Installing Drain Hose - Fujitsu ABYA12-24LBTH Installation Manual

Vrf system indoor unit floor / ceiling type
Table of Contents

Advertisement

Silencer pipe
Insulation (pipe)
(Accessories)
CAUTION
• There should be no gaps between the insulation and the
unit.

5. INSTALLING DRAIN HOSE

]
CAUTION
• Install the drain hose in accordance with the instructions
in this Installation Manual and keep the area warm
enough to prevent condensation. Problems with the
piping may lead to water leaks.
Use general hard polyvinyl chloride pipe and connect it with
adhesive (polyvinyl chloride) so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain pipe that matches the size of the drain hose.
• Do not perform a rise, trap and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed, to prevent the pipes
from freezing.
• Install the pipes in a way that allows for the removal of the
control box.
Drain pipe
When using the drain port on the left side of the unit, remove
the drain cap and install it to the right side drain port.
(Only when suspended from the ceiling)
Unit
INSTALL THE DRAIN HOSE
Working procedure
1) Install the attached drain hose to the drain port of the
body. Install the hose band from the top of the hose within
the graphic display area. Secure fi rmly with the hose
band.
2) Use vinyl adhesive agent to glue the drain piping (PVC
pipe VP25) which is prepared on site or piping socket.
(Apply color adhesive agent evenly until the gauge line
and seal)
3) Check the drainage.
4) Install the heat insulation.
5) Use the attached heat insulation to insulate the drain port
and band parts of the body.
No gap
Small pipe
O.D.
32 mm (VP25)
Drain cap
Top view
Drain pan
10~15mm
Drain hose
(Accessories)
Side view
Applying
area of
Hard PVC side
adhesive
Wrap the Drain hose insulation around the drain hose
connection.
Top view
Drain pan
100mm
Drain hose
Hose opening view
Wind the attached heat insulation
around the hose band. Make sure
the alignment is on top.
A. Floor console type
Be sure to arrange the drain hose so that it is leveled lower
than the drain hose connecting port of the indoor unit.
OK
Drain hose
Arrange the drain
hose lower than
this portion.
CAUTION
• Do not install the unit so that the drain hose side is too
high. Height A should be less than 5 mm.
Drain hose
NO GOOD
Ensure there is no space
Hose Band
(Accessories)
Soft PVC side
Joint pipe
(Field supply)
Drain pipe (VP25)
(Field supply)
4 mm or less
Drain hose insulation
(Accessories)
NO GOOD
NO GOOD
NO GOOD
En-9