Performance Specification & Installation Guide
*SRUS*-*-*
120-277Vac, SWITCH-MOUNT, PIR SENSOR
PART NO.
DESCRIPTION
OSRUS1-W
1-Pole, white
OSRUS2-P-W
2-Pole with photo sensor, white
OSRUS2-P-G
2-Pole with photo sensor, gray
OSRUS2-P-I
2-Pole with photo sensor, ivory
VSRUS1-W
1-Pole vacancy (Manual-ON only), white
VSRUS2-P-W
2-Pole vacancy (Manual-ON only) with photo sensor, white
VSRUS2-P-G
2-Pole vacancy (Manual-ON only) with photo sensor, gray
2-Pole vacancy (Manual-ON only) with photo sensor, ivory
VSRUS2-P-I
FEATURES
• Commercial grade components for long term reliability
• Straightforward wiring for quick installation
*Faceplate not included
• Factory configured for the most common applications
• DIP switches and dials for advanced functionality
• Photo sensor for natual daylight control (some models)
• Vacancy sensors permanently configured for Manual-ON/Auto-OFF
Operation
CENTO 120/277Vac sensors draw control power directly from the lighting circuit they are intended to control.
When in operation the sensor will detect initial motion using Passive Infrared (PIR); once motion is detected, the
internal contact will close. Motion through PIR is used to maintain the occupied condition as long as occupants
remain within coverage range and line-of-sight of Sensor.
Test Mode LED
DIP Switches
5
20
30
1
Automatic Timeout Mode LED
Lo
Hi
Test
Light Level Dial
Sensor
Photo sensor "P"
models only
Time Delay Dial
Ranges from 30s to 30 min.
Manual Override Button
Full turn Clockwise for Auto Time
Full turn Counterclockwise for test mode
SPECIFICATIONS
Power
120/277Vac
60 Hz
Contact Ratings
120Vac - 800W
277Vac - 1200W
Power Consumption
400 micro amps
Approvals
Certified to UL 508, UL244A, CSA C22.2 #14
Title 24, California
Local Law 48, New York (Vacancy models)
Environment
Indoors, stationary, non-vibrating, non-corrosive atmosphere
and non-condensing humidity
Ambient Operating Temperature: 32°F to 104°F (0°C to 40°C)
Storage Temperature: -14°F to 140°F (-25°C to 60°C)
Page 1 of 2
CENTO Occupancy Sensors - Wall Switch, Passive Infrared (PIR), 120/277Vac
Wiring Diagrams
CENTO 120/277Vac sensors include #14 AWG wiring leads. Use appropriate sized wire nuts for connecting
wires.
CAUTION: Turn power off at the circuit breaker before working on sensor. According to NEC 240-83(d), if the
branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be
marked SWD. All installations should be in compliance with National Electric Code (NEC) and all state, provin-
cial, federal, and local codes.
Hot
Neutral
Ground
(required)
Hot
Neutral
Ground
(required)
DIMENSIONS - inches (mm)
1.25 (32)
1.62 (41)
1.18 (30)
1.69 (43)
1-pole
No Neutral
Black
Black/White
Load
Green
2-pole
No Neutral
}
Black
Blue
Hot
This pole can be used for
controlling a second fixture such
as bathroom fan when utilizing
Black/White
Blue/White
Restroom Mode.
Load
Load
Neutral
Green
Both poles should be powered by the same circuit.
Individually cap unused leads for at least 600Vac.
Installation Coverage
Installing in Offices
• PIR Requires Line of Sight
Typical Office
Standard Lens
• Optimal usage is to detect small motions such as hand movements
• Designed for a mounting height of 4ft
Top View
Side View
15 ft
8 ft
7.5 ft
4 ft
180º
0 ft
7.5 ft
0 ft
15 ft
Sensor Location Guidelines
To optimize the performance of CENTO Sensors, please review the coverage pattern, range, and model
to match with the application. Room dynamics will change when people and furniture are occupying the
space. In some rooms, after move in, some sensors may require adjustments.
• Ensure that the sensor is at least 30 inches away from air handlers/registers and not pointed directly at
windows
51 Century Blvd., Suite 230 • Nashville, TN 37214 • 615-316-5100 • (TES) 1-800-BALLAST • www.unvlt.com
Installing in Restrooms
• Use 2-pole model to control two loads in
restroom (e.g. light and fan)
Typical Restroom
15º
15º
0 ft
15 ft

Advertisement

loading

Summary of Contents for Cento OSRUS1-W

  • Page 1 Operation 2-pole Standard Lens CENTO 120/277Vac sensors draw control power directly from the lighting circuit they are intended to control. • Optimal usage is to detect small motions such as hand movements No Neutral When in operation the sensor will detect initial motion using Passive Infrared (PIR); once motion is detected, the •...
  • Page 2 ON, an OFF Time Delay of 3 minutes is used (OFF Time Delay must be greater than 3 minutes). If motion CENTO Occupancy Sensors with photo sensors are controlled by DIP 6. is detected after 30 seconds of lights ON, the configured OFF Time Delay is followed.

This manual is also suitable for:

Osrus2-p-gVsrus1-wOsrus2-p-iOsrus2-p-wVsrus2-p-gVsrus2-p-w ... Show all