine calibration and maintenance to be carried out as required.
LC-Series Controller: 1-4 Channel ENMET 5.0 Operation When a preset alarm point is reached, visual and/or audio alarms are activated. The backlit graphics display automatically displays the channel in alarm and an alarm level Led(s) are activated on the control panel. The LC-8 is factory set to maintain these alarms until they are acknowledged.
Page 14
LC-Series Controller: 1-4 Channel ENMET Connection Procedure Disconnect power from the system. Remove the terminal cover to gain access to the wiring. Remove the terminal cover and display module to gain access to the configuration link settings.
LC-Series Controller: 1-4 Channel ENMET 5.2 Analogue Output Configuration In addition to providing the connections for various connector types, the Input Module can also provide an analogue output. This output mimics the signal detected so that it may be used by external equipment (e.g. chart recorders, data loggers) for a variety of purposes.
LC-Series Controller: 1-4 Channel ENMET 5.2.3 1-5V Voltage Output Alarm Alarm level 1 Level 2 LC 1 15 Channel 1 Channel 2 Channel 3 Channel 4 Chart recorder - ve The LC Control Unit can provide a voltage output. i.e.
LC-Series Controller: 1-4 Channel ENMET 6.0 Maintenance Routine Servicing The MCU Control Unit will provide a reliable and fault free service but they rely upon sensible housekeeping and regular calibrations. It is recommended that the system be calibrated at least once every six months. This can be arranged with Status Scientific Controls as part of a maintenance contract.
LC-Series Controller: 1-4 Channel ENMET 7.0 Technical Data and Specifications Type Size (nominal) ‘mm’ 188 x 160 x 106 Weight (approx.) Operating Temp -10ºC to +50ºC Storage Temp -20ºC to +50ºC Humidity Range 0 to 95% R.H. Non-condensing Input Voltage...
Page 20
LC-Series Controller: 1-4 Channel ENMET Type Size (nominal) ‘mm’ 280 x 219 x 156 Weight (approx.) 1.9Kg Operating Temp -10ºC to +50ºC Storage Temp -20ºC to +50ºC Humidity Range 0 to 95% R.H. Non-condensing Input Voltage 18-28V DC, or 100-240V AC 50/60...
Page 21
LC-Series Controller: 1-4 Channel ENMET Type Size (nominal) ‘mm’ 390 x 316 x 167 Weight (approx.) 3.8Kg Operating Temp -10ºC to +50ºC Storage Temp -20ºC to +50ºC Humidity Range 0 to 95% R.H. Non-condensing Input Voltage 18-28V DC, or 100-240V AC 50/60 Hz...
ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour. All instruments sent to ENMET are subject to a minimum evaluation fee, even if returned unrepaired.
Page 24
Mailing/Shipping Address: ENMET 680 Fairfield Court Ann Arbor, MI 48108 Phone: 734.761.1270 repair@enmet.com Fax: 734.761.3220 Service Request Form Product Name or Number: Product Serial Number: Describe Problem or Needed Service: Warranty Claim? ☐ Yes ☐ No CUSTOMER INFORMATION Billing Address:...