Page 2
Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits afforded under federal and international copyright and patent laws in its products, including without limitation software, firmware, and documentation. The information in this document is provided for informational use only and is subject to change without notice. Schweitzer Engineering Laboratories, Inc. has approved only the English language document.
List of Tables Table 1 Communication Cables to Connect the SEL-300G Relay to Other Devices ......4 Table 2 SET Command Editing Keystrokes ..................7 Table 3 SEL-300G Relay Contact I/O Viewed by the TAR Command ..........10 Table 4 Serial Port Commands That Clear Relay Data Buffers ............
SEL-300G3 Rear-Panel Drawings for Rack- and Panel-Mount Relays (2U and 3U), Connectorized Version .................. 28 Figure 21 Jumper, Connector, and Major Component Locations on the SEL-300G Main Board (All Models) ..........................30 Figure 22 Jumper, Connector, and Major Component Locations on the SEL-300G Extra I/O Board (Models 0300G_1, Screw-Terminal Block Version)..........
Required Equipment on page 1. Obtain an SEL-300G Relay Instruction Manual To obtain a copy of the SEL-300G Relay Instruction Manual, simply contact the factory using the information provided in Factory Assistance. The SEL-300G Relay Instruction Manual contains additional details on relay operation and settings calculations.
Page 10
Do not apply reverse polarity dc voltage or ac voltage to terminals N'appliquer pas un voltage CC avec polarité inversée ou un voltage CA, sur Z25 and Z26 of SEL-300G Relays rated for 24/48 Vdc applications. les bornes Z35 et Z26 des relais 300G dont la tension d'alimentation Relay failure and permanent power supply damage will result from nominale est 24/48 VCC.
Factory Assistance We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at: Schweitzer Engineering Laboratories, Inc. 2350 NE Hopkins Court Pullman, WA 99163-5603 U.S.A. Tel: +1.509.338.3838 Fax: +1.509.332.7990...
Relay Commissioning Procedure Introduction The procedure below is intended to help you enter settings into an SEL-300G and verify that the relay is properly connected. Steps later in the procedure call for operation of the protected generator at no load, light load, and full load to verify ac connections and take measurements for calculation of 100% stator ground fault protection elements.
Tripping Settings STEP 21 STEP 23 Shut Down Shut Down Clear Relay STEP 8 Generator Generator Data Buffers Connect PC to Relay Figure 1 Relay Commissioning Flowchart (refer to text for detailed instructions) SEL-300G Relay Quick-Start Guide Date Code 20170804...
Relay Commissioning Procedure Commissioning Procedure Step 1. Ensure that dc power is removed from the SEL-300G dc circuits by opening the appropriate dc breaker or removing dc fuses. Step 2. Verify the accuracy and correctness of the ac and dc connections by performing point-to-point continuity checks on the circuits associated with the SEL-300G Relay.
Page 16
Contact SEL for further information on these products. Table 1 Communication Cables to Connect the SEL-300G Relay to Other Devices (Sheet 1 of 2) SEL-300G EIA-232 Serial Connect to Device (Gender Refers to the Device)
62.5 µm core diameter fiber-optic cable with ST connectors Data Terminal Equipment. A corresponding main board jumper must be installed to power the dial-up modem with +5 Vdc (0.5 A limit) from the SEL-300G. See Figure 20 and Table 11. Data Communication Equipment.
Page 18
(Password: ?). The relay will ask up to three times. If the requested password is incorrectly entered three times, the relay closes the ALARM contact for one second and remains at Access Level 0 (“ ” prompt). SEL-300G Relay Quick-Start Guide Date Code 20170804...
Page 19
If changes are made to the Group settings for the inactive setting group, the relay is not disabled while it saves the new settings. The ALARM contact closes momentarily, but the EN LED remains on while the new settings are saved. Date Code 20170804 Quick-Start Guide SEL-300G Relay...
Step 12. Verify relay ac connections. Connect the protective relay ac test signal source to the SEL-300G through the ac protection cabinet wiring. (You may connect directly to the relay, however this does not verify the accuracy of the wiring in the protection cabinet.) Apply rated ac voltage (67 V1n, 120 V11) and current...
IN101, the 87 LED illuminates. Verify inputs IN201 through IN208 of SEL-300G_1 and SEL-300G_Y Relays using TAR 40. When input verification is complete, press the TARGET RESET or EXIT pushbutton to reset the front-panel target LEDs. Date Code 20170804 Quick-Start Guide SEL-300G Relay...
Page 22
Relay Commissioning Procedure Commissioning Procedure Table 3 SEL-300G Relay Contact I/O Viewed by the TAR Command TAR 0 (Front-Panel LEDs) BKR CLOSED LOP 60 TRIP_LED 21/51V TAR 1 (Front-Panel LEDs) 27/59 TAR 31 OOST IN106 1IN105 IN104 IN103 IN102 IN101...
Page 23
Step 22. Calculate settings for the 64G2 element using the measurements taken above and the guidelines shown in Section 2: Relay Element Settings of the SEL-300G Relay Instruction Manual. Using the serial port SET command, enter the newly calculated 64G element settings and add 64G2T to tripping SEL control equations.
SEL-5601 Analytic Assistant. => CHIS Show compressed history. => Show compressed status report. => View/change date OTHER => Event reports => Display active setting group number GROUP => Event summaries/histories EVENTS SEL-300G Relay Quick-Start Guide Date Code 20170804...
Page 25
Change settings =>> STA C Clear self-test status and restart relay =>> SYN R Clear sync-check reports and reset breaker close time average [300G2, 300G3] =>> PAS C Changes Access Level C password Date Code 20170804 Quick-Start Guide SEL-300G Relay...
Secondary Function Primary (see Figure 7) Secondary) Figure 6 SEL-300G Front-Panel Pushbuttons—Overview Primary Functions Note in Figure 7 and Figure 8 that the front-panel pushbutton primary functions correspond to serial port commands—both retrieve the same information or perform the same function. To get more detail on the information provided by the front-panel pushbutton primary functions, refer to the corresponding serial port commands in Table 5.
* Front-panel pushbutton functions that correspond to Access Level 1 serial port commands do not require the entry of the Access Level 1 password through the front panel. Figure 7 SEL-300G Front-Panel Pushbuttons—Primary Functions Front-Panel Password Refer to the comments at the bottom of Table 8 concerning Access Level B and Access Level 2 passwords.
Local control is not available through the serial port and does not require the entry of a password. DWG: M300G138a Figure 8 SEL-300G Front-Panel Pushbuttons—Primary Functions (continued) Secondary Functions After a primary function is selected (see Figure 7 and Figure 8), the pushbuttons then revert to operating on their secondary functions (see Figure 9).
*Front-panel pushbutton functions that correspond to Access Level 1 serial port commands do not require the entry of the Access Level 1 password through the front panel. DWG: M300G139a Figure 9 SEL-300G Front-Panel Pushbuttons—Secondary Functions Date Code 20170804 Quick-Start Guide...
Step 4. Identify which drawout board needs to be changed. All Equipment components are sensitive to electrostatic discharge (ESD). SEL-300G models have a main board in the top guides, and Undetectable permanent damage can Models 0300G_1 and 0300G_Y have an extra I/O board below result if you do not use proper ESD procedures.
Accessing the Relay Main Board (All Models) and Extra I/O Board (Models 0300G_1 and 0300G_Y) OUT101 OUT102 OUT103 OUT104 OUT105 OUT106 OUT107 JM P2 3 ALARM JMP2 JMP1 DW G: M300G096 Figure 21 Jumper, Connector, and Major Component Locations on the SEL-300G Main Board (All Models) SEL-300G Relay Quick-Start Guide Date Code 20170804...
JMP17 DWG: M30 0G25 7 Figure 23 Jumper, Connector, and Major Component Locations on the SEL-300G Extra I/O Board (Model 0300G_Y, Plug-In Connector Version) Output Contact Table 6 shows the correspondence between output contact jumpers and the output contacts they control. The referenced figures show the exact location Jumpers and correspondence.
OUT212–OUT209 Figure 23 “Extra Alarm” Output All SEL-300G Relays have dedicated alarm output contacts (labeled ALARM—see Figure 12 through Figure 19). Often more than one alarm Contact Control output contact is needed for such applications as local or remote annunciation, Jumper backup schemes, etc.
Table 11 EIA-232 Serial Port Voltage Jumper Positions for Standard Relay Shipments EIA-232 Serial Port 2 EIA-232 Serial Port 3 Reference Figures (rear panel) (rear panel) JMP2 = OFF JMP1 = OFF Figure 21 SEL-300G Relay Quick-Start Guide Date Code 20170804...
Note: 24, 48, 125, 220, and 250 Vdc optoisolated inputs draw approximately 5 mA of current and 110 Vdc inputs draw Range: 18–60 Vdc polarity dependent approximately 8 mA of current. All current ratings are at nominal Burden: <25 W input voltages. Date Code 20170804 Quick-Start Guide SEL-300G Relay...
Page 48
Conducted Radio Frequency: ENV 50141:1993 10 V/m 5 A Model IEC 61000-4-6:1996 Reach: 0.1–100.0 ohms [EN 61000-4-6:1996] Offset: 0.0–10.0 ohms 10 V/m, IEC 60255-22-6:2001 10 Steady-State Impedance Accuracy: ±5%, ±0.1 ohm Minimum Phase Current: 0.5 A SEL-300G Relay Quick-Start Guide Date Code 20170804...
Page 49
5 A Model: 0.25–100.00 Maximum Transient Angle Accuracy: ±1.8 • slip°, ±0.5° 1 A Model: 0.05–20.00 Steady-State Pickup Accuracy: 5 A Model: ±0.05 A, ±3% 1 A Model: ±0.01 A, ±3% Transient Overreach: ±5% of pickup Date Code 20170804 Quick-Start Guide SEL-300G Relay...
Page 50
0.5–500.0 ohms Time-Delay Setting Range: 0.00–3000.00 s Reverse Reach: 0.5–500.0 ohms Note: Desired time delay may be added using SEL control OGIC Single Blinder equation timers. Right Blinder: 0.5–250.0 ohms Left Blinder: 0.5–250.0 ohms SEL-300G Relay Quick-Start Guide Date Code 20170804...
Page 51
±0.1%, ±4.2 ms at 60Hz Currents I 5 A Nominal: ±1 mA or ±0.1% (0.5–10.0 A) 1 A Nominal: ±0.2 mA or ±0.1% (0.1–2.0 A) Temperature Coefficient: [(0.0002%)/(°C) ] • (__°C –20°C) (see following example) Date Code 20170804 Quick-Start Guide SEL-300G Relay...
Page 52
Metering accuracy calculation example for currents I , and I because of preceding stated temperature coefficient: For temperature of 40°C, the additional error for currents I and I [(0.0002%)/(°C) ] • (40°C –20°C) = 0.08% SEL-300G Relay Quick-Start Guide Date Code 20170804...
SEL-300G Quick-Start Guide Differential Element Commissioning Worksheet Differential Element Commissioning Worksheet Date: Installer: RELAY ID (RID): TERMINAL ID (TID): CTR = CTRD = E87 = TRCON = CTCON = With load applied to the relay, use the front panel METER Inst function to find the current quantities (magnitude...
SEL-300G Quick-Start Guide Differential Element Commissioning Worksheet Check List Step 1. Phasor rotation is as expected. Step 2. Circle your transformer and CT connection: Plot Phasors If E87 = G, OR If E87 = T AND TRCON = GEN, CTCON = Y...