Overview approximately 2 seconds. Continue holding the button until you see the word “test” on the lower The PT9250 is a versatile tool that can be used display. At this point, the TR9250 will continue by building owners and contractors to better it’s self-diagnosis until readings on the upper...
Background The PT9250 not only measures CO Temperature but it also calculates the outside air ventilation rate in cfm per person based on the Battery power level is also displayed in the difference between inside and outside CO middle left portion of the display.
Page 4
OSHA. In buildings the CO concentration is than the 400 ppm level assumed by the PT9250. more an indication of ventilation. If a space feels (A difference of about 50 ppm will result in an uncomfortable, stuffy, or stale and the CO levels error of about 0.5 cfm/person in the calculation.)
Prior to starting the program on your PC, turn the PT9250 on and plug it into your PC using the This part of the program allows you to adjust the cable provided. (Note: If your computer does not...
Page 6
Here you can change a number of characteristics based on the range of measurements observed. of the LCD display on the PT9250. By clicking in For more options in graphing, the logged data the box you will see a menu of the display can be exported to a text file and graphed in a choices that are available.
7 Day – 15 minute sampling • Battery Life & Logging: The battery life of the PT9250 is 10 to 16 hours. As a rule you should have the PT9250 plugged into it’s charger whenever you are logging concentrations for extended periods of time.
Calibration gases, tubing and regulators are available from AirTest. Zero & Span Calibration: Typically, drift of the PT9250 is on the zero adjustment of the sensor. The sensor generally should not require span adjustment. If performing both types of calibration the zero calibration should be performed first.
Page 9
Control: If outside levels are at or near 400 ppm and the activity level is close to office type activity then AirTest has just release an easy to use software the CO /cfm-per-person conversion chart in tool that allows you to compare the cost of Section 3 of this guide can be used.
Page 10
Calibrate You And Your Customers: Dealing With IAQ Complaints: The AirTest PT 9250 is an ideal tool that can be Many symptoms related to indoor air quality used to calibrate you and your customers to CO (IAQ) complaints can also be associated with and ventilation.
Page 11
CO level. You can involved in a CO retrofit. use the PT9250 to determine the level of odor perception in a facility. A permanently installed Location Of Sensors: Sensors should be monitor in the space can then use this located in each major occupied space.
Page 12
AirTest also has products that will allow you to control a VAV box based on CO temperature.
Need help?
Do you have a question about the PT9250 and is the answer not in the manual?