Figure 14 Front terminal detail drawing
FRONT
TOP VIEW
(SECTION "B")
FRONT VIEW
(SECTION "B")
See Bus Termination
Detail
Negative Term. Bus (-)
Positive Term. Bus (+)
Ground Bus
(See Detail)
RIGHT SIDE VIEW
NOTES:
1. All dimensions are in in [mm].
2. Top and bottom cable entry available through removable access plates.
3. Control wiring and power wiring must be run in separate conduit.
4. Unless otherwise noted, all cables must be suitable for at least 75°C and
must be copper conductors only.
5. All wiring is to be in accordance with national and local electrical codes.
6. For cabinets ordered as stand-alone, the negative and positive terminal
bus does not extend to full width of battery cabinet.
7. 24" minimum clearance above unit is required for air exhaust and service.
* Doors and covers removed for clarity
(+)
(-)
[ 14]
TYP.
GROUND BUS DETAIL
Ø.56 X .75" SLOT
[Ø14 X 19]
BUS TERMINATION DETAIL
FOR POS. AND NEG. BUSBAR
19
Installation Drawings
.56
1.75
[44]
1.75
[44]
1.75
1.75
[45]
[44]
TYP.
TYP.
®
™
Liebert
NXL
Battery System