Weil-McLain WM97+100 Manual page 109

Series 2 gas-fired water boilers
Table of Contents

Advertisement

WM97+ Series 2
Troubleshooting
Figure 117
Troubleshooting suggestions for WM97+ boilers —
The WM97+ control is able to record information about the boiler's condition at the time of the three previous faults or errors.
This information is available to view in Contractor Menus under "DIAGNOSTICS" by selecting "ERRORS." The control will display
the following information:
Information
Control Fault
Ignition Retries
Manual Reset Count
Auto Reset Count
Lockout History 1
Lockout History 2
Lockout History 3
How to read the last 3 lockout histories:
How to clear all lockout histories:
Part number 550-142-204/0117
-
GAS
FIRED WATER BOILER
(continued)
Description
Records the number of internal control faults.
Displays the number of ignition attempts in the current
ignition sequence.
Records number of lockouts that required a manual reset
since this count was last cleared.
Records number of lockouts that have automatically reset
since this count was last cleared.
Details of present or last recorded lockout.
Details of boiler during the second oldest lockout still in
memory.
Details of boiler during the oldest lockout still in memory.
1. Scroll down to "DIAGNOSTICS" and press the
enter key (Square Key in center).
2. Scroll down to "ERRORS" and press the enter key
(Square Key in center).
3. Scroll down to "LOCKOUT HISTORY #" and press
the enter key.
4. Scroll to choose the either "MANUAL RESET" or
"AUTO RESET" and press the enter key to display
the fault condition that was recorded.
1.
While on the "ERRORS" screen, hold the Left
and Right arrow buttons simultaneously for 7
seconds.
— Boiler Manual
WM97+ control Error Condition Log
Action
Select and press the enter key to reset this count.
Select and press the enter key to reset this count.
Select and press the enter key to reset this count.
Select and press the enter key for more details.
Select and press the enter key for more details.
Select and press the enter key for more details.
5. Press the left arrow key to return to the LOCKOUT
HISTORY # screen. Scroll up or down to highlight
other choices and press the enter key to view the
details of the boiler's condition when the lockout
was recorded.
– 109 –