OPERATION FLOW AND SETTING MENU
TTM-000 SERIES USER'S MANUAL
/
1
DIN. DIGITAL TEMPERATURE CONTROLLER
●Power ON
16
Thank you for purchasing model TTM-000 SERIES
Digital Temperature Controller.
●Operate mode display
Please go through this Instruction Manual carefully
A.
and use the unit in proper manner.
Process value
/
NOTICE
WARNING BEFORE OPERATION USE
B. Priority displays. Refer to Ex.1.
When having the purchased controller at hand, please be sure that its unit is
●
SET0 : Priority displays by
a correct model (See the following "Model Configuration" ).
setting and shows max.9
displays by setting.
The following symbol marks
provide to prevent incident or damage. Kindly
●
refer to the details of the WARNING/CAUTION when using for the first time.
●
Another copy of the user's manual "Advanced Version" is provided at
customer's request.
●FUNC key
FUNK key operates on the selected
Due to mishandling,
setting mode 7.
Refer to Ex.2.
serious dangers may occur to
WARNING
the operator such as death,
electrocution and a skin burn.
Ex.1. Priority displays & its setting
Owing to mishandling, it may
cause some damage to
CAUTION
the unit or the operator
eg. :
getting slight injury.
*Screen is shifted when pressing mode key each time.
CAUTION
Ex.2. FUNC key work
For prevention of its malfunction, do not push the front
●
key with sharp points.
Spare terminal must not be used for other purposes.
1.Digit shift
●
Setting digit shift is enabled when setting value is changed.
2.RUN/READY
Control stop (READY) and control performance (RUN) are
WARNING
alternately switched every time FUNC key is pressed.
(READY lamp is ON during control stop)
3.Auto-Tuning (AT)
●
Make sure the correct wiring connection before turning on electricity.
AT starts instantly after pressing FUNC key.
(Start/Reset operation is available, each time FUNC key
Mis-wiring may cause malfunction of the unit and fire.
is pressed)
●
Never modify the unit to prevent damage or incident such as
4.Timer
malfunction and fire etc.
Available for start/reset.
・Please put this user's manual aside for your reference, when
Ex.3. To select PID
operating the unit.
Feature of type A and B
・Copy or reprint of this manual, wholly or partially, is not allowed.
Type A
・The contents of this manual may change without notice in future.
Type B
If control is unstable under self-tuning,
please change to type A or B and also to ON/OFF control.
ACCESSORY
&
CONFIGURATION
Ex.4. ARW
1
)
Please be sure that the unit enclosed in packing carton is a right model
before using.
2
)
Kindly check the following accessory being contained in that carton box.
●
ARW controls integral action(PV accords with SV).
●
If integral value goes down, it takes effects.
Installation Attachment (For installation, please see "INSTALLATION
●
If integral value is set "0", it stops integral action.
AND WIRING" on the back.)
This user's manual : 1 copy
●
Table1. To select input sensors and setting range.
3
)
Model Configuration
Symbol
00 K Thermocouple
Model
Input
Output 1
Option
01 J
T T M - □ □ □ − □ − □ − A □ □ □
02 R
03 T
04 N
05 S
Option
MODEL Front Dimensions
CODE
06 B
10 Pt100
002
24
×
48 mm
B
Output 2 Relay contact
11 JPt100
B or P selectable
Output 2 SSR drive voltage
004
48
×
48 mm
P
20 DC0 – 5V
X04
48
×
48 mm
R
EV 2 Relay contact
Not optional for TTM-002 / 004.
When DI is selected for
005
96
×
48 mm
21 DC1 – 5V
TTM-005, 006, 007 or 009,
006
48
×
96 mm
this option is not available.
007
72
72 mm
×
22 DC4 – 20mA
D
CT input When DI is selected for TTM-002 / 004,
009
96
×
96 mm
this option is not usable.
When I output (4–20mA) is selected,
Input Type
CODE
this option is not provided.
NIL
Thermocouple (K, J, R,
E
DI (Digital input) When CT is selected for TTM-002 / 004,
*Either thermocouple or R.T.D.
T, N, S, B)
this option cannot be obtained.
(Pt 100/JPt 100) is selectable for
R.T.D. (Pt100, JPt100)
When EV 2 is selected for TTM-005, 006,
input type, by pressing the front key.
2
0–5V, 1–5V, 4–20mA
007 or 009, this option cannot be chosen.
*Either "B" or "P" is optional.
M
Communication RS-485
Output 1
*A (Event 1) : Single alarm is provided
CODE
* A (EV1) provided in the standard specifications.
R
Relay contact
in the standard specifications.
* Without output 2, EV2 is not available.
SSR drive voltage
P
* Output 2 is equally used as EV2, but both not
activated simultaneously.
I
Current 4–20 mA DC
Conformed Standards
SPECIFICATIONS
Safety : EN61010-1(IEC1010-1)
EMI : EN50081-2
Power Supply Voltage
100 to 240V AC, 50/60Hz
EMS : EN50082-2
Power Consumption
Below 10 VA
UL3121-1(UL /CUL)
Memory Element
EEPROM
Input of Sensor
Thermocouple, R.T.D./0–5V, 1–5V, 4–20mA
(Changeable by front key)
Control Output
Relay contact, SSR drive voltage, Current
CAUTION BEFORE CONTROL
Control Method
Two kinds of PID, ON/OFF
0 to 50℃, 20 to 90%RH (Avoid making dew)
Operation Environment
●
Setting program is stored after power OFF, as non-volatile memory
Storage Environment
−25 to 70℃, 5 to 95%RH (Avoid making dew)
is equipped with TTM-000 SERIES controllers for setting storage.
Weight
TTM-002/004 Less than 180g, TTM-005/006 Less than 240g,
Either thermocouple or R.T.D.(Pt 100/JPt 100) is selectable
TTM-007 Less than 250g, TTM-009 Less than 310g.
●
input type, but Current/Voltage input needs to be selected
Location of the Unit Setting
Keep away from the followings.
・Gas of corrosion, dust and oily smoke.
individually. For suitable application, please select most
・The electric noise of generator.
CAUTION
appropriate input type and adjust input setup.
・The influence of electromagnetic field.
●
PID or ON/OFF control is selective for the optimal
・Mechanical vibration and shock.
performance and each detail of features is specified in the
・The direct sunlight.
Installation condition
Installation category2
table on the right side.
Setting display shows the existence of option.
●Setting mode
<SET1:Initial Setting>
<SET2:Control Setting>
Shows for 4 seconds
▲ KEY
1. Initial setting display
9. Details of control setting
(Warming up)
Initial setting mode
Calling display
▼ KEY
MODE key
Primary displays
: Press key
* After select,
2. Input type setting
10. High limit setting in SV limiter
press MODE key
Set the temperature
Select input type
* Current/Voltage
Setting value
required
「22」
Refer to Table 1.
MODE key more
MODE key
MODE key
than 2 seconds
3. PV correction gain
11. Low limit setting in SV limiter
When measurement value
comes an error, set the
correction value (Multiplication)
MODE key
MODE key, return to A
4. Zero point setting for PV correction
12. Control mode setting
When measurement value
comes an error, set the
correction value (Addition)
MODE key
5. Filtre input
CR filter effect is operational on
software when making first-order
lag operation to process value (PV).
MODE key
13. Selection of control type setting
6. Position of decimal point
This function is to shift the most essential
Thermocouple/R.T.D.(Pt100, JPt100)
screens on setting mode into operation mode
as a priority. Please select priority displays
Not required
through priority display setting.
Required
Basic display
Output 1 manipulated value
Current/Voltage
PID,
Refer to Ex.3.
Setting high limit for event Output 1
Not required
0:Type A
1 digit
1:Type B
2 digits
3 digits
MODE key
This function is to enable FUNC key to use as
14. Change of normal or reverse
a specific key, for the following actions selected
7. FUNK key setting (Refer to Ex.2.)
in FUNC key setting belonged to setting mode.
Selectable below
functions
None
Change of digit
RUN/READY
15. Manipulated value for output 1 (%)
Auto-Tuning
Timer
MODE key
8. Key lock setting
Key lock setting for protection
of error operation.
Selectable below functions
None
All lock
Operation mode lock only
Except operation mode
Ordinary PID
MODE key, return to 1
Over shoot protection PID
<When select PID control>
26. Manipulated value for output 2 (%)
16. Setting for PID tuning type
Shows process manipulated
Tunes suitably for
value for output 2, and setting
setting value.
the value on manual control.
Display range : 0.0∼100.0%
Auto-tuning output 1
Anti-reset wind-up take effect for overshooting
by over-integral of PID control action.
Self-tuning output 1
Setting range : Manipulated value
Auto-tuning output 2
Self-tuning output 2
MODE key
Auto-tuning output 1.2
27. Proportional band setting for output 2
Auto-tuning : Select above ・ or and press
Adjusts proportional
FUNC key once. Call off autotuning : press
band.
FUNC key once on operating.
unit:℃
MODE key
(19. To Set multiple of output proportional band)
Low limit∼High limit
0.0 Setting
− 200∼1372
−199.9∼990.0
17. AT coefficient setting
MODE key
〃
− 200∼ 850
−199.9∼850.0
Coefficient is multiplied by
28. Proportional cycle setting for output 2
proportional band value
〃
−
0∼1700
Adjusts proportional
computed at auto-tuning.
〃
cycle time
− 200∼ 400
−199.9∼390.0
MODE key
1∼120 (second)
〃
− 200∼1300
−199.9∼990.0
18. AT sensitivity setting
MODE key
〃
−
0∼1700
〃
−
0∼1800
Sensitivity is set up during ON/OFF
29. High limit setting of manipulated value for output 2
control at auto-tuning, particulary
− 199∼ 500
−199.9∼500.0
For setting of
when PV is fairly unstable.
− 199∼ 500
−199.9∼500.0
manipulated high limit
MODE key
value. (output 2) (%)
−1999∼9999
−199.9∼999.9
19. Proportional band setting for output 1
MODE key
−19.99∼99.99
−1.999∼9.999
Adjusts proportional band
30. Low limit setting of manipulated value for output 2
for output 1 (% per SLL
−1999∼9999
−199.9∼999.9
For setting of
∼SLH)
−19.99∼99.99
manipulated low limit
MODE key
value. (output 2) (%)
−1.999∼9.999
20. Integral time setting
MODE key
−1999∼9999
−199.9∼999.9
−19.99∼99.99
Adjusts integral time
31. Manual reset setting
−1.999∼9.999
0∼3600 (second)
For shifting
proportional band.
MODE key
21. Deviative time setting
MODE key
Adjusts deviative time
32. Dead band Setting
0∼3600 (second)
For heating and
MODE key
cooling control(℃).
22. Proportional cycle setting for output 1
Adjusts proportional
cycle time
1∼120 (second)
MODE key
23. ARW setting (see Ex. 4)
Adjusts ARW by %
0.0∼100.0% (−10.0∼110.0%)
MODE key
24. High limit setting of manipulated value for output 1
For setting of
manipulated high limit
value. (output 1) (%)
MODE key
25. Low limit setting of manipulated value for output 1
For setting of
manipulated low limit
*When output 2
value. (output 1) (%)
is ON/OFF,
MODE key
go to 35.
Merit
Better control result is achieved
as opposed to that of ON/OFF control.
Demerit
Life span of relay is shorter, as output
exists frequently with relay contact .
※ PID constants are automatically reckoned up to write in,
when control begins or SV is altered on self-tuning.
<SET3:Event Output 1>
<SET4:Event Output 2>
▲ KEY
▲
37. Event output 1 setting
47. Event output 2 setting
Control setting mode
EV1 setting mode
EV2 setting mode
Calling display
Calling display
Calling display
▼ KEY
▼
MODE key
MODE key
MODE key
38. Function setting for EV 1
48. Function setting for EV 2
Display of high limit setting
* Current/Voltage
Select below functions.
Select below functions.
of setting value.
「9000」
(Within setting range of Table 1)
PV Event functions
PV Event functions
MODE key
0:None
0:None
1:Deviation high and low limit
1:Deviation high and low limit
Display of low limit setting
* Current/Voltage
2:Deviation high limit
2:Deviation high limit
of setting value.
「−1000」
3:Deviation low limit
3:Deviation low limit
(Within setting range of Table 1)
4:Deviation high and low limit range
4:Deviation high and low limit range
MODE key
5:Absolute value high and low limit
5:Absolute value high and low limit
6:Absolute value high limit
6:Absolute value high limit
7:Absolute value low limit
7:Absolute value low limit
Usable for control mode
8:Absolute value high and low limit range
8:Absolute value high and low limit range
setting
Additional Event functions
Additional Event functions
Control performance
0:
None
0:
None
Non-control performance
1:
EV output hold
1:
EV output hold
2:
2:
(Manipulated value low limiter output)
Stand-by sequence
Stand-by sequence
3:
EV output hold & stand-by sequence
3:
EV output hold & stand-by sequence
Manual control
MODE key
MODE key
MODE key
39. High limit setting for EV 1
49. High limit setting for EV 2
Selectable and switchable below
Set high limit value.
Set high limit value.
control modes.
MODE key
MODE key
40. Low limit setting for EV 1
50. Low limit setting for EV 2
Control
Control output 2
output 1
Set low limit value.
Set low limit value.
0:None
1:PID
1:PID
2:ON/OFF
2:ON/OFF
MODE key
MODE key
3:Event output
41. Control sensitivity setting for EV 1
51. Control sensitivity setting for EV 2
MODE key
Set sensitivity when
Set sensitivity when
。
。
required(C
).
required(C
).
Switchable below
MODE key
MODE key
control output actions.
42. Delay timer setting for EV 1
52. Delay timer setting for EV 2
0:Reverse (Heating)
Set delay timer when
Set delay timer when
1:Normal (Cooling)
required(sec).
required(sec).
MODE key
MODE key
MODE key
43. Abnormal for EV 1
53. Abnormal for EV 2
Shows process manipulated
value for output 1, and setting
For outbreak of sensor
For outbreak of sensor
the value on manual control.
and heater abnormal
and heater abnormal
Display range : 0.0∼100.0%
(−10.0∼110.0%)
Type
Type
Setting range : Manipulated value
0:None
0:None
low/high limiter
1:PV abnormal (sensor break)
1:PV abnormal (sensor break)
MODE key
2:Heater abnormal
2:Heater abnormal
3:PV + Heater abnormal
3:PV + Heater abnormal
Action
Action
0:None
0:None
1:Hold
1:Hold
(Power reset)
(Power reset)
MODE key
MODE key
44. Polarity setting for EV 1
54. Polarity setting for EV 2
Normal open/close is
Normal open/close is
selectable while event
selectable while event
output is ON.
output is ON.
Normal open
Normal open
(−10.0∼110.0%)
Normal close
Normal close
low/high limiter
MODE key
MODE key
45. CT Input Monitor for EV 1
55. CT Input Monitor or EV 2
Monitors current value
Monitors current value
of heater current
of heater current
detector. 1∼60A
detector. 1∼60A
MODE key
MODE key
46. Abnormal current value of heater for EV 1
56. Abnormal current value of heater for EV 2
Setting for current
Setting for current
value when heater is
value when heater is
abnormal. 1∼30A
abnormal. 1∼30A
MODE key, return to 37
MODE key, return to 47
(Display)
(Description)
Shown whenever input value exceeds the high limit of
display range. Also displays when the wire
thermocouple, ABb terminal of R.T.D is snapped off.
Shown whenever input value exceeds
the low limit of display range.
Display of memory error.
Display of A/D converter error or incorrect sensor
connection with selectable input.
Display of auto-tuning error.
<When select ON/OFF Control>
33. Contorol sensitivity setting for output 1
Displayed when parameter is changed in
Adjusts control sensitivity of
ON/OFF control for output1.
key-lock condition.
MODE key
Alternately this and SV/PV display are shown.
34. OFF position setting for output 1
For setting OFF position of
Displayed when setting value is changed on SV2
control output1.
control.
MODE key
From 25.
Displayed when changing setting value of shift on DI.
35. Contorol sensitivity setting for output 2
Adjusts control sensitivity of
Displayed when making setting value change in
ON/OFF control for output2.
control display while function key is on RUN/READY.
MODE key
36. OFF position setting for output 2
Displayed when altering setting value in control
display while being on timer.
For setting OFF position of
control output2.
MODE key, return to 9
※See also "PARTS INDICATION" & "INSTALLATION AND WIRING" on the reverse.
PID Control
ON/OFF Control
Life span of relay is generally longer,
as it is ON when temperature is below
SV and it is OFF when temperature is
over SV (For heating control).
Control value is worse in comparison
with that of PID control.
TOHO ELECTRONICS INC.
<SET5:Digital Input>
<SET6:Communication>
<SET7:Timer>
▲
▲
▲
57. DI setting
61. Communication setting
67. Timer setting
DI setting mode
Communication setting mode
Timer setting mode
Calling display
Calling display
Calling display
▼
▼
▼
MODE key
MODE key
MODE key
58. Function setting for DI
62. Parameter setting for communication
68. Timer output setting
Select below functions.
Stop bit length
DI action
Non-use
SV
SV2
1 bit
Control output
RUN
READY
2 bit
Event 1 output
AUTO
Manual
Parity check
MODE key
Reverse
Normal
Nil
69. Timer function setting
AT release
AT start
Odd number
Reverse SV
Normal SV2
Even number
Reset
Timer start
Data length
Auto start
(ON delay)
MODE key
7 bit
Manual start
(ON delay)
59. Polarity setting for DI
8 bit
Event start
(ON delay)
Select below polarity.
BCC check
Auto start
(OFF delay)
None
Manual start
(OFF delay)
Close action
Available
Event start
(OFF delay)
Open action
SV start
(OFF delay)
MODE key
MODE key
MODE key
63. Speed setting
60. Setting for SV2
70. Timer unit selection
Displays only when SV2
is selected at DI.(℃)
1200bps
MODE key, return to 57
Hour / minute
2400bps
Minute / second
4800bps
MODE key
9600bps
19200bps
71. Timer SV start permissible range
Thermocouple/R.T.D.(Pt100, JPt100) Input
MODE key
Setting range : 0∼999
64. Address setting
0.0∼999.9
Setting unit : ℃
Setting range : 1∼99
Current/Voltage Input
Setting range : 0∼9999
MODE key
(Decimal point at designated position)
Setting unit : digit
65. Response delay time setting
MODE key
Setting range : 0∼250mS
72. Timer time setting
Setting range : 0:00∼99:59
MODE key
0:00∼59:59
66. Mode selection setting
MODE key
73. Timer residual time monitor setting
Residual time monitor.
R communication
Timer starts when
pressing FUNC key.
RW communication
MODE key, return to 67
MODE key, return to 61
●How to release
BLIND Function
1.
Power ON
Automatically
2.
Initial Display
Automatically
CAUTION
3.
Operation Mode
Press MODE Key (10 sec)
ERROR MESSAGES AND
TROUBLE SHOOTING
4.
Immediately after the "Blink",
press FUNC Key, and quickly
press MODE Key.
Press MODE Key (3 sec)
5.
(Trouble Shooting)
Check the snapping of thermocouple
6.
Press UP Key (△) for 1 7
and R.T.D. input.
Check short circuit of input lines
7.
Press FUNC Key
between A-B and A-b R.T.D.
for OFF
ON
In case this indication shows after the re-
input of power, replace unit if it persists.
8.
Power OFF
Ditto
9.
Power ON
Automatically
Check sensor connection or change to
other tuning.
10.
Initial Display
Automatically
Discontinue to change parameter.
11.
TIMER Setting Mode (OPERATION Mode)
Normality
Press MODE Key (2 sec)
Press UP Key (△) for 1 7
12.
Discontinue to change setting value
(during control of SV2)
Discontinue to change setting value of
13.
Go on TIMER Setting
the self on digital input
Press MODE Key consecutively
Discontinue to change setting value
1
Please select an appropriate charactor (eg. Timer Setting etc) being of
* *
BLIND Function effect for the demanding release.
* *
2
Charactor selected for TIMER Setting.
* *
3
BLIND Function for "SELECTION DISPLAY (Timer Setting Mode)" is released.
Head office: 1-13-21, Tanashioda, Sagamihara Kanagawa 229-1125 Japan.
Phone:
+
81-42-777-3311
E-Mail: info@toho-inc.co.jp
Web site: http://www.toho-inc.co.jp
●Selection memo for
priority displays.
<SET0:Priority Displays>
Display NO. for record,
▲
74. Priority displays setting
1st display
Select priority displays
NO.
Calling display
(Refer to Ex.1.)
▼
MODE key
MODE key
75. Setting for 1st priority display
2nd display
Select 1st display on
NO.
operation mode B.
MODE key
MODE key
76. Setting for 2nd priority display
3rd display
Select 2nd display on
NO.
operation mode B.
MODE key
MODE key
77. Setting for 3rd priority display
4th display
Select 3rd display on
NO.
operation mode B.
MODE key
MODE key
78. Setting for 4th priority display
5th display
Select 4th display on
NO.
operation mode B.
MODE key
MODE key
79. Setting for 5th priority display
6th display
Select 5th display on
NO.
operation mode B.
MODE key
MODE key
80. Setting for 6th priority display
7th display
Select 6th display on
NO.
operation mode B.
MODE key
MODE key
81. Setting for 7th priority display
8th display
Select 7th display on
NO.
operation mode B.
MODE key
MODE key
82. Setting for 8th priority display
9th display
Select 8th display on
NO.
operation mode B.
MODE key
MODE key
83. Setting for 9th priority display
Return to primary display
Select 9th display on
operation mode B.
MODE key, return to 74
eg. Release of Timer Setting
Mode from BLIND Function
before newly its set-up.
taking 4 sec
(Blink once)
1
* *
* *
2
* *
3
taking 4 sec