22V – 30V DC Mounting The mechanical assembly of the u::Lux NetCon is effected on a 35mm top-hat rail which has to be mounted horizontally. Therefore a flap is provided on the bottom part of the housing. If the flap is pulled forwards (screwdriver) the u::Lux NetCon can be easily placed on the top-hat rail.
Page 4
NetCon / u::Lux NetCon Power - Manual The installation width is 35mm. There are ventilation slots on the top and the bottom of the housing which provide heat exchange. Please note that these vents are not covered and a sufficient distance to adjacent components is kept.
Mounting order 1. u::Lux NetCon or u::Lux NetCon Power must snap into place on the top-hat rail. 2. Connect the network cable (not included in the scope of delivery) for the u::Lux Switch RJ45 to LAN1 or/and LAN2. We recommend the use of a Patchpanel (taking into account the potential equalization) so that a shielded network cable can be lead to ground or to get a better ground-contact from the installation cable to the Patch cable.
A maximum of 2x10 u::Lux Switches RJ45 per u::Lux NetCon Power can be supplied with energy. Therefore 2 units of u::Lux NetCon Power are required for the energy supply of all 40 u::Lux Switches RJ45.
NetCon / u::Lux NetCon Power - Manual Network wiring An u::Lux Switch line may not exceed the total length of 200 m because of the cable resistance (voltage drop). We recommend not exceeding the max. length of 50 m of a single sub segment.
22V - 30V Power consumption: max. 1,5W (without connection of u::Lux Switch RJ45) max. 48 W (with connection of 2 x 10 pieces of u::Lux Switches RJ45) Connections: 1 x supply (+VCC or –VCC, Phoenix MSTB 2,5/ 2-ST-5,08 2 x Ethernet RJ45 jacks with 48V supply (LAN1 and LAN2 -> each via Pins 4+5 [–VCC] and 7+8 [+VCC])
Strictly observe the prevailing accident prevention measures. Failure to observe the installation instructions may result in damage to the device, fire or other dangers. u::Lux NetCon or u::Lux NetCon Power are devices which do not correspond to the PoE standard. CE – marking The CE marking is exclusively addressed to the governmental supervising authorities of the Member States and facilitates the free movement of goods.
NetCon / u::Lux NetCon Power - Manual Version Management Version Date Name Notes 1.00 12.12.2012 Creation of the document 1.01 17.12.2012 THSI Correction/Release 1.02 18.12.2012 Correction/Release 1.03 14.01.2013 Addition (Network connections via patchpanel) 1.04 21.01.2013 Addition (Connections) 1.05 14.01.2014...