Bus expander – 16 inputs for jablotron 100 system

Advertisement

Quick Links

This product is a component of the JABLOTRON 100 system. It is
used for powering and connecting up to 16 detectors with contact
outputs. It is possible to install the module straight into the JA-106K
control panel. It should be installed by a trained technician with a valid
certificate issued by an authorised distributor.
Installation
1. Put the module into the JA-106K box in the bottom right corner or
to an installation box.
2. Connect every single loop to the input terminals from 1 to 16 and
the COM common terminals. Take power for the detectors from the
+U and GND output terminals. The max. load current of connected
devices is 100mA for each +U GND terminals.
Zones can be connected as NO (example: 1-COM), as NC
(example: 2- COM), as a single balanced loop (example: 3-COM)
or as a double balanced loop (example: 8-COM).
Activation by repeated pulses (e.g. a roller blind) is available for
input terminals 1 to 8.
Balancing resistors for single and double balancing are
selectable from these: 1k, 2k2, 3k3, 4k7, 5k6, 10k. The
selection is common to all expander inputs. There are 32x 1k
resistors in the module accessories.
You are able to connect up to 5 devices (magnetic, PIR, or
any other detectors) to one input terminal when you use a
double balanced zone with 1k resistors
The maximum length of a wired loop is 100m.
Figure: Example of wiring more detectors to one input terminal when the
loop is double balanced by 1k resistors. Connection of 2 magnetic
contacts to the 4-COM input terminals. Connection of detectors with
alarm and tamper contacts to the 5-COM input terminals.
3. When the module is mounted in an installation box, this box has to
be equipped with a tamper contact. For external tamper contact
connection, use any wired input terminal.
4. Connect the BUS cable.
When connecting the module to the system
BUS, always switch the power off.
5. Proceed according to the control panel installation manual. Basic
procedure:
a.When the device is connected, the yellow LED (4) starts flashing
repeatedly to indicate that the module has not been enrolled to the
system.
JA-116H BUS expander - 16 inputs
JA-116H BUS expander – 16 inputs
Figure: Loop connection
example
The
mode
of
connection is selectable
for
every
input
individually using F-Link
sw
in
the
module
Internal settings.
b.Go to the F-Link software, select the required position in the
Devices window and launch enrollment mode by clicking on the
Enroll button. Necessary condition: After the selected position,
the next 15 positions have to be free.
c. Press the LEARN button (5) – the module is enrolled into the 16
selected positions and the yellow LED goes off. Warning – the
module is enrolled to sixteen (16) consecutive positions (each input
is enrolled to one position). If some positions in those 15 are
already occupied, they will be overwritten. When there are not
enough positions at the end of the list of devices, only a limited
number of inputs will be enrolled to fill in the rest of the positions.
6. Close the installation box.
the
Module settings
The Internal settings option (at any module position) in the Devices
window in the F - Link software opens a dialog window where you can
set the following options for each output: (* factory settings):
LED activity indication: Enabled *: A short flash (3) indicates a
status change on any input (activation and deactivation).
Balanced inputs: The chosen value of balancing resistor R is
common for all terminals of the module. You can choose between 1k*,
2k2, 4k7, 5k6, or 10k. Valid for single and double balanced inputs.
Inputs 1 - 8 and Inputs 9 - 16: Disabled – no reaction (input is
completely disabled), Enabled * – input reacts to status change
connected to the input terminal (NC is standby), Balanced – contact is
connected in series with balancing resistor R (32 x 1k resistors are
available in the accessories). Activation happens if the resistance rises
or drops by more than 30% of the EOL resistor value, Rollerblind –
(inputs 1 - 8 only) reacts to short repeated pulses with sensitivity
adjustable to two levels: Impulse 1 = activation by 3 pulses up to max.
2 minutes; Impulse 2 = activation by 5 pulses up to max. 2 minutes.
Double balanced – standby: connection to COM via the EOL resistor R
( 20%), Activation: connection to COM via the EOL resistor 2R (
30%), Tamper: connection to COM via EOL resistor lower than R –30%
or higher than 2R+30%.
Inverted input reaction: (valid for Enabled or Balanced input). The
default reaction is set to disconnection from COM (NC)*. By this you
can set the opposite reaction to grounding (NO).
Pulse mode: (valid for Enabled or Balanced input and inputs 1 to 8).
The default is a status reaction, the input reacts to activation
(disconnection from COM) and deactivation (connecting back to
COM)*. If you tick this option, the input will only react to disconnection
from COM (after 2s it returns to standby mode).
Delayed input reaction: a time filter for increasing the immunity and
to suppress false activations, 0.5 s* (options: 0.5s ... 300 s). This tells
you how long the input has to be activated to trigger an alarm in the
control panel. It is possible to use the parameter with the input set as
enabled (options from 0.1s), balanced and double balanced.
Note: The expander faulty reports are recorded in the event memory
of the control panel. The source of these events is the 1
defined by enrolling.
The manufacturer only guarantees correct functioning
of the module. However, it cannot guarantee the
correct functioning
therefore strongly recommend using Jablotron JA-100
bus detectors.
1 / 2
Figure:
1 – BUS cable;
2 – digital BUS terminals;
3 – red LED indicator;
4 – yellow LED indicator;
5 – LEARN (enroll) button;
6 – input terminals;
7 – production code
Note: Enrolling the module
to the system is possible by
entering
the
production
code (7) via F-link software
or by a production code
reader. All digits under the
production
code
are
required
(1400-00-0000-
0001).
st
input position,
of
connected detectors. We
MLN55105

Advertisement

loading
Need help?

Need help?

Do you have a question about the JA-116H and is the answer not in the manual?

Questions and answers

Summary of Contents for jablotron JA-116H

  • Page 1 JA-116H BUS expander – 16 inputs This product is a component of the JABLOTRON 100 system. It is b.Go to the F-Link software, select the required position in the used for powering and connecting up to 16 detectors with contact Devices window and launch enrollment mode by clicking on the outputs.
  • Page 2 -10 to +40 °C Also complies with EN 50130-4, EN 55022 JABLOTRON ALARMS a.s. hereby declares that the JA-116H is in a compliance with the relevant Union harmonisation legislation: Directives No: 2014/30/EU, 2011/65/EU. The original of the conformity assessment can be found at www.jablotron.com - Section Downloads.