• Wrap the area which accommodates the rear piping
housing section with vinyl tape.
Connection
pipe
Vinyl tape
(wide)
Connecting cable
Vinyl tape(narrow)
• Bundle the piping and drain hose together by wrap-
ping them with vinyl tape for enough to cover where
they fit into the rear piping housing section.
Wrap with vinyl tape
Pipe
Drain hose
3) Connection of the pipes-Outdoor
1. Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Indoor
unit pipe
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
2. Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow on
the wrench.
Capacity
(Btu/h)
GAS
7K, 8K, 9K
3/8"[4.2kg.m]
11K, 12K, 14K
1/2"[5.5kg.m]
7K~14K
3/8"[4.2kg.m]
Outdoor unit
-25-
Pipe Size[Torque]
LIQUID
1/4"[1.8kg.m]
1/4"[1.8kg.m]
1/4"[1.8kg.m]
Liquid side piping
(Smaller diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
Refrigerant
R-22
R-410A