Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of NOTIFIER. NION™ and UniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation.
Primary Number Account Code (17-20).............. 31 Primary Number 24 Hour Test Time (21-24) ............31 Primary Number 24/12 Hour Test Time Interval (25) ......... 32 Secondary Phone Number (26-41)............... 32 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 6
Lamp Test Mode......................57 Reporting Formats Data Reporting Structure ..................59 Ademco Contact ID....................61 Compatible Receivers UL Listed Receivers ....................65 Appendix A: AFP-100 General ........................67 Mounting ........................67 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 7
For Point Reporting:..................... 88 Zone Assignments...................... 89 Point Assignments ..................... 90 Appendix F: AFC-600 General ........................93 Mounting ........................93 Wiring......................... 93 Connections......................93 Type Mode Programming ..................95 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 8
Mounting ........................121 Wiring........................121 Connections......................121 Appendix L: Annunciators General ........................123 AFP-100, AFP-200, AFP-300/AFP-400 and AFC-600 ........123 System 500 & System 5000 ................123 AM2020/AFP1010/INA ................... 124 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Introduction Overview Introduction This document contains information for installing, programming and operating the UDACT, Universal Digital Alarm Communicator/Transmitter. The table below contains a list of document sources for supplemental information: Control Panels Refer to... Part Number System 500 System 500 Instruction Manual...
The Universal Digital Alarm Communicator/Transmitter (UDACT) may be used with a variety of Notifier control panels. The UDACT transmits system status to UL Listed Central Station Receivers via the public switched telephone network. The UDACT, which is compact in size, mounts internally in some panels or externally in a separate enclosure.
Figure 1 Controls and Indicators Compatible Panels The UDACT has been designed to be compatible with the following “Notifier” Fire Alarm Control Panels. FACP firmware with the listed part numbers or higher (those part numbers beginning with a # are higher than those without) must be installed to allow use of the UDACT with the corresponding panel.
EIA-485 serial interface which is power-limited and supervised by the control panel and the UDACT. The wiring connections are made to the RS +, RS – and Shield terminals of TB1 on the UDACT. The EIA-485 circuit cannot be T-Tapped and must be wired in a continuous fashion from the control panel to the UDACT and, if installed, annunciators.
REN for the calling area. Digital Communicator Before connecting the UDACT to the public switched telephone network, the installation of two RJ31X jacks is necessary. The following information is provided if required by the local telephone company:...
Industry Canada (IC) Compliance - "This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications." IC Registration Number: 2132 6030 A Load Number: 3 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
UDACT troubles are also transmitted. Program Mode Program Mode is used to program the UDACT. While the UDACT is in the program mode, it cannot receive host FACP status information. Refer to “Programming Instructions” on page 29 for complete information.
Modes and Special Functions Clear Function When the clear function is activated, it causes the UDACT to immediately stop transmissions, hang-up from the telephone network and clear out any messages that were waiting for transmission and reset. Manual Test Function The manual test function allows for a test report message to be sent to both Central Stations upon activation.
Installation Options The UDACT is either installed internally in the FACP cabinet or in a remote cabinet. The following table contains information specific to each FACP that is compatible with the UDACT. See "Internal Installation" on page 20 for instructions on internal installation and "Remote Installation" on page 22 for instructions on remote installation.
Page 20
CAUTION: Remove all power from the control panel by disconnecting AC and batteries before installation or making any connections to prevent personal and/or circuit damage. CHS-4/CHS-4MB Chassis Mounting The UDACT is installed on a CHS-4/CHS-4MB Chassis within the control panel backbox as described and shown below: Step Action Disconnect AC power and disconnect batteries.
Page 21
Installation CHS-M2 Chassis Mounting The UDACT is installed on a CHS-M2 Chassis within the control panel backbox as described and shown below: Step Action Disconnect AC power and disconnect batteries. Insert the tab at the bottom of the board into the chassis slot as indicated.
Page 22
Installation Remote Installation For remote installation the UDACT uses either an ABS-8R/RB or UBS-1 enclosure. The unit must be placed within 6000 feet (1828.8 meters) of the Fire Alarm Control Panel. Installation for either enclosure is detailed below: Step Action Align the UDACT to the four (4) threaded standoffs at the back of the ABS-8R/RB or UBS-1 enclosure.
Rs– Figure 5 Power Connection Communication Connection The EIA-485 Serial Interface is connected between the Fire Alarm Control Panel and the UDACT using twisted pair, shielded cable. Recommended wire size is 12 AWG (3.25mm ) to 18 AWG (0.75mm For complete information on wiring the UDACT to a specific FACP see the appropriate appendix.
RJ31X style interconnection. (RJ31X jacks must be ordered separately). Note: It is critical that the UDACT be located as the first device on the incoming telephone circuit to properly function. To Premise Phones...
Wiring from the UDACT terminal TB3 to the relay must be in the same room, no more than 20 feet in length, and enclosed in conduit. Wiring from the relay output contacts must remain in the same room as the UDACT.
Page 26
(MR-201/C may be used) Note: FMM-1 Monitor Module is used to supervise Normally Closed output of MR-101/C. On UDACT trouble and Comm Fail, MR-101/C relay contact will open causing FMM-1 to transmit trouble condition to FACP. Figure 9 Monitoring for UDACT Trouble UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. Telephone Connections Nonpower-limited circuits Power-limited circuits Use power-limited source Figure 10 Typical Wiring for UL Power-limited Requirements UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
ENTER STORE you enter information into the UDACT, the digits will scroll across the display from right to left. You are allowed a pause of up to 10 seconds in between each number while entering the code. After pressing key, the UDACT will be in Program Mode and display 00_F. You are allowed up to...
C= look for secondary dial tone for up to 2 seconds (then, dial anyway) D= 3-second pause E= 5-second pause F= end of phone number (Note: F must be entered) UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
ENTER STORE UDACT which identifies the specific zone or point status to the Central Station. All other formats report the number of zones or points that are active but do not identify the specific zone or point. Choose from the list of formats below:...
'E', Contact ID. When selecting the format, note that Ademco Contact ID is the only format in the UDACT which identifies the specific zone or point status to the Central Station. All other formats report the number of zones or points that are active but do not identify the specific zone or point. Choose one...
Note 9. Reports status of up to 2040 points Table 3 Start and End Monitoring Addresses Note: For additional information on the starting and ending addresses, refer to the host FACP Manual. UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
EIA-485 communications bus supervision. Use the receive/transmit entry when annunciators are not installed or when the UDACT receive/transmit function is to be used to supervise the EIA-485 communication bus. For more information on the receive/transmit function, refer to annunciator manuals.
Loop Numbers from one panel to the next need not be sequential; i.e., the Loop Numbers assigned for the UDACT on one AM2020 or NFS-3030 might be 00, 01 or 02 while the Loop Numbers for another FACP might be 10, 11 or 12 or any other set of unused consecutive numbers.
. For example to return to Normal Mode: Press , 6676, ENTER STORE MODE . During Program Mode, if no key is pressed within 10 minutes, the UDACT will ENTER STORE revert to Normal Mode. UDACT Instruction Manual PN 50050:H 09/16/2002...
Primary # Comm. Trouble Secondary Number Restore Code Primary # 485 Comm. Trouble Restore Code Primary # System Off Normal Restore Code Primary # UDACT Off Normal Restore Code Primary # System 24 Hour Test Primary # System 24 Hour Test w/active event Primary # Manual Test Note: Zero entries prevent the transmission of the report to the Central Station.
Secondary # Comm. Trouble Secondary Number Restore Code Secondary # 485 Comm. Trouble Restore Code Secondary # System Off Normal Restore Code Secondary # UDACT Off Normal Restore Code Secondary # System 24 Hour Test Secondary # System 24 Hour Test w/active event Secondary # Manual Test Note: Zero entries prevent the transmission of the report to the Central Station.
127-128 Primary # 485 Comm. Trouble Restore Code 129-130 Primary # System Off Normal Restore Code 131-132 Primary # UDACT Off Normal Restore Code 133-134 Primary # System 24 Hour Test 135-136 Primary # System 24 Hour Test w/active event...
197-198 Secondary # 485 Comm. Trouble Restore Code 199-200 Secondary # System Off Normal Restore Code 201-202 Secondary # UDACT Off Normal Restore Code 203-204 Secondary # System 24 Hour Test 205-206 Secondary # System 24 Hour Test w/active event...
1) Zero entries prevent the transmission of the report to the Central Station. 2) Refer to Contact ID program locations 64 - 68. 3) The identification of the zone/device number is automatically transmitted by the UDACT and is added to the main event code. See Table 5-3 for more information.
1) Zero entries prevent the transmission of the report to the Central Station. 2) Refer to Contact ID program locations 64 - 68. 3) The identification of the zone/device number is automatically transmitted by the UDACT and is added to the main event code. See Table 5-3 for more information.
Start Monitoring Address: Valid entries are 01 through 32. End Monitoring Address: Valid entries are 01 through 32. UDACT Communication Selection: Enter '0' to disable UDACT communication; '1' for zone reporting receive only communication; '2' for zone reporting receive/transmit communication; '3' for point reporting receive only;...
Page 44
'8' for AFP-300/AFP-400; or leave default of '6' for AFP-200; all other entries are invalid. Loop Number: Factory set to '00'. Valid entries are 00 through 97 Device/Zone Number for General Reports: Factory set to '000'. Valid entries are 000 through 999. UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Make/Break Ratio: Leave default of 0. Leave default of 0. AC Loss Reporting Delay: Host Panel ID: Loop Number: Device/Zone Number for General Reports: Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
2532 spells CLEA on a Touch-Tone® phone. Test If the key is pressed three times in rapid succession the UDACT will transmit a test message to TEST both Central Stations. The message reported is the same as the system 24 hour test message for all for- mats except Ademco Contact ID which has a separate test message.
6676 spells NORM on a Touch-Tone® phone. 1st Event This key along with the Up Arrow and Down Arrow keys, are used to display UDACT fault conditions. Press the 1 key at any time to display the first event that occurred.
During a comm fail, the display will show either a PH1 and PH2 or no1 and no2. Power - A green LED that remains on while power is supplied to the UDACT. If this indicator fails to light under normal conditions, service the system immediately.
The UDACT comes with line seizure capability provided for both the primary and secondary telephone line interfaces. Any time that the UDACT needs to make a call to the Central Station, line seizure will disconnect any local premises phones sharing the same telephone line.
Page 53
Table 9. When Ademco Contact ID format is used, the actual zone or point activated is identified in the report. The UDACT comes factory programmed with the reports identified above as item numbers 2, 4, 7, 20, 22 and 25 set to zero, preventing the reports from being transmitted for the pulsed and Ademco Express formats.
Mode causes a transmission of a 'UDACT return to normal' restoral message. Panel OFF Normal Report The UDACT will send a "System off normal" report when the host FACP indicates it has gone ‘OFF Normal’ during various aspects of system programming, on most panels. When the host FACP is returned to normal, restoring the fire protection, the UDACT will report a “System off normal restoral”...
Type Mode Type Mode CAUTION: The UDACT fire protection and reporting capabilities are inactive while in Type Mode. Type Mode may be used to disable reports by zone or point and to identify the specific functionality of each zone or point in the system via Ademco Contact ID format. Factory default for all zones is Fire Alarm.
90-99, use Type Mode entries of '0' or '2' through 'F'. Zone or Point Supervisory A zone or point must be defined as supervisory to allow the UDACT to identify the correct report to transmit to the central station. Follow the programming instructions in the FACP manual to program a zone or point as supervisory.
Transformer Figure 14 Handset/Speaker Connection Lamp Test Mode This will test all system LEDs. The LEDs will stay on for five seconds, then the UDACT will return to Normal Mode. ☛ To perform a Lamp Test, press , then 5267, then...
SSS(S) X SSSS XX2 Abnormal Test Report SSS(S) XA SSSS XAXA2 Table 12 Data Reporting Structure Note: Refer to Table 17 on page 65 for a list of compatible receivers. UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Note: Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or R for New Restore. Note: CCCC, the first C is not transmitted by the UDACT but is printed by the Central Station Receiver printer output. Continued on the next page...
Appendix A: AFP-100 General The UDACT is capable of reporting a maximum of 56 zones or 198 points when used with the AFP-100. For more information on the AFP-100 see the AFP-100 Instruction Manual. Mounting Internal The UDACT can be mounted in the AFP-100 cabinet by following the instructions and referring to the...
Connections With internal installation the EIA-485 circuit and 24VDC are provided directly from the J16 connector. Note: A 120 ohm EOL resistor is not required on the UDACT EIA-485 terminals when it is installed inside the AFP-100 cabinet. For external connections refer to Figure 16 on page 68.
Use Type Mode (refer to "Type Mode" on page 55) to match the function of remaining zones in the system for proper reporting. Zone Zone Function Zone Zone Function Table 18 Table 19 Zone Assignments - AFP-100 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Type of Device Point Type of Device Point Type of Device Point Type of Device Module Loop Module Loop Module Loop Module Loop Table 20 Table 21 Point Assignments - AFP-100 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at fire alarm panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as shown in Figure 17. Note: The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both ends of shield under any circumstance since a ground fault may result.
Page 72
Wiring Below is a remote installation of a UDACT with an AFP-200: Solid Earth To Phone Lines Ground (supervised) Connection Ferrite Core ABS-8R or UBS-1 AFP-200 Circuit Board AFP-200 Cabinet +24V EARTH ACS/TERM Comm FAILURE RS– +24V SHIELD DO NOT USE TERM Rs–...
Note: When selecting burglary zones, modify the general supervisory report at addresses 75-77 and 145-147, to report general burglary. Zone Zone Function Zone Zone Function Zone Zone Function Table 22 Table 23 Zone Assignments - AFP-200 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Appendix C: System 500 General The UDACT is capable of reporting a maximum of 56 zones when used with the System 500. It reports alarms and troubles on inputs and reports only troubles on outputs. Beware of 'gaps' in the reporting of input circuits.
Page 76
Wiring Below is a remote installation of a UDACT with a System 500: Solid Earth To Phone Lines Ground (supervised) Connection Ferrite Cores ABS-8R or UBS-1 System 500 CPU BATT+ BATT – +24V RESET COMMON +24V POWER COMMON +24V MPS-24BPCA...
Use Type Mode (refer to "Type Mode" on page 55) to match the function of remaining zones in the system for proper reporting. Zone Zone Function Zone Zone Function Table 24 Table 25 Zone Assignments - System 500 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Appendix D: System 5000 General The UDACT is capable of reporting a maximum of 120 zones when used with the System 5000. It reports alarms and troubles on inputs and reports only troubles on outputs. Beware of 'gaps' in the reporting of input circuits.
Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at fire alarm panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as shown in Figure 20. Note: The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both ends of shield under any circumstance since a ground fault may result.
Page 81
Below is a remote installation of a UDACT with a System 5000 using an MPS-24B power supply: Solid Earth To Phone Lines Ground Connection (supervised) Ferrite Cores ABS-8R or UBS-1 EIA-485 Interface CPU-5000 +24V RESET COMMON +24V POWER COMMON BATT +...
Use Type Mode (refer to "Type Mode" on page 55) to match the function of remaining zones in the system for proper reporting. Zone Zone Function Zone Zone Function Zone Zone Function Table 28 Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Use chart to carefully identify function of each zone in the system. Take special precaution with any supervisory zones in the system. Use Type Mode (refer to "Type Mode" on page 55) to match the UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 84
Zone Zone Function Zone Zone Function Zone Zone Function Table 31 Table 32 Zone Assignments - System 5000 without AIM-200 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at fire alarm panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as shown in Figure 21. Note: The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both ends of shield under any circumstance since a ground fault may result.
Page 86
Wiring Below is a remote installation of a UDACT with an AFP-300/AFP-400: Solid Earth To Phone Lines Ground (supervised) Connection Ferrite Cores ABS-8R or UBS-1 CPU-300/-400 MPS-400 +24V EARTH ACS/TERM Comm FAILURE RS– CAB-400AA Cabinet +24V SHIELD TERM DO NOT USE Rs–...
CAUTION: Addresses 97 - 100, 197 - 200, 297 - 300, and 397-400 must not be programmed. System 5000 output module addresses are dependent upon module location. Refer to the CAB-B3, CAB-C3 and CAB-400AA illustrations on next page. UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Loop 2, Modules 297 through 299 and Detectors 297 through 299 are omitted. However, when devices are installed on either SLC Loop and the device is in alarm or trouble, the UDACT will transmit the general alarm and general trouble reports if enabled.
Note: When selecting burglary zones, modify the general supervisory report at addresses 75-77 and 145-147, to report general burglary. Zone Zone Function Zone Zone Function Zone Zone Function Table 33 Table 34 Zone Assignments - AFP-300/AFP-400 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Type of Device: Point Type of Device: Point Type of Device: Module Loop 1 Module Loop 1 Module Loop 2 Module Loop 2 Do Not Do Not Program Program Table 35 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 91
Program Program Table 36 Note: Addressable detectors on Loops 1 and 2 may be disabled using Type Mode. The Event Code cannot be altered. Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 92
Note: System 5000 modules may only be disabled using Type Mode. Event Code cannot be altered. Physical location is critical to the point number reported. Refer to Appendix C. Table 38 Point Assignments - AFP-300/AFP-400 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
For mounting instructions see "Remote Installation" on page 22. If the AFC-600 is contained in a CAB-3/4 Series cabinet, then the UDACT may be mounted to a CHS-4 chassis within that cabinet. For mounting instructions see "Internal Installation" on page 20.
Page 94
Wiring Below is a remote installation of a UDACT with an AFC-600: Solid Earth Ground To Phone Lines Ferrite Cores Connection (supervised) ABS-8R or UBS-1 CPU-600 MPS-6 +24V EARTH ACS/TERM Comm FAILURE RS– CAB-600AA Cabinet +24V SHIELD TERM DO NOT USE Rs–...
Note: When selecting burglary zones, modify the general supervisory report at addresses 75-77 and 145-147, to report general burglary. Zone Zone Function Zone Zone Function Zone Zone Function Table 39 Table 40 Zone Assignments UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Type of Device: Point Type of Device: Point Type of Device: Module Loop 1 Module Loop 1 Module Loop 2 Module Loop 2 Table 41 Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 98
Type of Device: Point Type of Device: Point Type of Device: Module Loop 1 Module Loop 1 Module Loop 2 Module Loop 2 Table 42 Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 99
Not Used Table 43 Note: Addressable detectors on Loops 1 and 2 may be disabled using Type Mode. The Event Code cannot be altered. Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 100
Detector Loop 1 Table 44 Note: Addressable detectors on Loops 1 and 2 may be disabled using Type Mode. The Event Code cannot be altered. Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 101
Not Used Table 45 Note: Addressable detectors on Loops 1 and 2 may be disabled using Type Mode. The Event Code cannot be altered. Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 102
Point Assignments Point Assignments continued: Point Type of Device: Point Type of Device: Output Module Output Module Table 46 Table 47 Point Assignments UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Connect only one end of shield: a) shield may be connected to cabinet (earth ground) at fire alarm panel, or b) shield may be connected to TB1 Terminal 5 (Shield) at UDACT as shown in Figure 25. Note: The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both ends of shield under any circumstance since a ground fault may result.
Page 104
Wiring Below is a remote installation of a UDACT with an NFS-640: Solid Earth To Phone Lines Ground (supervised) Ferrite Cores Connection ABS-8R or UBS-1 CPU-640 CPU-640 TB13 24VDC nonresettable power +24V EARTH ACS/TERM Comm FAILURE NFS-640 in RS– +24V...
NCA. Mounting If the UDACT is not mounted in the same cabinet that contains the NCA, it must be mounted remotely in an ABS-8R/RB or UBS-1 enclosure placed within 6000 feet (1828.8 meters) away from the control panel. For mounting instructions see "Remote Installation" on page 22.
Page 108
Wiring Below is a remote installation of a UDACT with an NCA: Solid Earth To Phone Lines Ground (supervised) Ferrite Cores Connection ABS-8R or UBS-1 +24V EARTH ACS/TERM Comm FAILURE RS– +24V SHIELD TERM DO NOT USE Rs– Figure 27 UDACT and NCA in Separate Cabinets...
Type Mode feature (refer to "Type Mode" on page 55). All points greater than 568 can be transmitted only as fire alarm points. For the UDACT to report a supervisory point to the central station, both the FACP and the UDACT must have the point programmed as supervisory.
Page 110
Wiring Below is a remote installation of a UDACT with an AM2020/AFP1010 using an MPS-24A main power supply: Solid Earth Ground To Phone Lines Ferrite Cores Connection (supervised) ABS-8R or UBS-1 EIA-485 Interface SIB-2048 POWER LIMITED BAT + BAT -...
Use the following charts to carefully identify the function of each point in the system. Take special precaution with any supervisory points in the system. For the UDACT to report a supervisory point to the central station, both the FACP and the UDACT must have the point programmed as supervisory. Failure to program the panel or UDACT correctly will result in a fire alarm signal being transmitted to the central station.
Page 112
Point Assignments Continued on the next page... Point Assignments continued: Point Point Point Point Point Function Point Function Point Function Point Function Table 49 Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 113
Point Assignments continued: Point Point Point Point Point Function Point Function Point Function Point Function Table 50 Table 51 Point Assignments - AM2020/AFP1010 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Type Mode feature (refer to "Type Mode" on page 55). All points greater than 568 can be transmitted only as fire alarm points. For the UDACT to report a supervisory point to the central station, both the FACP and the UDACT must have the point programmed as supervisory.
Page 116
Wiring Below is a remote installation of a UDACT with an NFS-3030 using power supplied by the control panel: Wires in conduit To supervised Solid earth phone lines ground CAB-3/4 Series Cabinet EIA-485 (ACS Mode) TB7 on control panel +24V...
Use the following charts to carefully identify the function of each point in the system. Take special precaution with any supervisory points in the system. For the UDACT to report a supervisory point to the central station, both the FACP and the UDACT must have the point programmed as supervisory. Failure to program the panel or UDACT correctly will result in a fire alarm signal being transmitted to the central station.
Page 118
Point Assignments Continued on the next page... Point Assignments continued: Point Point Point Point Point Function Point Function Point Function Point Function Table 53 Continued on the next page... UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 119
Point Assignments Point Assignments continued: Point Point Point Point Point Function Point Function Point Function Point Function Table 54 Table 55 Point Assignments - AM2020/AFP1010 UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Failure to program the panel or UDACT correctly will result in a fire alarm signal being transmitted to the central station. Note: The UDACT does not support voice and burglary options when used with the INA. Refer to the Intelligent Network Annunciator Manual for additional restrictions and more information.
Page 122
Wiring Below is a remote installation of a UDACT with an INA with an MPS-24A main power supply: Solid Earth Ground To Phone Lines Ferrite Cores Connection (supervised) ABS-8R or UBS-1 POWER LIMITED BAT + BAT - +24R COMMON COMMON...
The UDACT is connected to the EIA-485 communication bus. AFM series and LDM series annunciators may also occupy the same bus. Use of a UDACT along with one of the above mentioned annunciators on the same control panel will alter the assignments of the first eight yellow LEDs on the...
AC Fail Notes: Use of a UDACT with the AFP-200, System 500 or System 5000 will not alter the assignment of the first eight red LEDs on the annunciator. The first Red LED annunciates alarms while the next seven Red LEDs are not used.
Page 125
37–38 Firmware Supervisory 37–38 Installation Manual Trouble 37–38 Installation Options Code Alarm panel ID Communication Fault schematic Communication Format 31–32, 36 AFP-400 Communications 25, 62 AFP4R20 Canadian Department of UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Page 126
Lamp Test 15, 57 fault events LDM series fault message letter code letter codes Features Line Seizure Ferrite cores 68, 71, 75, 80, 85, 93, 103, 107, 109, Linear/Sescoa Firmware UDACT Instruction Manual PN 50050:H 09/16/2002 Technical Manuals Online! - http://www.tech-man.com...
Limited Warranty NOTIFIER® warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of NOTIFIER® is to...
Page 132
World Headquarters NOTIFIER is an operation of 12 Clintonville Road Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.notifier.com Technical Manuals Online! - http://www.tech-man.com...
Need help?
Do you have a question about the UDACT and is the answer not in the manual?
Questions and answers