INSTALLATION INSTRUCTIONS FOR THE RHEEM H AC ROOFTOP UNIT FEATURING eSYNC™ INTEGRATION TECHNOLOGY RLHL SERIES 10 TON [35.2 kW] INTEGR TION TECHNOLOGY Featuring Industry Standard R-410A Recognize this symbol as an indication of Important Safety Information! DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
I. TABLE OF CONTENTS Read this booklet and any instructions packaged with separate equipment required to make up the system prior to installation. I. Table of Contents ......2 Give this booklet to the owner and explain its provisions.
Units are designed for downflow-only supply and return air and are 2. Quick Reference Guide For R-410A weatherized and intended for outdoor installation. • R-410A refrigerant operates at approximately 60% higher Since the waste-heat recovery/water heating feature of the H pressure (1.6 times) than R-22.
Unit Dimensions (LHL-C120) IMPORTANT: THIS UNIT MUST BE MOUNTED LEVEL IN BOTH DIRECTIONS TO ALLOW WATER TO DRAIN FROM THE CON- DENSER SECTION AND CONDENSATE PAN.
VI. INSTALLATION FIGURE 6 A. GENERAL ROOFTOP INSTALLATION 1. PRE-INSTALLATION CHECK-POINTS Before attempting any installation, the following points should be carefully considered: a. Structural strength of supporting members. (rooftop installation) b. Clearances and provision for servicing. c. Power supply and wiring. d.
D. ROOFTOP INSTALLATION FIGURE 7 1. Before locating the unit on the roof, make sure that the RIGGING FOR LIFTING strength of the roof and beams is adequate at that point to support the weight involved. This is very important CORNER WEIGHTS BY PERCENTAGE and user’s responsibility.
Balancing dampers should be provided for each branch duct in FIGURE 9 the supply system. Ductwork should be properly supported FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING from the structure. DISTRIBUTION SYSTEM. MOUNTED ON ROOFCURB. CURB MUST BE LEVEL When installing ductwork, consider the following items: 1.
X. ELECTRICAL WIRING FIGURE 11 BRANCH CIRCUIT DISCONNECT LOCATION Field wiring must comply with the National Electrical Code ( and local ordinances that may apply. in Canada) A. POWER WIRING 1. This unit incorporates single-point electrical connections for the unit and electric heat accessory. 2.
FIGURE 12 2. The H AC Rooftop unit should be installed as close to the 7. Use the H AC Rooftop Unit Water Flowrate vs. Water storage tank as possible to minimize heat loss from inter- Pressure Drop graph to verify that total system equivalent connecting piping.
Page 24
List all piping components from the storage tank to the H AC rooftop unit and back again. The equivalent length of straight tubing is the same as the actual length. The equivalent length of fittings are obtained from the table below.
Page 25
FIGURE 13 ISOLATION/FLUSHING VALVE Water Flow Rate (GPM) (15 GPM minimum) Water Velocity using 1-1/2” Nom. Type L Copper Tubing (fps) 2.71 3.61 4.51 5.41 Available Pressure Head at Unit @ 230/460 Volts (Head ft.) 30.3 23.8 16.3 (psig) 13.1 10.3 Maximum Equivalent Feet of 1-1/2 Nom.
a higher point than the integral air bleed valve, an addition- Required items: al valve needs to be installed at that point. • Five gallon bucket • Small circulation pump 4. Start unit and verify the correct sequence of operation. •...
XV. PRE-START CHECK XVII. OPERATION COOLING MODE 1. Is unit properly located and slightly slanted toward indoor condensate drain? NOTE: For this two-stage cooling and potable water heating unit, the water heating section is located on the rear (second 2. Is ductwork insulated, weatherproofed, with proper spacing stage) refrigerant system.
F ULTS/LOCKOUTS/MISC. 5. Freeze protection - If ambient is <35°F, water pump is energized until ambient is >37°F. 1. Low-temperature lockout - Occurs at 40°F for the water- cooled condenser (water heating) mode. Unit will only 6. Leak detection - If leak detector senses water, an alarm signal is sent to the thermostat and waterside operation is operate in the air-cooled condenser mode below 40°F.
XXI. TROUBLE SHOOTING CHART WARNING DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH. SYMPTOM POSSIBLE CAUSE REMEDY Unit will not run •...
XXIV. CHARGING CHART RLHL-C120 SYSTEM CHARGE CHART FIGURE 17...
Page 47
RLHL-D120 SYSTEM CHARGE CHART FIGURE 18 SYSTEM CHARGE CHART - REFRIGERANT 410A 10 TON, CIRCUITS 1 & 2 BOTH COMPRESSORS MUST BE OPERATING BEFORE CHECKING REFRIGERANT CHARGE. RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONS BEFORE FINAL REFRIGERANT CHECK! CIRCUIT 1 CIRCUIT 2 92-102259-36-01...
Need help?
Do you have a question about the RLHL SERIES and is the answer not in the manual?
Questions and answers