S-Access SA-ACU-SR User Manual

Alarm control unit

Advertisement

Quick Links

SA-ACU-SR
SA-ACU-SR
Alarm Control Unit
USER MANUAL
Version
Revision
Document name
User Manual
1.0
14. Now. 2002
UM_SA-ACU-SR_v1-0.doc

Advertisement

Table of Contents
loading

Summary of Contents for S-Access SA-ACU-SR

  • Page 1 SA-ACU-SR User Manual SA-ACU-SR Alarm Control Unit USER MANUAL Version Revision 14. Now. 2002 Document name UM_SA-ACU-SR_v1-0.doc...
  • Page 2 SA-ACU-SR User Manual © Copyright © 2002 by S-Access GmbH. The contents of this publication may not be reproduced in any part or as a whole, transcribed, stored in a retrieval system, translated into any language, or transmitted in any form or by any means, electronic, mechanical, magnetic, optical, chemical, photocopying, manual, or otherwise, without the prior written permission of S-Access GmbH.
  • Page 3: Table Of Contents

    Connection of the shelf to the clock source ............ 10 Connection of external devices over the RS485 interface ......10 Power failure alarm ..................11 INSTALLATION ....................... 12 SA-ACU-SR installation .................. 12 Installation requirements ................. 12 TECHNICAL SPECIFICATIONS................13 Interfaces ......................13 5.1.1...
  • Page 4: Version Control

    SA-ACU-SR User Manual VERSION CONTROL Version Date Major changes to previous version 14.11.2002 Initial version. S-Access GmbH Tel: +41 44 700 31 11 Oberhausenstrasse 47 Fax: +41 44 700 31 03 Page 8907 Wettswil a/A Email: contact@s-access.ch Switzerland WEB: www.s-access.ch...
  • Page 5: The Sa-Acu Module

    SA-ACU-SR User Manual 1 THE SA-ACU MODULE The SA-ACU module is installed into the SA-R shelf and is used for the following: • connection of the shelf to external visual and sound alarm control units which inform an operator about alarm conditions while operating different devices;...
  • Page 6: Ordering Information

    SA-ACU-SR User Manual 2 ORDERING INFORMATION Model Description SA-ACU-SR AccessGain, alarm control unit S-Access GmbH Tel: +41 44 700 31 11 Oberhausenstrasse 47 Fax: +41 44 700 31 03 Page 8907 Wettswil a/A Email: contact@s-access.ch Switzerland WEB: www.s-access.ch...
  • Page 7: Description Of The Sa-Acu Module

    SA-ACU-SR User Manual 3 DESCRIPTION OF THE SA-ACU MODULE 3.1 Schematic of the module Fig. 3.1 shows the front view of the SA-ACU-SR module. Fig. 3.1 Front panel of the SA-ACU-SR module S-Access GmbH Tel: +41 44 700 31 11...
  • Page 8: Description And Lay-Out Of Jumpers And Sockets

    SA-ACU-SR User Manual The front panel of the module contains: • four LEDs, indicating the operating conditions of the power feeding circuits and the presence of the external clock signal; • the “2048 kHz IN” socket for the connection of the external clock source;...
  • Page 9: Control And Configuration Of The Modules

    The front panel of each device has LEDs indicating its condition. Each device has signal outputs connected to the common signal bus of the shelf. The SA-ACU-SR module has two relays and control circuits of their condition for the connection of the common bus to external voice and visual alarm signaling units.
  • Page 10: Connection Of The Shelf To The Clock Source

    The universal AccessGain platform has a possibility of synchronization of signals transmitted from the external clock source. The SA-ACU-SR module contains a unit designed to receive and process (supervise) clock impulses at a frequency of 2048 kHz. The socket for the connection of the external clock source is of a 75-Ohm BNC type.
  • Page 11: Power Failure Alarm

    SA-ACU-SR User Manual 3.7 Power failure alarm The front panel of the SA-ACU-SR module displays the status of the shelf power feeding. The A and B “–48V ” LEDs inform an operator about the status of primary and auxiliary power feeding circuits, respectively. In normal condition the LEDs are green, while in case of a power supply failure, the LEDs will be extinguished.
  • Page 12: Installation

    SA-ACU-SR User Manual 4 INSTALLATION 4.1 SA-ACU-SR installation • Unpack and install the module appropriately. • Check the settings of jumpers/switches of the power source type. • Install the module into the shelf (slot 13 or 14). • Connect the module (if necessary) to the external clock source.
  • Page 13: Technical Specifications

    SA-ACU-SR User Manual 5 TECHNICAL SPECIFICATIONS 5.1 Interfaces 5.1.1 Monitor-interface Connector type SubD9 female Signal level According to ITU-T Rec. V.24 Data rate 9600 bauds, asynchronous mode Protocol VT100 8 bits, without parity 1 stop-bit without carriage return to a new line...
  • Page 14: Rs485 Interface

    SA-ACU-SR User Manual 5.1.2 RS485 interface Connector type SubD9 female Data rate 9600 bauds, asynchronous mode Protocol 8 bits, parity, 1 stop-bit Description of pins Signal Description 1, 5 Protective ground 2, 3, 4 Not used RX_485+ RS485 input (positive)
  • Page 15: Alarm Relay Interface

    SA-ACU-SR User Manual 5.1.3 Alarm relay interface Connector type SubD15, male Max. Switching power 30 W Max. Switching current 1 А Max. Switching voltage 110 V , 125 V Electrical isolation contact-coil 100 V for 1 min Description of pins...
  • Page 16: Service Requirements

    SA-ACU-SR User Manual 5.3 Service requirements 5.3.1 Climatic conditions Storage ETS 300 019-1-1 Class 1.2 -25°С ... +55°С Transportation ETS 300 019-1-2 Class 2.3 -40°С ... +70°С Operation ETS 300 019-1-3 Class 3.2 -5°С ... +45°С 5.3.2 Safety According to EN 60950.