Engineering Guide VertiCool ™ Classic Product Features The VertiCool™ Classic Series of units are splittable, a variety of evaporator air flow patterns for application self-contained, floor mounted, single package units. flexibility. Additionally, the units are available as standard They are available as air-cooled, water-cooled or as configurations or they can be tailored for a specific water source heat pump configurations.
Engineering Guide VertiCool ™ Classic Electrical Data The following sections provides the formulas and the data to calculate the Minimum Circuit Ampacity (MCA) and the Maximum Fuse Size (MOP) for your specific unit configuration. There are a variety of unit configurations. Please make sure to use the correct formulas per your configuration. It must be noted that the formulas refer to the largest motor amps�...
Engineering Guide VertiCool ™ Classic Electrical Data Examples Cooling Only: Package Unit NOTE: Largest motor amps may not always be the compressor� MCA = (1�25 x largest motor amps) + the sum of the remaining motors MOP = (2�25 x largest motor amps) + the sum of remaining motors Dual Compressors RLA = 19�2 each Evap�...
Engineering Guide VertiCool ™ Classic Electrical Data Cooling with Electric Heat: Package Unit NOTE: Largest motor amps may not always be the compressor� Electric Heat On equipment with multiple modes of operation (i�e� cooling or heating), each mode shall be evaluated and whichever load condition provides the highest value shall be used� Use the larger of the following: MCA = (1�25 x largest motor amps) + the sum of the remaining motors or MCA = (Heater FLA + Evap�...
Engineering Guide VertiCool ™ Classic Cabinet Configurations and Unit Drawings Not to Scale For specific unit dimensions, please visit our website at www.unitedcoolair.com/classic-drawings or click here if you are viewing this document electronically� Subject to change without notice. 20.10-TD (0816)
Engineering Guide VertiCool ™ Classic Service Clearance (Plan View) Notes: (a) If evaporator is not ducted, maintain a 24” clearance from the wall for air intake� (b) Control box location may change or it could be located externally� Subject to change without notice. 20.10-TD (0816)
Condensate Drain Pipes: 3/4” IPS Notes: Reference United CoolAir’s Louver and Ducting Guidelines TechTip for proper selection andapplication of wall louvers� You can view it on our website at www�unitedcoolair�com/ tips or click here if you are reading this document electronically�...
Engineering Guide VertiCool ™ Classic BASIC MODEL DESIGNATION EXAMPLE: — — a� “VA”, “VW”, “VHW”, “E”, “BVA”, “BCVA”, “BVW” or “VCW” “VA” Air-Cooled Air Conditioner “VW” Water-Cooled Air Conditioner “VHW” Water Source Heat Pump “E” Evaporator Section only as a prefix to any of the above “BVA”...
Page 33
Engineered to Order LIMITED WARRANTY Authorized Distributor: United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor (labor not included). Maintenance items such as filters and belts are excluded under this limited warranty�...