Bio Module With Static Outputs - ABB REF 542plus Technical Reference Manual

Protection relay
Hide thumbs Also See for REF 542plus:
Table of Contents

Advertisement

REF 542plus
REF 542plus
6.4.2.
46
Multifunction Protection and Switchbay Control
Unit
Technical Reference Manual
6 power outputs (channels
BO 1 to 6)
2 signal outputs (BO7 and
BO8) and 1 watchdog
output (WD)
Optional: 1 static output on
BO7
1 coil supervision circuit on
BO2

BIO module with static outputs

The technical data for the binary input and output module with static outputs are
listed in Table 6.4.2.-1. This module is full range and covers the complete voltage
range from 48 up to 265 VDC.
Table 6.4.2.-1
Technical data for the binary input and output module with
static outputs
14 inputs (BI 1-14)
3 power outputs (BO1,2 and
þ7)
4 power outputs (BO3 ... 6) Operating voltage
2 signal outputs (BO8,9)
and 1 watchdog output
(WD)
2 coil supervision circuits on
BO1 and BO2 channels
Maximum operating voltage
Make current
Load current
Breaking capacity
Operating time
Maximum operating voltage
Load current
Operating time
Maximum operating voltage
Make current
Load current
Operating time
Coil OK when impedance below 10 Ω
Auxiliary voltage range:
Operating voltage
Make current
Load current
Operating time
Make current
Load current
Operating time
Operating voltage
Make current
R
on
R
off
Operating time
Coil OK when impedance below 10 kΩ
1MRS755859
Hardware fixed filter time 1 ms.
Additional filter time can be
configured in software.
250 V AC/DC
8 A
6 A
1 contact 70 W, 2 contacts in
series 130 W at L/R ≤ 40 ms and
10.000 operations
8 ms
250 V AC/DC
2 A
8 ms
250 V DC
1.5 A peak
0.7 A continuous
1 ms
48 to 265 V DC (Threshold 35 V
DC)
Hardware fixed filter time 5 ms.
Additional filter time can be
configured in software.
48 to 250 V DC
64 A
16 A
1 ms
48 to 250 V DC
120 A
31 A
1 ms
48 to 250 V DC
1.5 A (100 ms)
1.06 Ω
40 MΩ
1 ms

Hide quick links:

Advertisement

Table of Contents
loading