M8100 series synchroscope

Advertisement

Quick Links

M8196-72E
M8100 Synchroscope
User Manual
SELCO
Betonvej 11 - DK-4000 Roskilde
Denmark
Phone: 45 7026 1122 - Fax: 45 7026 2522
e-mail:
selco@selco.com
Web site:
www.selco.com
Page 1 of 7

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the M8100.0060 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Selco M8100.0060

  • Page 1 M8196-72E M8100 Synchroscope User Manual SELCO Betonvej 11 - DK-4000 Roskilde Denmark Phone: 45 7026 1122 - Fax: 45 7026 2522 e-mail: selco@selco.com Web site: www.selco.com Page 1 of 7...
  • Page 2: Table Of Contents

    User Manual M8100 Table of contents Preface ............................3 Function ............................3 Connections ..........................3 Adjustments ..........................4 Check synchronizer relay ......................4 Dead bus closure ........................5 4.2.1 Voltage Offset ........................5 4.2.2 Dead busbar delay time ....................5 Specifications ..........................
  • Page 3: Preface

    User Manual M8100 1 Preface This manual describes the M8100 Synchroscope with built-in check synchronizer relay and dead bus closure function. 2 Function The M8100 Synchroscope provides illuminated indication of the actual phase difference between generator voltage and bus voltage. If the vector and the light spot turn clockwise, the generator frequency is too high and must be reduced.
  • Page 4: Adjustments

    User Manual M8100 4 Adjustments On the rear side of the unit are a number of potentiometers and DIP switches for programming of the unit: 4.1 Check synchronizer relay On DIP switch S1 pin 1 the check synchronizer relay can be programmed to offer a constant closing signal that remains activated as long as voltage-, frequency-, and phase difference between generator and busbar voltage are within limits for automatic closure, or a pulse signal of 0,4 or 0,8s.
  • Page 5: Dead Bus Closure

    User Manual M8100 The highest tolerance is adjusted by turning the potentiometer P1 clockwise until end position. Then the limits are as follows: ∆U = 20% ∆f = 0,3Hz ◦ ∆φ = 12 4.2 Dead bus closure This function enables the built-in check synchronizer relay to close the circuit breaker even though there is no voltage on the busbar.
  • Page 6: Specifications

    User Manual M8100 5 Specifications Max. Voltage 660V Voltage range 70 - 110% Consumption 2x 3VA max. Frequency range 35 - 70Hz Pull in / drop out diff. frequency ±9Hz Operating temperature -20°C to +70°C CE according to EN50081-1, EN50082-1, EN50081-2, EN50082-2 Approvals Certified by major classification societies...
  • Page 7: Type Selection Table

    User Manual M8100 6 Type Selection Table Terminals Type Function M8100.0050 450V 400V With check synchronizer relay M8100.0060 230V With check synchronizer relay M8100.0070 480V 415V With check synchronizer relay M8100.0080 110V 100V With check synchronizer relay Other voltages on request.